Instruction Manual
resIdentIal Gas water heaters
power vent/power dIrect vent Gas Models
wIth hot surface IGnItIon
Ashland City, TN 37015
www.hotwater.com
• for Your safety •
AN ODORANT IS ADDED TO THE GAS USED
BY THIS WATER HEATER.
all technIcal and warrantY questIons: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS
PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING.
Keep thIs Manual In the pocKet on heater for future reference
whenever MaIntenance adjustMent or servIce Is requIred.
PRINTED IN THE U.S.A 1208
197835-001
safe InstallatIon, use and servIce
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and
othersof apotentialinjuryhazard. read and obeyallsafetymessagesand instructionsthroughoutthismanual. Itisveryimportant
that the meaning of each safety message is understood by you and others who install, use or service this water heater.
all safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and
how to avoid the risk of injury.
the california safe drinking water and toxic enforcement act requires the Governor of california to publish a list of substances
known to the state of california to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of
potential exposure to such substances.
this product contains a chemical known to the state of california to cause cancer, birth defects, or other reproductive harm. this
appliance can cause low level exposure to some of the substances listed.
IMportant defInItIons
• Qualified Installer or Service Agency: Installation and service of this water heater requires ability equivalent to that
of a Qualified Agency (as defined by ANSI below) in the field involved. Installation skills such as plumbing, air supply,
venting, gas supply, electrical supply are required in addition to electrical testing skills when performing service.
• ANSI Z223.1 2006 Sec. 3.3.83: “Qualified Agency” - “Any individual, firm, corporation or company that either in person
or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping
or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such
work; that is familiar with all precautions required; and that has complied with all the requirements of the authority
having jurisdiction.”.
• Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning
appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of
gas piping up to and including the Natural Gas meter or Propane storage tank of a building.
2
General safetY
3
General safetY
4
taBle of contents
SAFE INSTALLATION, USE AND SERVICE............................2
Installation Sequence......................................................21
Vertical Vent Terminal Installation ...................................21
Installation of Vent System, Sidewall ..............................22
Installation of Vertical Vent System.................................22
Vent Pipe Preparation.....................................................26
Controls and Switches....................................................28
Power Vent Wiring Schematic.........................................29
LIGHTING & OPERATING LABEL.........................................30
TEMPERATURE REGULATION ............................................31
USING THE ELECTRONIC CONTROLLER ..........................32
FOR YOUR INFORMATION...................................................36
Start Up Conditions
Smoke/Odor ............................................................36
Thermal Expansion .................................................36
Strange Sounds ......................................................36
Operational Conditions ...................................................36
Smelly Water...........................................................36
“Air” in Hot Water Faucets.......................................36
PERIODIC MAINTENANCE...................................................37
Venting System Inspection..............................................37
Burner Operation and Inspection....................................37
Burner Cleaning..............................................................37
Housekeeping.................................................................37
Anode Rod Inspection.....................................................38
Temperature-Pressure Relief Valve Operation ...............38
Draining...........................................................................38
Service............................................................................39
LEAKAGE CHECKPOINTS....................................................39
TROUBLESHOOTING ...........................................................40
NOTES............................................................................. 41-42
WARRANTY...........................................................................43
GENERAL SAFETY..................................................................3
TABLE OF CONTENTS............................................................5
INTRODUCTION......................................................................5
Preparing for the Installation.............................................5
Get to Know Your Water Heater........................................6
INSTALLATION CONSIDERATIONS .......................................7
Rough In Dimensions........................................................7
Commonwealth of Massachusetts....................................8
Water Piping - Mixing Valve Usage...................................9
Facts to Consider About Location...................................10
Insulation Blankets..........................................................11
Combustion Air and Ventilation.......................................11
Appliances in Unconfined Spaces...........................11
Appliances in Confined Spaces ..............................11
INSTALLING THE WATER HEATER..................................... 13
Chemical Vapor Corrosion..............................................13
Water Piping ...................................................................13
Temperature-Pressure Relief Valve ................................14
Gas Piping ......................................................................15
Sediment Traps...............................................................16
Filling the Water Heater ..................................................16
Venting............................................................................16
Vent Pipe Termination............................................... 16-17
Planning the Vent System...............................................19
Condensate.....................................................................19
Installation of Vent System..............................................20
Vent Terminal Installation, Sidewall.................................20
Sequence of Installations, Figure 18A ............................20
Direct Venting..................................................................20
Direct Vent Terminal Installation......................................20
IntroductIon
thank You for purchasing this water heater. Properly installed and
maintained, it should give you years of trouble free service.
2. The installation must conform with these instructions and the
local code authority having jurisdiction. In the absence of local
codes, the installation must comply with the current editions of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National
Electrical Code, NFPA70 or CAN/CSA-B149.1, the Natural Gas and
Propane Installation Code and CSA C22.1, the Canadian Electrical
Code. All documents are available from the Canadian Standards
Association, 8501EastPleasantValleyRoad, Cleveland, OH44131.
NFPAdocuments are also available from the National Fire Protection
Association, 1 Batterymarch Park, Quincy, MA 02269.
Abbreviations Found In This Instruction Manual:
• CSA - Canadian Standards Association
• ANSI - American National Standards Institute
• NFPA - National Fire Protection Association
• ASME - American Society of Mechanical Engineers
• GAMA - Gas Appliance Manufacturer’s Association
• UL - Underwriters Laboratories Inc.
3. The water heater when installed must be grounded in accordance
with the local codes, or in the absence of local codes: the National
Electrical Code (NFPA 70) or the Canadian Electrical Code (C22.1).
This gas-fired water heater is design certified by Underwriters
Laboratories Inc. under American National Standard/CSA Standard
for Gas Water Heaters ANSI Z21.10.3 • CSA 4.3 (current edition).
4. If after reading this manual you have any questions or do not
understand any portion of the instructions, call the local gas utility
or the manufacturer whose name appears on the rating plate.
5. Carefully plan the place where you are going to put the water
heater. Correct combustion, vent action, and vent pipe installation
are very important in preventing death from possible carbon
monoxide poisoning and fires, see Figures 1 and 2.
preparInG for the InstallatIon
1. Read the “General Safety” section, page 3 and 4 of this manual
first and then the entire manual carefully. If you don’t follow the
safety rules, the water heater will not operate properly. It could
cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY
DAMAGE.
Examine the location to ensure the water heater complies with
the “Facts to Consider About Location” section in this manual.
6. For California installation this water heater must be braced,
anchored, or strapped to avoid falling or moving during an
earthquake. See instructions for correct installation procedures.
Instructions may be obtained from California Office of the State
Architect, 400 P Street, Sacramento, CA 95814.
This manual contains instructions for the installation, operation,
and maintenance of the gas-fired water heater. It also contains
warnings throughout the manual that you must read and be
aware of. All warnings and all instructions are essential to the
proper operation of the water heater and your safety. Since we
cannot put everything on the first few pages, read the entIre
Manual Before atteMptInG to Install or operate
the water heater.
7. Massachusetts Code requires this water heater to be installed in
accordance with Massachusetts 248-CMR 2.00: State Plumbing
Code and 248-CMR 5.00, See page 8.
8. Complies with SCAQMD rule #1146 and districts having equivalent
NOx requirements.
5
Get to Know Your water heater - Gas Models
a
B
c
d
e
f
G
h
I
control assembly
Blocked Inlet switch
Blocked outlet switch
fan prover switch
Blower assembly
Burner assembly
flame sensor
hot surface Igniter
junction Box
Gas control valve thermostat
display Board
top plastic enclosure
Y
Z
Inlet dip tube
T/P Relief Valve
M
display enclosure
**n exhaust elbow assembly
**o condensate tubing
aa rating plate
BB labels
cc drain valve
**dd vent terminal
ee Metal drain pan
ff anode
GG Insulation
hh upper temperature probe
II
p
q
r
off/on switch
display label
hot water outlet
*S Electrical Outlet (120VAC)
t
u
v
w
X
Gas supply
Main Manual Gas shutoff valve
union
Inlet water shutoff valve
cold water Inlet
j
K
l
access door
replaceMent parts and delIMInG products
Replacement parts and recommended delimer may be ordered through
authorized servicers or distributors. When ordering parts, provide complete
model and serial numbers (see rating plate), quantity and name of part
desired. Standard hardware items may be purchased locally.
access panel
caution: This access panel covers
a 2” NPT plug that was required
during the manufacturing of this
water heater. This 2” NPT flange is
not a cleanout fitting, removing the
2” NPT plug and using this fitting as a
cleanout could void your warranty.
vacuuM relIef
valve
*Install per
local codes
* CAUTION HARNESS HAS 120 VAC. IN OPERATION.
** see “planning the vent system,” “Installation of vent system” and “condensate” for more information.
FIGURE 1.
6
InstallatIon consIderatIons
rouGh In dIMensIons
FIGURE 1A.
rough-In-dimensions
Model Units
Inches 68.50 49.25 22.00 15.75
cm 174 125.09 55.88 40.00
A
B
C
D
E
F
3.00
7.62
8.00
100
20.32
Top/Side Inlet and Outlet: 3/4” NPT
Gas Inlet: 1/2” NPT
capacity, Gas and electrical characteristics
Approximate Capacity
Manifold Pressure
Liters Gas Type “WC kPA
189 Nat./LP 0” 0”
Electrical Characteristics
Model
100
U.S. Gals.
50
Volts/Hz
120/60
Amperes
<5
All models - Maximum Supply Pressure: 14 inches W.C. (3.48kPa)
Minimum Supply Pressure for Natural Gas: 3.50” (.87kPa)
Minimum Supply Pressure for Propane Gas: 8.00” (1.99kPa)
Minimum pressure must be maintained under both load and no load (dynamic and static) conditions.
recovery capacities - u.s. Gallons/hr. and liters/hr. at temperature rise Indicated
Input
Recovery Capacities
Model
100
F
30
17
40
22
50
28
60
33
70
39
80
44
90
50
100
56
110
61
120
67
130
72
140
78
Rating
Rating
(kW)
Temp.
(Btu/hr)
Rise
C
GPH
LPH
387
291
233
882
194
734
166
628
145
549
129
488
116
439
106
401
97
90
83
100,000
29.3
1465 1102
367
341
314
Recovery capacity based on 96% thermal efficiency
7
InstallatIon requIreMents for the coMMonwealth of Massachusetts
For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters
installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned
or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above
finished grade in the area of the venting, including but not limited to decks and porches, the following requirements
shall be satisfied:
InstallatIon of carBon MonoXIde detectors At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up
is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that
a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building
or structure served by the sidewall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure
the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a
battery operated carbon monoxide detector with an alarm shall be installed.
approved carBon MonoXIde detectors Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified.
sIGnaGe A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “Gas vent
dIrectlY Below. Keep clear of all oBstructIons.”
InspectIon The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
eXeMptIons: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA
54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building, or structure used in whole or in part for residential purposes.
Manufacturer requIreMents - Gas equIpMent ventInG sYsteM provIded When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the
equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
Manufacturer requIreMents - Gas equIpMent ventInG sYsteM not provIded When the manufacturer
of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue
gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include
a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or
equipment at the completion of the installation.
8
water pIpInG - MIXInG valve usaGe
* the side recirculation loop connections may not be used as the primary water inlet and outlet connections. for your convenience, plugs are installed
in these fittings at the factory. Remove these plugs if needed for your specific installation. Otherwise (as with all connections) check for leaks while
filling the tank with water and after completing the installation.
FIGURE 2.
This appliance has been design certified as complying with
American National Standard/CSA Standard for water heaters and
is considered suitable for:
HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water. Water heated
to a temperature which will satisfy space heating, clothes
washing, dish washing, and other sanitizing needs can scald
and permanently injure you upon contact. Some people are more
likely to be permanently injured by hot water than others. These
include the elderly, children, and the physically or developmentally
disabled. If anyone using hot water from this heater fits into one
of these groups or if there is a local code or state law requiring
a certain temperature water at the hot water tap, then you must
take special precautions. In addition to using the lowest possible
temperature setting that satisfies your hot water needs, a means
such as a Mixing Valve, should be used at the hot water taps
used by these people or at the water heater, see Figure 2. Mixing
valves are available at plumbing supply or hardware stores.
Consult a Qualified Installer or Service Agency. Follow mixing
valve manufacturer’s instructions for installation of the valves.
Before changing the factory setting on the thermostat, read the
“Temperature Regulation” section in this manual.
Water (Potable) Heating and Space Heating: All models are
considered suitable for water (potable) heating and space heating.
9
facts to consIder aBout the locatIon
Carefully choose an indoor location for the new water heater, because
the placement is a very important consideration for the safety of the
occupants in the building and for the most economical use of the
appliance. this water heater is not for use in manufactured
(mobile) homes or outdoor installation.
Whether replacing an old water heater or putting the water heater in
a new location, the following critical points must be observed:
1. Select a location indoors as close as practical to the vent terminal or
locationtowhichthewaterheaterventpipingisgoingtobeconnected,
and as centralized with the water piping system as possible.
2. Selected location must provide adequate clearances for servicing
and proper operation of the water heater.
Installation of the water heater must be accomplished in such a manner
that if the tank or any connections should leak, the flow will not cause
damage to the structure. For this reason, it is not advisable to install
the water heater in an attic or upper floor. When such locations cannot
be avoided, a suitable metal drain pan should be installed under the
water heater. Drain pans are available at your local hardware store.
Such a drain pan must have a clearance of at least 1.0” (2.5cm)
greater than any point on the water heater’s outer jacket and must
be piped to an adequate drain. The pan must not restrict combustion
air flow. For example, if a circular pan is used, it must be a minimum
of 27” (69cm) in diameter. See Figure 1.
Water heater life depends upon water quality, water pressure and
the environment in which the water heater is installed. Water heaters
are sometimes installed in locations where leakage may result in
property damage, even with the use of a drain pan piped to a drain.
However, unanticipated damage can be reduced or prevented by
a leak detector or water shut-off device used in conjunction with a
piped drain pan. These devices are available from some plumbing
supply wholesalers and retailers, and detect and react to leakage
in various ways:
• Sensors mounted in the drain pan that trigger an alarm or turn off the
incoming water to the water heater when leakage is detected.
• Sensors mounted in the drain pan that turn off the water supply to
the entire building when water is detected in the drain pan.
• Water supply shut-off devices that activate based on the water
pressure differential between the cold water and hot water pipes
connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater while
at the same time shutting off its water supply.
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS
(VAPORS) ARE LIKELY TO BE PRESENT OR STORED
(GARAGES, STORAGE AND UTILITY AREAS, ETC.): Flammable
liquids (such as gasoline, solvents, propane (LP or butane, etc.) and
other substances (such as adhesives, etc.) emit flammable vapors
which can be ignited by a gas water heater’s hot surface igniter or
main burner. The resulting flashback and fire can cause death or
serious burns to anyone in the area.
This water heater must not be installed directly on carpeting.
Carpeting must be protected by metal or wood panel beneath the
appliance extending beyond the full width and depth of the appliance
by at least 3” (7.6 cm) in any direction, or if the appliance is installed
Also, the water heater must be located and/or protected so it is not
subject to physical damage by a moving vehicle.
10
in an alcove or closet, the entire floor must be covered by the panel.
Failure to heed this warning may result in a fire hazard.
for placement on the blanket directly over the existing labels.
• Do inspect the insulation blanket frequently to make certain it
does not sag, thereby obstructing combustion air flow.
coMBustIon aIr and ventIlatIon
Agas water heater cannot operate properly without the correct amount
of air for combustion. Do not install in a confined area such as a closet,
unless you provide air as shown in the “Facts to Consider About
Location” section. Never obstruct the flow of ventilation air. If you have
any doubts or questions at all, call your gas supplier. Failure to provide
the proper amount of combustion air can result in a fire or explosion
and cause death, serious bodily injury, or property damage.
Minimum clearances between the water heater and combustible
construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the front
and 12” (30.5 cm) from the top. (Standard clearance.) If clearances
stated on the heater differ from standard clearances, install water
heater according to clearances stated on the heater.
Adequate clearance 24” (61.0 cm) for servicing this appliance should be
considered before installation, such as changing the anodes, etc.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access to
replaceable parts such as the thermostats, drain valve and relief valve.
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the wall as practicable
and as centralized with the water piping system as possible.
FIGURE 4.
InsulatIon BlanKets
FIGURE 5.
Insulation blankets are available to the general public for external use
on gas water heaters but are not necessary with these products. The
purpose of an insulation blanket is to reduce the standby heat loss
encountered with storage tank heaters. Your water heater meets or
exceeds the Energy Policy Act standards with respect to insulation and
standby loss requirements, making an insulation blanket unnecessary.
If this water heater will be used in beauty shops, barber shops, cleaning
establishments, or self-service laundries with dry cleaning equipment,
it is imperative that the water heater (s) be installed direct vent so that
all air for combustion and ventilation is taken from outdoors.
Propellants of aerosol sprays and volatile compounds, (cleaners,
chlorine based chemicals, refrigerants, etc.) in addition to being highly
flammable in many cases, will also react to form corrosive hydrochloric
acid when exposed to the combustion products of the water heater.
The results can be hazardous, and also cause product failure.
Should you choose to apply an insulation blanket to this heater, you
should follow these instructions (For identification of components
mentioned below, see Figure 1). Failure to follow these instructions
can restrict the air flow required for proper combustion, potentially
resulting in fire, asphyxiation, serious personal injury or death.
applIances In unconfIned spaces
unconfIned space is space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the
aggregate input rating of all appliances installed in that space. Rooms
communicating directly with the space in which the appliances are
installed, through openings not furnished with doors, are considered
a part of the unconfined space.
In unconfined spaces in buildings, infiltration may be adequate to
provide air for combustion, ventilation and dilution of flue gases.
However, in buildings of tight construction (for example, weather
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air
may need to be provided using the methods described in “Appliances
in Confined Space” that follows.”
applIances In confIned spaces
• Do not apply insulation to the top of the water heater, as this will
interfere with safe operation of the blower assembly.
• Do not cover the outer door, thermostat or temperature & pressure
relief valve.
confIned space is a space whose volume is less than 50 cubic
feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input
rating of all appliances installed in that space.
When drawing combustion air from inside a conventionally constructed
building to a confined space, such a space should be provided
with two permanent openings. ONE WITHIN 12 INCHES (30 cm)
OF THE ENCLOSURE TOP AND ONE WITHIN 12 INCHES (30
cm) OF THE ENCLOSURE BOTTOM. Each opening should have
• Do not allow insulation to come within 2” (5.1 cm) of the floor to
prevent blockage of combustion air flow to the burner.
• Do not cover the instruction manual. Keep it on the side of the
water heater or nearby for future reference.
• Do obtain new warning and instruction labels from the manufacturer
11
a free area of one square inch per 1000 Btu/hr (22 cm2/kW) of the
total input of all appliances in the enclosure, but not less than 100
square inches (645 cm2).
enclosure, see Figure 9.
If the confined space is within a building of tight construction, air for
combustion and ventilation must be obtained from outdoors. When
directly communicating with the outdoors or communicating through
vertical ducts, two permanent openings, located in the above manner,
should be provided. Each opening should have a free area of not less
than one square inch per 4000 Btu/hr (5.5 cm2/kW) of total input of all
appliances in the enclosure. If horizontal ducts are used, each opening
should have a free area of not less than one square inch per 2000 Btu/
hr (11cm2/kW) of the total input of all appliances in the enclosure.
a. all aIr froM InsIde BuIldInGs: (See Figure 5 and 6)
The confined space should be provided with two permanent openings
communicating directly with an additional room(s) of sufficient volume
so that the combined volume of all spaces meets the criteria for an
unconfined space. The total input of all gas utilization equipment installed
in the combined space should be considered in making this determination.
Each opening should have a minimum free area of one square inch
per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas
utilization equipment in the confined space, but not less than 100 square
inches (645 cm2). One opening should commence within 12 inches
(30 cm) of the top and one commencing within 12 inches (30 cm) of the
bottom of the enclosures.
FIGURE 8.
4. When ducts are used, they should be of the same cross-sectional area
as the free area of the openings to which they connect. The minimum
short side dimension of rectangular air ducts should not be less than
3 inches (7.6 cm), see Figure 9.
FIGURE 9.
FIGURE 6.
5. Alternatively a single permanent opening may be used when
communicating directly with the outdoors, or with spaces that freely
communicatewiththeoutdoors.Theopeningshould haveaminimum
freeareaof1squareinchper3,000BTUperhour(8.3cm2/kW)oftotal
input rating of all equipment in enclosure. See Figure 9A.
B. all aIr froM outdoors: (See Figures 7, 8 and 9)
The confined space should be provided with two permanent
openings, one commencing within 12 inches (30 cm) of the top and
one commencing within 12 inches (30 cm) from the bottom of the
enclosure. The openings should communicate directly, or by ducts,
with the outdoors or spaces (crawl or attic) that freely communicate
with the outdoors.
1. When directly communicating with the outdoors, each opening should
have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/
kW) of total input rating of all equipment in the enclosure, see Figure 7.
FIGURE 9.
6. Louvers and Grilles: In calculating free area, consideration should be
given to the blocking effect of louvers, grilles or screens protecting openings.
Screens used should not be smaller than 1/4 inch (6.4 mm) mesh. If the free
areathroughadesignoflouverorgrilleisknown,itshouldbeusedincalculating
the size opening required to provide the free area specified. If the design and
free area is not known, it may be assumed that wood louvers will be 20-25
percent free area and metal louvers and grilles will have 60-75 percent free
area.Louversandgrillesshould befixedintheopenpositionorinterlockedwith
the equipment so that they are opened automatically during equipment
operation.
FIGURE 7.
2. When communicating with the outdoors through vertical ducts, each
opening should have a minimum free area of 1 square inch per 4,000
Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the
enclosure, see Figure 8.
7. SpecialConditionsCreatedbyMechanicalExhaustingorFireplaces:
operation of exhaust fans, ventilation systems, clothes dryers or
fireplaces may create conditions requiring special attention to avoid
unsatisfactory operation of installed gas utilization equipment.
3. Whencommunicatingwiththeoutdoorsthroughhorizontalducts,each
opening should have a minimum free area of 1 square inch per 2,000
Btu per hour (11 cm2/kW)) of total input rating of all equipment in the
12
InstallInG the new water heater
closed water sYsteMs
cheMIcal vapor corrosIon
Water supply systems may, because of code requirements or such
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF
AIRFORCOMBUSTIONCONTAINSCERTAINCHEMICALVAPORS.SUCH conditions as high line pressure, among others, have installed devices
CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
such as pressure reducing valves, check valves, and back flow preventers.
Devices such as these cause the water system to be a closed system.
Spray can propellants, cleaning solvents, refrigerator and air
conditioning refrigerants, swimming pool chemicals, calcium and
sodium chloride (water softener salt), waxes, and process chemicals
are typical compounds which are potentially corrosive.
therMal eXpansIon
As water is heated, it expands (thermal expansion). In a closed system
the volume of water will grow when it is heated. As the volume of water
grows there will be a corresponding increase in water pressure due
to thermal expansion. Thermal expansion can cause premature tank
failure (leakage). This type of failure is not covered under the limited
warranty. Thermal expansion can also cause intermittent temperature-
pressure relief valve operation: water discharged from the valve due to
excessive pressure build up. The temperature-pressure relief valve is
not intended for the constant relief of thermal expansion. This condition
is not covered under the limited warranty.
Do not store products of this sort near the heater. Also, air which is
brought in contact with the heater should not contain any of these
chemicals. If necessary, uncontaminated air should be obtained from
remote or outside sources. The limited warranty is voided when failure
of water heater is due to a corrosive atmosphere. (See limited warranty
for complete terms and conditions).
water pIpInG
A properly sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion..
HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water. Water heated to a
temperature which will satisfy space heating, clothes washing, dish
washing, cleaning and other sanitizing needs can scald and permanently
injure you upon contact. Some people are more likely to be permanently
injured by hot water than others. These include the elderly, children, the
physically or developmentally disabled. If anyone using hot water fits into
one of these groups or if there is a local code or state law requiring a
certain temperature water at the hot water tap, then you must take special
precautions. In addition to using the lowest possible temperature setting
that satisfies your hot water needs, a means such as a *mixing valve,
should be used at the hot water taps used by these people or at the water
heater, see Figure 2. Valves for reducing point of use temperature by
mixing cold and hot water are also available:
Consult a Qualified Installer or Service Agency. Follow manufacturer’s
instructions for installation of the valves. Before changing the factory
setting on the thermostat, read the “Temperature Regulation” section in
this manual.
This water heater should not be connected to any heating systems or
component(s) used with a non-potable water heating appliance.
All piping components connected to this unit for space heating
applications should be suitable for use with potable water.
FIGURE 10.
Toxic chemicals, such as those used for boiler treatment should not be
introduced into this system.
note: to protect against untimely corrosion of hot and cold
water fittings, it is strongly recommended that di-electric unions
or couplings be installed on this water heater when connected
to copper pipe, see Figure 2 also.
When the system requires water for space heating at temperatures
higher than required for domestic water purposes, a mixing valve must be
installed. Please refer to Figure 2 for suggested piping arrangement.
13
Figures 2 and 10 show the typical attachment of the water piping to If replaced, the valve must meet the requirements of local codes, but
the water heater. The water heater is equipped with 3/4 inch NPT not less than a combination temperature and pressure relief valve
water connections.
certified as indicated in the above paragraph.
The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water heater
(150 psi = 1,035 kPa) and a discharge capacity not less than the
water heater Btu/hr input rate as shown on the water heater’s
model rating plate.
note: If using copper tubing, solder tubing to an adapter
before attaching the adapter to the water heater connections.
do not solder the water lines directly to the water heater
connections. It will harm the dip tube and damage the
tank.
For safe operation of the water heater, the relief valve must not be
removed from its designated opening nor plugged.
T & P Valve and Pipe Insulation (if supplied)
Remove insulation for T & P valve and pipe connections from
carton.
The temperature-pressure relief valve must be installed directly into
the fitting of the water heater designed for the relief valve. Position
the valve downward and provide tubing so that any discharge will
exit only within 6 inches (15.2 cm) above, or at any distance below
the structural floor. Be certain that no contact is made with any live
electrical part. The discharge opening must not be blocked or reduced
in size under any circumstances. Excessive length, over 30 feet (9.14
m), or use of more than four elbows can cause restriction and reduce
the discharge capacity of the valve, see Figures 10.
No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances
demand. If the discharge pipe is not connected to a drain or other
suitable means, the water flow may cause property damage.
FIGURE 11.
Fit pipe insulation over the incoming cold water line and the
hot water line. Make sure that the insulation is against the top
cover of the heater.Fit T & P valve insulation over valve. Make
sure that the insulation does not interfere with the lever of the
T & P valve.
Secure all insulation using tape.
teMperature-pressure relIef valve
The Discharge Pipe:
• Should not be smallerin size than the outlet pipe size of the valve, or
have any reducing couplings or other restrictions.
• Should not be plugged or blocked.
• Should be of material listed for hot water distribution.
• Should be installed so as to allow complete drainage of both the
temperature-pressure relief valve, and the discharge pipe.
• Should terminate at an adequate drain.
• Should not have any valve between the relief valve and
tank.
This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed equipment of
materials as meeting the requirements for Relief Valves for Hot Water
Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements
of ASME.
14
The temperature-pressure relief valve must be manually
operated at least once a year , see Figure 28. Caution should be
taken to ensure that (1) no one is in front of or around the outlet
of the temperature-pressure relief valve discharge line, and (2)
the water manually discharged will not cause any bodily injury
or property damage because the water may be extremely hot.
hIGh altItude InstallatIons
If after manually operating the valve, it fails to completely reset
and continues to release water, immediately close the cold water
inlet to the water heater, follow the draining instructions, and
replace the temperature-pressure relief valve with a new one.
Gas pIpInG
Rated inputs are suitable up to 10,100 feet (3,079m) elevation. Consult
the factory for installation at altitudes over 10,100 feet (3,079m).
WARNING: THIS HIGH EFFICIENCY WATER HEATER IS CERTIFIED
FOR USE WITHOUT MODIFICATION FOR AN ALTITUDE OF 10,100
FEET (3,079 METERS). INSTALLATIONS ABOVE THESE ALTITUDES
MAY REQUIRE REPLACEMENT OF BURNER ORIFICE. CALL THE
TECHNICAL CENTER AT (800) 527-1953 FOR REQUIREMENTS.
Make sure gas supplied is same type listed on model rating plate. The
inlet gas pressure must not exceed 14 inch water column (3.5 kPa)
for natural and propane gas (L.P.). The minimum inlet gas pressure
shown on rating plate is that which will permit firing at rated input.
Some gas utility companies derate their gas for altitude, making
it unnecessary to install high altitude orifices. Call the local gas or
utility company to verify BTU content.
All gas piping must comply with local codes and ordinances or with the
National Fuel Gas Code (ANSI Z223.1/ NFPA-54) or the Natural
Gas and Propane Installation Code (CAN/CSA B149.1) whichever
applies. Copper or brass tubing and fittings (except tin lined copper
tubing) should not be used.
Due to the input ration reduction at high altitudes, the output rating
of the appliance is also reduced and should be compensated for in
the sizing of the equipment for applications.
If the gas control valve is subjected to pressures exceeding 1/2 psi
(3.5 kPa), the damage to the gas control valve could result in a fire
or explosion from leaking gas.
If the main gas line Shut-off serving all gas appliances is used, also
turn “off” the gas at each appliance. Leave all gas appliances shut
“off” until the water heater installation is complete.
A gas line of sufficient size must be run to the water heater.
Consult the current edition of National Fuel Gas Code
(ANSI Z223.1/NFPA54) or the Natural Gas and Propane Installation
Code (CAN/CSA B149.1) and your gas supplier concerning pipe
size.
Use pipe joint compound or teflon tape marked as being resistant
to the action of petroleum [Propane (L.P.)] gases.
There must be:
The appliance and its gas connection must be leak tested before
placing the appliance in operation.
• A readily accessible manual shut off valve in the gas supply
line serving the water heater, and
The appliance and its individual Shut-off valve should be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 pound per square inch
(3.5 kPa). It should be isolated from the gas supply piping system
by closing its individual manual Shut-off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 pound per square inch (3.5 kPa).
• A drip leg (sediment trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
valve.
• A flexible gas connector or a ground joint union between the
shut off valve and control valve to permit servicing of the
unit.
Be sure to check all the gas piping for leaks before lighting the
water heater. Use a soapy water solution, not a match or open
flame. Rinse off soapy solution and wipe dry.
IMportant: MaKe sure the Gas lIne Is pIped In wIth
hard pIpe. avoId fleX lIne constructIon for Gas due
to possIBle Gas flow proBleMs.
15
sedIMent traps
ventInG
Asediment trap should be installed as close to the gas inlet of the water
heater as practical at the time of water heater installation. The sediment
trap should be either a tee fitting with a capped nipple in the bottom
outlet or other device recognized as an effective sediment trap.
Contaminants in the gas lines may cause improper operation of the
gas control valve that may result in fire or explosion. Before attaching
the gas line be sure that all gas pipe is clean on the inside. To trap any
dirt or foreign material in the gas supply line, a drip leg (sometimes
called a sediment trap) must be incorporated in the piping. The drip
leg must be readily accessible. Install in accordance with the “Gas
Piping” section. Refer to the current edition of the National Fuel
Gas Code (ANSI Z223.1/NFPA 54) or the Natural Gas and Propane
Installation Code (CAN/CSA B149.1).
vent pIpe terMInatIon
fIllInG the water heater
The first step is to determine where the vent pipe will terminate.
See Figures 19, 20, and 21. The vent may terminate through a
sidewall as shown in Figure 19 or through the roof as shown in
Figures 20 and 21.
The vent system must terminate so that proper clearances
are maintained as cited in local codes or the current
edition of the National Fuel Gas Code, (ANSI Z223.1, 12.9.1
through 12.9.4) or the Natural Gas and Propane Installation
Code (CAN/CSA-B149.1).
Never use this water heater unless it is completely full of water. To prevent
damage to the tank, the tank must be filled with water. Water must flow
from the hot water faucet before turning “ON” gas to the water heater.
Instructions on proper installation through a sidewall are provided
in Figures 15A, 15B, 15C, and 15D.
Plan the vent system layout so that proper clearances are
maintained from plumbing and wiring.
To fill the water heater with water:
1. Close the water heater drain valve by turning the handle to the right
(clockwise). The drain valve is on the lower front of the water heater.
2. Open the cold water supply valve to the water heater.
note: the cold water supply valve must be left open when
the water heater is in use.
3. To insure complete filling of the tank, allow air to exit by opening the
nearest hot water faucet. Allow water to run until a constant flow is
obtained. This will let air out of the water heater and the piping.
4. Check all water piping and connections for leaks. Repair as needed.
Vent pipes serving power vented appliances are classified by
building codes as “vent connectors”. Required clearances from
combustible materials must be provided in accordance with
information in this manual under FACTS TO CONSIDER ABOUT
LOCATION and INSTALLING THE WATER HEATER, and with
the National Fuel Gas Code and local codes.
16
u.s. power vent
warnInG
VENT HOOD(S) MAY BE
eXtreMelY hot
durInG operatIon.
FIGURE 15A.
cautIon
to prevent eXhaustInG products froM cIrculatInG to the aIr IntaKe In
wIndY/cold areas, the MaXIMuM practIcal dIstance Between these two
terMInals Is recoMMended.
warnInG
VENT HOOD(S) MAY BE
eXtreMelY hot
canadIan power vent
durInG operatIon.
FIGURE 15B.
17
u.s. dIrect vent
warnInG
VENT HOOD(S) MAY BE
eXtreMelY hot
durInG operatIon.
FIGURE 15C.
cautIon
to prevent eXhaustInG products froM cIrculatInG to the aIr IntaKe In
wIndY/cold areas, the MaXIMuM practIcal dIstance Between these two
terMInals Is recoMMended.
canadIan dIrect vent
warnInG
VENT HOOD(S) MAY BE
eXtreMelY hot
durInG operatIon.
FIGURE 15D.
18
of existing venting system must be performed prior to any installation
work. Verify that correct material as detailed above has been used,
andthattheminimumormaximumventlengthsandterminallocation
as detailed in this manual have been met. Carefully inspect the entire
venting system for any signs of cracks or fractures, particularly at
joints between elbows and other fittings and straight runs of vent
pipe. Check system for signs of sagging or other stresses in joints as
a result of misalignment of any components in the system. If any of
these conditions are found, they must be corrected in accordance with
the venting instructions in this manual before completing installation
and putting the water heater into service.
plannInG the vent sYsteM
Plan the route of the vent system from the exhaust elbow to the
planned location of the vent terminal.
1. Layout total vent system to use a minimum of vent pipe and elbows.
2. This water heater is capable of venting flue gases equivalent to
25’ (7.6 m) of 2” pipe, 65’ (19.8 m) of 3” pipe, or 128’ (39.0 m) of
4” pipe as listed in Table 1.
TABLE 1
Number of
90° Elbows
2” Maximum
Pipe - ft. (m)
20 (6.1)
15 (4.6)
3” Maximum
Pipe - ft. (m)
60 (18.3)
55 (16.8)
50 (15.2)
45 (13.7)
40 (12.2)
35 (10.7)
4” Maximum
Pipe - ft. (m)
120 (36.6)
112 (34.1)
104 (31.7)
96 (29.3)
note: a. For water heaters in locations with high ambient
temperatures (above 100°F) it is recommended that CPVC or
ABS pipe and fittings be used. B. A 22.5 degree elbow (2” vent
pipe) or a 45 degree elbow (3” and 4” vent pipe) with an installed
screen VENT TERMINAL must be used in all cases.
1
2
3
4
5
6
10 (3.0)
--
--
--
4. There will be some installations where condensate will be formed
in the horizontal runs of the vent system. This condensate will
run into the condensate elbow. The water heater is shipped with
a condensate hose that attaches to the condensate elbow. No
other tee or fitting is required.
88 (26.8)
80 (24.3)
The minimum vent lengths for each of the pipe sizes is one 90° plus
2’ (61 cm) of straight pipe and the appropriate termination.
note: The equivalent feet (m) of pipe listed above are exclusive
of the termination. That is, the termination, with an installed
screen, is assumed to be in the system and the remainder of the
system must not exceed the lengths discussed above.
condensate
Thiswaterheaterisacondensingunitandrequiresadraintobelocatedin
close proximity to allow the condensate to drain safely. The condensate
drains from the unit at the exhaust tee located at the bottom of the unit
(see figure 16). Condensate from this water heater is mildly acidic.
Please note that some local codes require that condensate is treated
by using a pH neutralizing filter prior to disposal.
3. The exhaust elbow assembly is designed to accept only straight
sections of 2” pipe. To start, a minimum of 2” (5.1cm) of 2” pipe
must be inserted and glued to the exhaust elbow assembly if
utilizing 3” or 4” vent pipe. Use the same method with the blower
inlet if a direct vent configuration is utilized.
Caution must be used to ensure that the drain is free and clear of debris
and will not allow backflow through the condensate hose. Consideration
must be given to avoid freezing of the condensate lines which could
result in excessive build up of condensate inside the water heater.
Waterproof heat tape may be required to prevent freezing of the condensate
lines. Please ensure that the outlet of the condensate drain does
not create a slippery condition which could lead to personal injury.
If using 2” inch vent pipe:
A minimum of 2” (5.1cm) diameter vent pipe must be attached
to the exhaust elbow assembly. The total system cannot exceed
the lengths discussed above, where each elbow is equal to 5
equivalent feet (1.5m) of straight pipe.
If using 3” or 4” inch vent pipe:
Two inches (5.1cm) of 2” pipe must be attached to the exhaust
elbow assembly before adding a reducer to acquire the desired
pipe diameter. An appropriately sized 45 degree elbow (supplied
locally-a schedule 40 DWV) vent terminal must be obtained with
an equivalent screen (supplied in vent kit). The total system cannot
exceed the equivalent pipe lengths discussed above where each
elbow is equal to 5 feet (1.5m) of straight pipe (3” vent pipe) or 8
feet (2.4m) of straight pipe (4” vent pipe).
u.s. InstallatIons:
note: This unit can be vented with PVC pipe materials (Cellular Core
ASTM-F891; DWV ASTM-D2665 or CSA B181.2; Schedule 40, 80,
120 ASTM-D1785 or CSA B137.3; or SDR Series ASTM-D2241 or
CSA B137.3), CPVC pipe materials (CPVC41 ASTM-D2846 or CSA
B137.6; Schedule 40, 80ASTM-F441 or CSAB137.6; or SDR Series
ASTM-F442), ABS pipe materials (Schedule 40 DWV ASTM-D2661
or CSAB181.1 or Schedule 40 DWV Cellular CoreASTM-F628). The
fittings, other than the TERMINATION should be equivalent to PVC-
DWV fittings meetingASTM D-2665 (Use CPVC fittings,ASTM F-438
for CPVC pipe and ABS fittings, ASTM D-2661/3311 for ABS pipe).
If CPVC or ABS pipe and fittings are used, then proper cement must
be used for all joints, including joining the pipe to Termination (PVC
Material). If local codes do not allow the use of the PVC termination
when a material other than PVC is used for venting, then an equivalent
fitting of that material may be substituted if the screen in the PVC
terminal is removed and inserted into the new fitting.
condensatIon warnInG: thIs water heater IsacondensInG
unItand requIresadraIn to Be located In close proXIMItY
to allow condensate to draIn safelY. the condensate
draIns froM unIt at the eXhaust elBow located at
BottoM of unIt. note: It Is IMportant that the condensate
hose not Be elevated aBove the eXhaust elBow, see
FIGURE 16. CONDENSATE BUILD-UP WILL BLOCK THE EXHAUST
outlet, whIch wIll cause IMproper operatIon.
canadian Installation of this water heater must comply with can/
CSA B149.1 - Natural Gas and Propane Installation Code which
requires the vent system components be certified to ULC S636.
This water heater has been design certified to be vented with PVC
pipe certified and marked as complying with ULC S636. This water
heater is supplied with a 2 inch 22.5 degree termination elbow that is a
special fitting that must be used with the appliance.Any outlet piping,
fittings and glue used to vent this appliance that is not supplied by the
manufacturer must comply with the ULC S636 requirements.
PVC Materials should use ASTM D-2564 Grade Cement; CPVC
Materials should use ASTM F-493 Grade Cement and ABS
Materials should use ASTM D-2235 Grade Cement.
If the water heater is being installed as a replacement for an existing
power vented heater in pre-existing venting, a thorough inspection
FIGURE 16.
19
InstallatIon of vent sYsteM
dIrect ventInG
The air intake provided on the unit contains a mesh screen to prevent
large particles from entering the unit.
Before beginning installation of piping system thoroughly read
the section of this manual VENT PIPE PREPARATION.
If you are installing your system so that it vents through roof,
please refer to section titled INSTALLATION OF VERTICAL
VENT SYSTEM.
vent terMInal InstallatIon, sIdewall
1. Install the vent terminal by using the cover plate as a template
to mark the hole for the vent pipe to pass through the wall.
BEWARE OF CONCEALED WIRING AND PIPING INSIDE
THE WALL.
2. If the Vent Terminal is being installed on the outside of a
finished wall, it may be easier to mark both the inside and
outside wall. Align the holes by drilling a hole through the
center of the template from the inside through to the outside.
The template can now be positioned on the outside wall using
the drilled hole as a centering point for the template.
FIGURE 18B.
WHEN THE UNIT IS TO BE SETUP AS A DIRECT VENT, THE
MESH SCREEN MUST BE REMOVED. THE INLET VENT PIPE
MAY THEN BE GLUED TO THE AIR INTAKE (See Figure 18B)
PROVIDED ON THE UNIT. THE SCREEN REMOVED FROM THE
INTAKE NEEDS TO BE INSERTED INTO THE 2” - 22.5 DEGREE
VENT TERMINAL SUPPLIED IN THE VENT TERMINAL KIT.
3. A) MASONRY SIDE WALLS
Chisel an opening approximately one half inch (1.3 cm) larger
than the marked circle.
B) WOODEN SIDE WALLS
dIrect vent terMInal InstallatIon IMportant
Drill a pilot hole approximately one quarter inch (0.64 cm) outside
of the marked circle. This pilot hole is used as a starting point
for a saws-all or sabre saw blade. Cut around the marked
circle staying approximately one quarter inch (0.64 cm) outside
of the line. (This will allow the vent to easily slide through
the opening. The resulting gap will be covered up by the
Vent Terminal cover plate.) Repeat this step on inside wall if
necessary.
THIS UNIT CONSISTS OF TWO VENT TERMINALS - AN INTAKE
VENTTERMINALANDAN EXHAUST VENTTERMINAL. THE INTAKE
VENT TERMINAL IS A 2” 22.5° PVC ELBOW(-) WITH A MESH WIRE
SCREEN AND THE EXHAUST VENT TERMINAL IS A 2” 22.5° PVC
ELBOW WITH A MESH WIRE SCREEN.
NOTE: TO PREVENT EXHAUSTING PRODUCTS FROM
CIRCULATING TO THE AIR INTAKE IN WINDY/COLD AREAS,
THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO
TERMINALS IS RECOMMENDED.
SEQUENCE OF INSTALLATIONS, FIGURE 18A
Cut a length of PVC pipe about 3.5 inches (8.9 cm) longer than the
wall thickness at the opening. Glue the vent terminal to this
section of pipe. Slide the wall plate over the pipe to stop against
the vent terminal. Place a bead of caulking (not supplied) around
the gap between the pipe and cover plate. Apply enough to
fill some of the gap between the pipe and wall. Place some of
the caulking on the back of the plate to hold it against the wall
after installation. If the vent pipe is installed up to the wall, with
a coupling on the end against the wall opening, the pipe with
the vent terminal can be prepared for gluing before inserting
through the wall. Slide the pipe through the wall and insert
into the coupling on the other side of the wall, making sure that
the vent terminal ends up pointed in the correct position, see
Figure 18A.
FIGURE 18C.
WHEN LOCATING THE TERMINALS ON A SIDEWALL, THE
FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL
LOCATION MUST BE FOLLOWED.
1. The intake air terminal and the exhaust vent terminal must terminate
on the same exterior wall and must be separated by a minimum of
24” (61cm) on vertical centerline (see Figure 18C). In colder climates
increasing the 24” (61cm) minimum will reduce possibility of frost
over from side winds blowing exhaust vapors to the air intake of the
direct vent.
2. The horizontal centerline of the intake air terminal may not be located
lower than the horizontal centerline of the exhaust vent terminal (see
Figure 18C).
VENT TERMINATION - FIGURE 18A.
20
InstallatIon sequence
vertIcal vent terMInal InstallatIon
For installations in the City of Los Angeles, California Category IV
PVC Pipe such as that manufactured by Brownline Pipe Company,
must be used as vent pipe material.
IMportant
when terMInatInG throuGh a roof, the followInG
specIfIcatIons pertaInInG to terMInal locatIon
Must Be followed.
cautIon
vent terMInals supplIed wIth heater Must Be used.
1. Proper support must be provided for all pipe protruding through
NOTE: BEFORE BEGINNING INSTALLATION OF ANY
VENT PIPE READ THE VENT PIPE MANUFACTURER’S
INSTALLATION INSTRUCTIONS.
the roof.
2. The vertical roof terminations should be sealed with a plumbing
roof boot or equivalent flashing.
1. After the points of termination have been determined,
use the cover plates as templates to mark the holes for
the vent pipes to be inserted through the wall. BEWARE OF
CONCEALED WIRING AND PIPING INSIDE OF WALL. If the
vent terminals are being installed on the outside of a finished
wall, it may be easier to mark both the inside and outside
wall. Align the holesby drilling a hole through the center of the
template from the inside through to the outside. The template
can now be positioned on the outside wall using the drilled holes
as a centering point for the template.
3. The intake vent termination and the exhaust vent termination must
penetrate the same side of roof.
4. The center line of the intake vent termination and the center
line of the exhaust vent termination must be no closer
than 24” (61cm).
A.) MASONRY SIDE WALLS Chisel an opening approximately
1/2” (1.3 cm) larger than the marked circle.
5. The intake vent terminal and the exhaust vent terminal must be
oriented facing downward and the same direction.
B.) WOODEN SIDE WALLS Drill a pilot hole approximately
one quarter inch outside of the marked circle. This
pilot hole is used as a starting point for a saws-all or
sabre saw blade. Cut around the marked circle staying
approximately one quarter inch outside of the line.
(This will allow the vent pipe to easily slide through
the opening. The resulting gap will be covered by the
vent terminal cover plates.) Repeat this step on the
inside wall if necessary.
The specifications are displayed in Figures 20 & 21.
NOTE: Exhaust vent terminal is installed using the same
procedure.
2. Cut a length of 3” PVC pipe about 3.5” (8.9 cm) longer than the
wall thickness at the opening.
3. Glue the intake vent terminal to the section of the pipe.
4. Slide the wall plate over pipe to stop against intake vent terminal.
5. Place a bead of caulking (not supplied) around the gap between
the pipe and the wall. Place some of the caulking on the
back of the plate to hold it against the wall after installation.
6. If the vent pipe is installed up to the wall, with a coupling on the
end against the wall opening, the pipe with the vent terminal can
be prepared for gluing before inserting through the wall. Slide the
pipe through the wall and insert into coupling on the other side of
the wall, making sure that the vent terminal ends up pointed in the
correct position (Figure 19).
FIGURE 20.
FIGURE 19.
FIGURE 21.
21
InstallatIon of vent sYsteM, sIdewall
With the route of the venting system and selection of materials completed,
as discussed in the section of this manual titled PLANNING THE VENT
SYSTEM, the through the wall vent terminal in place and the first section
of piping, up to first elbow, installed at the blower it is time to complete the
installation of the venting system for the sidewall installation.
FIGURE 23.
IMportant
The vent system must terminate so that proper clearances are
maintained as cited in local codes or the current edition of the
National Fuel Gas Code (ANSI Z223.1) or the Natural Gas and
Propane Installation Code (CAN/CSA-B149.1) and as listed below:
FIGURE 22.
Before completing the installation of the venting system be sure to read
the sections of this manual discussing the proper method of cutting and
cementing PVC pipe and fittings: VENT PIPE PREPARATION.
1. VentTermination must extend a minimum of 18 inches (46 cm) above
roof or 18 inches (46 cm) above the anticipated snow level to prevent
blockage of the vent termination, as shown in Figures 20 and 21.
It is recommended that the completion of the venting system start at
the blower assembly and run to the coupling on the inside wall of the
vent terminal, Figure 18A.
concentrIc vent InstallatIon
This appliance is certified for concentric venting with concentric vent
kit #9003910105. Follow instructions below for proper installations.
The vent system piping should be supported every 5 feet (1.5 m)
of vertical run and every 3 feet (91 cm) of horizontal run. All piping
and fittings must be joined by the proper procedures as described
under: VENT PIPE PREPARATION.
KIt coMponents
Each kit is comprised of the following:
InstallatIon of vertIcal vent sYsteM
Item
Rain Cap
SDR-26 pipe
SDR-26 pipe
Y Concentric Fitting
Installation Instructions
Description
3 in.
4 in. dia.
2½ in. dia.
3 in.
Qty.
1
1
1
1
A proper flashing or “BOOT” should be used to seal the pipe where it
exits the roof. The total vent system should not exceed the equivalent
feet of pipe as listed in Table 1.
Provide support for all pipe protruding through the roof. All piping
should be properly secured. The vent system piping should be
supported every 5 feet (1.5 m) of vertical run and every 3 feet (91 cm)
of horizontal run. All piping and fittings must be joined by the proper
procedures as described under: VENT PIPE PREPARATION.
194504
1
Field supplied pipe and fittings are required to complete the
installation.
22
This concentric vent termination kit may be used with 3 or 4 inch diameter 1. Determine best location for termination kit.
pipe systems. When connecting to a 4 in. diameter pipe system a 3 x 4 note: roof termination is preferred since it is less
inch field supplied reducer is to be installed at the intake and exhaust susceptible to damage, has reduced chances to intake
connection of the concentric vent termination kit.
contaminants, and less visible vent vapors.
2. Cut 1 hole (5 in. diameter)
safetY consIderatIons
3. Partially assemble concentric vent termination kit.
a) Cement Y concentric fitting to larger diameter kit
pipe, see Figure A.
Installing and servicing water heating equipment can be hazardous due to
gas and electrical components. Installation and service of the concentric
vent termination requires ability equivalent to that of a qualified installer or
service agent, see page 2. All precautions in the literature, on tags, and
labels attached to the unit must be observed.
b) Cement rain cap to smaller diameter kit pipe, see Figure A.
Follow all safety codes. Wear safety glasses and work gloves.
fIGure d.
note: Instead of cementing the smaller pipe to the rain cap, a
field-supplied stainless steel screw may be used to secure the
2 components together when field disassembly is desired for
cleaning, see figure d.
fIGure a.
warnInG
when using alternate screw method, drill clearance hole in rain
cap and pilot hole in vent pipe for screw size being used. failure
to drill adequate holes may cause cracking of pvc components,
allowing combustion products to be recirculated. failure to
follow this warning could result in personal injury or death.
warnInG
do not operate the heater with rain cap removed or recirculation
of combustion products may occur. water may also collect inside
larger combustion-air pipe and flow to the burner enclosure.
failure to follow this warning could result in product damage or
improper operation, personal injury or death.
fIGure B.
4. Install
Y
concentric fitting and pipe assembly through
*
Dimension 21 1/8 in. may be lengthened to 60 in. maximum.
Dimension 21 1/8 in. may also be shortened by cutting the
pipes, provided in the kit, to 12 in. minimum.
structure’s hole and field supplied roof boot/flashing.
** Dimension 39 will change accordingly as dimension
21 1/8 in. is lengthened or shortened.
fIGure c.
fIGure e.
INSTALLATION PROCEDURE 1 ROOF TERMINATION,
see figure c.
note: do not allow insulation or other materials to accumulate
inside pipe assembly when installing through hole.
23
5. Secure assembly to roof structure as shown in Figure E using
field supplied metal strapping or equivalent support material.
NOTE: See the venting information (pages 16-20) in this
manual for additional vent location requirements.
note: ensure termination height is above the roof surface or
anticipated snow level (1 ft. in U.S.A. or 1-1/2 ft. in Canada) as
shown in figure c.
2. Cut 1 hole (5 in. diameter)
3. Partially assemble concentric vent termination kit.
6. Install rain cap and small diameter pipe assembly in
roof penetration assembly, Ensure small diameter pipe
a) Cement the Y concentric fitting to larger diameter
kit pipe, see Figure A.
is cemented and bottomed in
Y
concentric fitting.
7. Cement water heater combustion air intake and vent pipes to
concentric vent termination assembly. See Figure E for
proper pipe attachment.
b) Cement the rain cap to the smaller diameter kit
pipe, see Figure A.
note: Instead of cementing the smaller pipe to the rain cap, a
field-supplied stainless steel screw may be used to secure the
2 components together when field disassembly is desired for
cleaning, see figure d.
8. Operate heater through 1 heat cycle to ensure combustion air
and vent pipes are properly connected to concentric vent termination
connections.
note: all vent terminations must be the same height when
installing multiple unit venting. If assembly is too short to meet
heightrequirement,the2pipessuppliedinthekitmaybereplaced
byusingsamediameter, fieldsuppliedSDR-26PVC(D2241)pipe.
Do not extend the 21-1/8” dimension outer pipe to be more than
60 inches, see Figure B.
warnInG
when using alternate screw assembly method, drill clearance
hole in rain cap and pilot hole in vent pipe for screw being
used. failure to drill adequate holes may cause cracking
of pvc components, allowing combustion products to be
recirculated. failure to follow this warning could result in
personal injury or death.
cautIon
Do not use field-supplied couplings to extend pipes. Airflow
restriction will occur and the heater pressure switch may cause
intermittent operation.
warnInG
do not operate the heater with rain cap removed or
recirculation of combustion products may occur. water may
also collect inside larger combustion-air pipe and flow to the
burner enclosure. failure to follow this warning could result
in product damage or improper operation, personal injury
or death.
PROCEDURE 2 SIDE WALL TERMINATION, see Figure F.
4. Install Y concentric fitting and pipe assembly through
structure’s hole.
note: do not allow insulation or other materials to accumulate
inside pipe assembly when installing through hole.
5. Install rain cap and small diameter pipe assembly in
Y concentric fitting and large pipe assembly. Ensure
small diameter pipe is bottomed and cemented in Y
concentric fitting.
6. Secure assembly to structure as shown in Figure G using field-
supplied metal strapping or equivalent support material.
note: ensure termination location clearance dimensions are as
shown in the diagrams found in Figure 15 A through D. When
extending the length of the 4” pipe, the added length beyond
21-1/8” must be deducted from the maximum equivalent feet of
vent pipe.
fIGure f.
1. Determine best location for termination kit.
NOTE: Consideration for the following should be used when
determining an appropriate location for the termination kit:
note: If assembly needs to be extended to allow side
wall thickness requirement, the 2 pipes supplied in
the kit may be replaced by using same diameter, field-
supplied SDR-26 PVC (D2241) pipe. Do not extend
21 1/8” dimension more than 60 in. (See Figure B.)
•
•
•
•
Termination kit positioned where the vent vapors will
not damage plants/shrubs or air conditioning
equipment.
Termination kit positioned so it will not be affected by
wind eddy that may allow recirculation of combustion
products, or airborne leaves, or light snow.
cautIon
Do not use field-supplied couplings to extend pipes. Airflow
restriction will occur and the heater pressure switch may cause
intermittent operation.
Termination kit positioned where it will not get damaged
or be subjected to foreign objects, such as stones,
balls, etc.
7. Cement heater combustion-air and vent pipes to concentric
vent termination assembly. See Figure G for proper pipe
attachment.
Termination kit positioned where the vent vapors will
not be objectionable.
24
8. Operate heater through 1 heat cycle to ensure combustion-air and
vent pipes are properly connected to concentric vent termination
connections.
figure h.
Concentric Vent Terminations
for Horizontal Direct Venting.
fIGure G.
MultI-concentrIc vent terMInatIons
When two or more appliances are directed vented with concentric
vent terminations near each other, each appliance must be
individually vented. NEVER common vent this appliance. When
two or more appliances are direct vented using concentric vent
terminations, the appliances may be vented as shown in Figure H
and Figure I.
figure I.
Concentric Vent Terminations for Vertical
Direct Venting through a roof.
25
prIMer
vent pIpe preparatIon
1. INITIAL PREPARATION.
It is recommended that Tetrahydrofuran (THF) be used to prepare the
surfaces of pipe and fittings for solvent welding. Do not use water,
rags, gasoline or any other substitutes for cleaning PVC or CPVC
surfaces. A chemical cleaner such as MEK may be used.
A.) Make sure the solvent cement you are planning to use
is designed for the specific application you are attempting.
B.) Knowthephysicalandchemicalcharacteristicsandlimitationsofthe
PVC and CPVC piping materials that you are about to use.
ceMent
The cement should be a bodied cement of approximately 500 to
1600 centipoise viscosity containing 10-20% (by weight) virgin PVC
material solvated with tetrahydrofuran (THF). Small quantities of
dimethyl formamide (DMF) may be included to act as a retarding
agent to extend curing time. Select the proper cement; Schedule 40
cement should be used for Schedule 40 pipe. Never use all-purpose
cements, commercial glues and adhesives orABS cement to join PVC
or CPVC pipe and fittings.
C.) Know the reputation of your manufacturer and their products.
D.) Knowyourownqualificationsorthoseofyourcontractor.Thesolvent
weldingtechniqueofjoiningPVCandCPVCpipeisaspecializedskill
just as any other pipe fitting technique.
E.) Closelysupervisetheinstallationandinspectthefinishedjobbefore
start-up.
F.) Contact the manufacturer, supplier, or competent consulting
agency if you have any questions about the application or
installation of PVC and CPVC pipe.
G.) Take the time and effort to do a professional job. Shortcuts will only
cause you problems and delays in start-up. By far, the majority of
failures in PVC and CPVC systems are the result of shortcuts and/or
improper joining techniques.
2. SELECTION OF MATERIALS.
applIcators
Cutting Device - Saw or Pipe Cutter.
•
Select a suitable pure bristle type paint brush. Use a proper width brush
or roller to apply the primer and cement (see chart below). Speedy
application of cement is important due to its fast drying characteristics.
IMPORTANT NOTE: A dauber type applicator should only be used
on pipe sizes 2” and below. For larger diameter pipe, a brush or roller
must be used.
Deburring Tool, Knife, File, or Beveling Machine (2” and above).
•
Brush - Pure Bristle.
•
Rag - Cotton (Not Synthetic).
•
Primer and Cleaner.
•
RECOMMENDED BRUSH* SIZE FOR PRIMER
and ceMent applIcatIons
Solvent Cement - PVC for PVC Components and CPVC for CPVC
Components.
•
Nominal Pipe (IPS)
Size Brush Width
1.5” (3.8cm)
2
3
Containers - Metal or Glass to hold Primer and Cement. Select the
•
type of PVC or CPVC materials to be used on the basis of their
application with respect to chemical resistance, pressure rating,
temperature characteristics, etc.
1.5”-2.5” (3.8cm - 6.4cm)
*use onlY natural BrIstle
Insertion Tool - Helpful for larger diameter pipe and fittings 6 inches
(15.2cm) and above.
•
3. MAKING THE JOINT.
A.) Cutting Pipe must be squarely cut to allow for the proper
interfacing of the pipe end and the fitting socket bottom. This
can be accomplished with a miter box saw or wheel type cutter
Wheel type cutters are not generally recommended for larger
diameters since they tend to flare the corner of the pipe end. If
this type of cutter is used, the flare on the end must be
completely removed.
NOTE: Power saws should be specifically designed to cut plastic pipe.
step a
26
B. deburring
Use a knife, plastic pipe deburring tool, or file to remove burrs from
the end of small diameter pipe. Be sure to remove all burrs from
around the inside as well as the outside of the pipe. A slight chamfer
(bevel) of about 10°-15° should be added to the end to permit easier
insertion of the pipe into the end of the fitting. Failure to chamfer the
edge of the pipe may remove cement from the fitting socket, causing
the joint to leak.
step B
C. Test dry fit of the joint
step e
Tapered fitting sockets are designed so that an interfaced fit should
occur when the pipe is inserted about 1/3 to 2/3 of the way into the
socket.Occasionally,whenpipefittingdimensionsareatthetolerance
extremes, it will be possible to fully insert dry pipe to the bottom of
the fitting socket. When this happens, a sufficient quantity of cement
must be applied to the joint to fill the gap between the pipe and fitting.
The gap must be filled to obtain a strong, leak-free joint.
f. joint assembly
Working quickly, insert the pipe into the fitting socket bottom and
give the pipe or fitting a 1/4 turn to evenly distribute the cement.
Do not continue to rotate the pipe after it has hit the bottom of the
fitting socket. A good joint will have sufficient cement to make a
bead all the way around the outside of the fitting hub. The fitting
will have a tendency to slide back while the cement is still wet
so hold the joint together for about 15 seconds.
d. Inspection, cleaning, priming
Visually inspect the inside of the pipe and fitting sockets and
remove all dirt, grease or moisture with a clean dry rag. If wiping
fails to clean the surfaces, a chemical cleaner must be used.
Check for possible damage such as splits or cracks and replace
if necessary.
depth-of-entry
Marking the depth of entry is a way to check if the pipe has
reached the bottom of the fitting socket in Step F. Measure
the fitting depth and mark this distance on the pipe O.D. You
may want to add several inches to the distance and make a
second mark as the primer and cement will most likely destroy
your first one.
step f
G. cleanup and joint movement
Remove all excess cement from around the pipe and fitting with a
dry cotton rag. This must be done while the cement is still soft.
The joint should not be disturbed immediately after the cementing
procedure, and sufficient time should be allowed for proper curing
of the joint. Exact drying time is difficult to predict because it
depends on variables such as temperature, humidity and cement
integrity. For more specific information, you should contact your
solvent cement manufacturer.
Apply primer to the surface of the pipe and fitting socket with
a natural bristle brush. This process softens and prepares the
PVC or CPVC for the solvent cementing step. Move quickly and
without hesitation to the cementing procedure while the surfaces
are still wet with primer.
e. application of solvent cement
• Apply the solvent cement evenly and quickly around the
outside of the pipe at a width a little greater than the depth
of the fitting socket.
• Apply a light coat of cement evenly around the inside of the
fitting socket. Avoid puddling.
• Apply a second coat of cement to the pipe end.
step G
27
open. When this switch prevents the unit from igniting, most likely the
exhaust is blocked by some means. Check to see if the condensate
is allowed to flow freely from the exhaust elbow and for obstructions
in the exhaust venting and exhaust vent terminal. Also verify that
the vent length does not exceed the maximum allowed as shown in
the Vent Section of this manual.
controls and swItches
This model is provided with three pressure switches. These switches
are essential to the safe and proper operation of the unit. All switches
are wired in series. The controller is set up to shut the unit down
whenever there is a failure of any of the switches. It is important to
understand the purpose of each switch.
BlocKed IntaKe swItch
(SEE FIGURE 12)
The Blocked Intake Switch is set up to shut the unit off when a
build-up of negative pressure in the intake air pipe occurs. This
switch is a negative pressure switch that requires an increase in
negative pressure to change the electrical contacts from normally
closed to open. The switch is connected to the pressure tap on the
PVC pipe connected to the inlet of the blower. When this switch
prevents the unit from igniting, most likely the intake is blocked.
Verify that the screen on the intake air connection (conventional
vent), the intake air pipe and termination (direct vent installations)
are free of obstructions that may prevent air from entering the unit.
Insure the screen on intake air connection has been removed on
direct vent installations, see Figure 18B. Also verify the intake
air pipe length does not exceed the maximum allowed as shown
in the Vent Section of this manual.
FIGURE 12.
on/off swItch
The ON/OFF Switch is a single-pole, single-throw rocker switch. This
switch provides 120V from the line source to the heater.
Blower prover swItch
(SEE FIGURE 12)
The Blower Prover Switch is provided on the heater to verify that
the fan is operating. It is a positive pressure switch whose electrical
contacts are normally open. When the fan increases the pressure
in the burner, the pressure switch will allow the electrical contacts
to close. The pressure switch is connected to the burner tap by a
piece of tygon tubing. This tubing must be connected in order for
the switch to change the electrical contacts. The controller requires
that the electrical contacts on this air flow switch be open before it
will allow the blower to come on.
cautIon
the water heater Is polarItY sensItIve. Before
applYInG electrIcItY to thIs heater Be certaIn that
supplY neutral wIre to Ground checK IndIcates
ZERO VOLTAGE.
hot surface IGnIter
BlocKed eXhaust swItch
The Hot Surface Igniter is a device that ignites the main burner by
high temperature (>1800°F or >982°C). When 120VAC is applied
to the igniter, sufficient heat is generated to ignite the main burner.
Although improvements have been made to strengthen the igniter,
it is still fragile and care must be taken when handling the igniter to
prevent breakage.
(SEE FIGURE 12)
The Blocked Exhaust Switch is set up to shut the unit off when a
build-up of positive pressure in the exhaust vent pipe occurs. This
switch is a positive pressure switch that requires an increase in
pressure to change the electrical contacts from normally closed to
28
cautIon
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND
DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
THIS WATER HEATER
IS POLARITY SENSITVE.
BEFORE APPLYING
ELECTRICITY TO THIS
HEATER BE CERTAIN
THAT SUPPLY NEUTRAL
WIRE TO GROUND
CHECK INDICATES ZERO
VOLTAGE.
POWER VENT WIRING SCHEMATIC - FIGURE 24.
29
for Your safetY read Before lIGhtInG
warnInG: If you do not follow these instructions exactly, a fire
or explosion may result causing property damage, personal injury or
loss of life.
Before operatInG: entIre sYsteM Must Be fIlled wIth water and aIr purGed froM all lInes.
A. This appliance does not have a pilot. It is equipped with
an ignition device which automatically lights the burner.
do not try to light the burner by hand.
B. Before operatInG smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
what to do If You sMell Gas:
•
If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to push in the gas control buttons.
Never use tools. If the control buttons will not push in, don’t
try to repair them, call a qualified service technician. Force
or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately contact a qualified installer or service
agency to replace a flooded water heater. Do not attempt
to repair the unit! It must be replaced!
•
•
Do not try to light any appliance.
Do not touch any electric switch;
Do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•
operatInG InstructIons
5. This appliance is equipped with a device which
automatically lights the burner.
do not trY to lIGht the Burner BY hand.
UP
Operating Set Point
Status: Heating
120 F
Help
6. Wait five (5) minutes to
gas. If you smell gas,
clear out any
STOP! Follow “B”
OFF
GAS
in the safety information above on this label.
If you don’t smell gas.
O
N
DN
Menu
7. Turn on all electrical power to the appliance.
8. Set the ON/OFF switch on the control box to the
“ON” position.
9. Set the thermostat to the desired setting.
cautIon: hotter water increases the risk
of scald injury. consult the instruction
manual before changing temperature.
on/off swItch
1.
STOP! Read the safety information above,
on this label.
10.If the appliance will not operate, follow the
instructions “TO TURN OFF GAS TO APPLIANCE”
and call your technician or gas supplier.
2. Set the ON/OFF switch on the control panel to
the “ON” position.
3. Set the thermostat to the lowest setting.
warnInG: turn off all electrIc
power Before servIcInG
4. Set the ON/OFF switch on the control box to the
“OFF” position.
to turn off Gas to applIance
1. Set the thermostat to the lowest setting.
2. Set the ON/OFF switch on the control panel to the
“OFF” position.
3. Turn off all electrical power to the appliance if service
is to be performed.
30
teMperature reGulatIon
It is recommended that lower water temperatures be used to avoid
The water temperature is controlled using the Temperature
Control on the Display at the front of the unit (See Figure 1).
This control utilizes a temperature probe to determine the tank
temperature. The primary temperature probe is located at the
top of the tank.
the risk of scalding. It is further recommended, in all cases, that the
water temperatures be set for the lowest temperature which satisfies
your hot water needs. This will also provide the most energy efficient
operation of the water heater.
The temperature may be adjusted from 90°F/32°C to 160°F/71°C.
The thermostat was adjusted to 120°F/49°C before the heater
was shipped from the factory. It is recommended that lower water
temperature be used to avoid the risk of scalding. It is further
recommended, in all cases, that the water temperature be set
for the lowest temperature which satisfies your hot water needs.
This will also provide the most energy efficient operation of the
water heater and minimize scale formation.
Valves for reducing the point-of-use temperature by mixing cold
and hot water are available, see Figure 2. Also available are
inexpensive devices that attach to faucets to limit hot water
temperatures. Contact a licensed plumber or the local plumbing
authority.
The table below shows the approximate time-to-burn relationship for
normal adult skin. Short repeated heating cycles caused by small
hot water uses can cause temperatures at the point of use to exceed
the thermostat setting by up to 20°F/11°C. If you experience this
type of use, you should consider using lower temperature settings
to reduce scald hazards.
HOT WATER CAN SCALD: Water heaters are intended to produce
hot water. Water heated to a temperature which will satisfy space
heating, clothes washing, dish washing, and other sanitizing needs
can scald and permanently injure you upon contact. Some people
are more likely to be permanently injured by hot water than others.
These include the elderly, children, the infirm, or physically/mentally
handicapped. If anyone using hot water from this heater fits into
one of these groups or if there is a local code or state law requiring
a certain temperature water at the hot water tap, then you must
take special precautions. In addition to using the lowest possible
temperature setting that satisfies your hot water needs, a means
such as a mixing valve, should be used at the hot water taps used
by these people or at the water heater. Mixing valves are available
at plumbing supply or hardware stores, see Figure 2. Follow
manufacturer’s instructions for installation of the valves. Before
changing the factory setting on the thermostat, read the “Temperature
Regulation” section in this manual.
time to produce
2nd & 3rd Degree
temperature setting
Burns on adult skin
160°F (71°C)
150°F (65°C)
140°F (60°C)
130°F (54°C)
120°F (49°C)
About 1/2 Second
About 1 1/2 Seconds
Less than 5 Seconds
More than30Seconds
More than5 minutes
Never allow small children to use a hot water tap, or to draw their own
bath water. Never leave a child or handicapped person unattended
in a bathtub or shower.
The water heater should be located in an area where the general
public does not have access. If a suitable area is not available,
a cover should be installed over the thermostat to prevent
tampering. The water temperature setting was factory set at
the lowest temperature; THIS WATER HEATER IS EQUIPPED
WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER
TEMPERATURE. HOT WATER TEMPERATURES REQUIRED
FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN
CAUSE SCALD BURNS RESULTING IN SERIOUS PERSONAL
INJURY AND/OR DEATH. THE TEMPERATURE AT WHICH
INJURY OCCURS VARIES WITH THE PERSON’S AGE AND THE
TIME OF THE EXPOSURE. THE SLOWER RESPONSE TIME
OF CHILDREN, AGED OR DISABLED PERSONS INCREASES
THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN
TO USE A HOT WATER TAP, OR TO DRAW THEIR OWN BATH
WATER. NEVER LEAVE A CHILD OR DISABLED PERSON
UNATTENDED IN A BATHTUB OR SHOWER.
HI LIMIT SWITCH (E.C.O.)
The top immersion well of the dual bulb controller also contains
the high limit (energy cutoff) sensor. The high limit switch
interrupts main burner gas flow should water temperature reach
approximately 202°F/94°C.
Should the high limit switch activate, the control system will
automatically reset the unit once the water temperature in the
tank falls below 140°F/60°C. If the unit is manually shut down
and restarted, as long as the temperature in the tank is lower
than 160°F/71°C, the unit will reset and initiate operation.
If you experience higher than usual water temperature along with
frequent automatic resetting of the system, this is evidence of high
limit switch operation. The following are possible reasons for high
limit switch operation.
•
A malfunction in the thermostatic controls would allow the gas
control valve thermostat to remain open causing water
temperature to exceed the thermostat setting. The water
temperature would continue to rise until high limit
switch operation.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA
WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS TO
SET TEMPERATURES.
SETTING THE WATER HEATER TEMPERATURE AT 120°F/49°C
WILL REDUCE THE RISK OF SCALDS. Some states require
settings at specific lower temperatures.
Contact your dealer or servicer if continued high limit switch
operation occurs.
31
usInG the electronIc controller
1. Overview
Interaction with the water heater controller is done through an up, a down, and three operation buttons. These buttons are illustrated to the
right. Operation of the three lower buttons is defined immediately above them on the screen. The [UP] and [DN] buttons are used to navigate
through the menus and make adjustments to the water heater.
While the water heater is operating, the user interface will display the desktop screen (if there are no active faults or warnings). An
example of this screen is shown to the right. The temperature on this screen is the Operating Set Point. The Operating Set Point is the
temperature at which the water heater will maintain the water inside the tank. The second line on the screen is a text description of the
Operational State of the water heater (please see Operating States for more details).
The following status icons describe graphically operational details of the heater. The legend of all the status icons is listed below.
32
2. Operating States
In the main desktop screen, there are some specific Operating States that
are indicated on the status line. These are summarized below:
actIon:
3. Adjusting the Operating Set Point
From the Main Menu, press select to enter the "Temperatures" screen.
The Operating Set Point of this water heater determines the regulated
temperature for the water in the tank. This parameter is adjusted in the
Temperature menu. Items in this menu allow you to monitor different
temperature readings in the tank along with adjusting the Operating Set
Point.
dIsplaY:
actIon:
From the desktop screen, press Menu.
dIsplaY:
actIon:
Press change then use the up and down buttons to change the Set
Point.
33
3. Changing the Display Units
4. Fault Conditions
The display interface to the heater has the option of selecting between
degrees Fahrenheit and degrees Celsius for temperature displays. This
can be found in the “Display Settings” menu. Also in this menu, you may
adjust how the backlight operates and the contrast of the LCD screen.
This water heater is equipped with electronic controls that have the
ability to monitor almost all aspects of the water heater operation. In
the case that there is an undesirable or unsafe condition that occurs,
the water heater controls will detect this condition and determine the
appropriate action. Part of this is displaying the information on the LCD
in plain text that accurately describes the condition and diagnostics
information that can be used to correct the issue.
actIon:
From the Main Menu, press the Down button to highlight "Display
Settings" then press Select.
• Faults: This is a safety related condition that has been detected
dIsplaY:
by the heater.
NOTE: When these conditions occur, the water heater will not
continue any further heating cycles and the water will no longer be
heated until the condition is corrected and, in most cases, power has
been cycled.
example of a fault:
actIon:
Use the UP and DOWN buttons to highlight the desired setting. Then
press Change. Again, use the UP and DOWN buttons to scroll through
the options for that setting.
dIsplaY:
advanced diagnostics Information
When a fault has been declared, advanced information can be found in
the control. By pressing the Advanced button, detailed information can
be found regarding diagnosing and resolving the problem.
warnInG: usage of the advanced information requires ability
equivalent to that of a licensed tradesmen in the field involved.
5. Access to the Current Fault
When a fault has been detected by the control, it will automatically be
displayed on the screen and the back light will blink. If you choose to leave
the current fault by pressing the Back key, you can always return to the
fault screen through the menu.
actIon:
Press update to accept the change or cancel to reject it.
dIsplaY:
34
actIon:
6. Viewing the Fault History
To get to the current fault information screen, press Menu.
The controller for this water heater will store a history of ten of the
last Fault conditions that occurred. This is stored in the Fault History.
Along with all the information about the fault, including a estimate
time of when the fault occurred, information regarding the advanced
diagnostics for that fault can be accessed at any time.
dIsplaY:
actIon:
Press the down button for more information.
dIsplaY:
actIon:
Press the down button to highlight "current Fault" and press select.
dIsplaY:
actIon:
Press the down key to scroll through the fault history. If you select
a specific fault, you may press the vIew button to view details
regarding this fault.
dIsplaY:
actIon:
Press the down button for more information.
dIsplaY:
7. Viewing Information About the Heater
The electronic control for this water heater monitors many different aspects
of the water to ensure safe and optimal operation. Much of the information
monitored is available to view in two areas of the control. The first is the
"Heater Status" and; the second is "Heater Information." These items
can be selected through the main menu in the same fashion as described
above. In these menus, detailed information about the water heater and
the current status of specific conditions can be found.
35
for Your InforMatIon
start up condItIons
operatIonal condItIons
sMellY water
sMoKe/odor
In each water heater there is installed at least one anode rod (see
parts section) for corrosion protection of the tank. Certain water
conditions will cause a reaction between this rod and the water.
The most common complaint associated with the anode rod is one
of a “rotten egg smell” in the hot water. The smell is a result of four
factors which must all be present for the odor to develop:
It is not uncommon to experience a small amount of smoke and
odor during the initial start-up. This is due to burning off of oil
from metal parts, and will disappear in a short while.
therMal eXpansIon
a. A concentration of sulfate in the supply water.
b. Little or no dissolved oxygen in the water.
c. A sulfate reducing bacteria which has accumulated within the
water heater (this harmless bacteria is nontoxic to humans).
d. An excess of active hydrogen in the tank. This is caused by the
corrosion protective action of the anode.
Smelly water may be eliminated or reduced in some water heater
models by replacing the anode(s) with one of less active material, and
then chlorinating the water heater tank and all water lines. Contact
the local water heater supplier or a qualified service agency for
further information concerning an Anode Replacement Kit and this
chlorination treatment.
Water supply systems may, because of such events as high
line pressure, frequent cut-offs, the effects of water hammer
among others, have installed devices such as pressure
reducing valves, check valves, back flow preventers, etc.
to control these types of problems. When these devices
are not equipped with an internal by pass, and no other
measures are taken, the devices cause the water system
to be closed. As water is heated, it expands (thermal expansion)
and closed systems do not allow for the expansion of
heated water.
If the smelly water persists after the anode replacement and chlorination
treatment, we can only suggest that chlorination or aeration of the
water supply be considered to eliminate the water problem.
do not remove the anode leaving the tank unprotected. By doing
so, all warranty on the water heater tank is voided.
“aIr” In hot water faucets
The water within the water tank expands as it is heated
and increases the pressure of the water system. If the
relieving point of the water heater’s temperature-pressure
relief valve is reached, the valve will release excess pressure. The
temperature-pressure relief valve is not intended for the constant
relief of thermal expansion. This is an unacceptable condition and
must be corrected. It is recommended that any devices
installed which could create a closed system have a
by-pass and/or the system have an expansion tank
or device to relieve the pressure built by thermal
expansion in the water system. Expansion tanks are
a v a i l a b l e f o r o r d e r i n g t h r o u g h
a
l o c a l p l u m b i n g
contractor. Contact the local water heater supplier
or qualified service agency for assistance in controlling these
situations.
HYDROGEN GAS: Hydrogen gas can be produced in a hot water
system that has not been used for a long period of time (generally
two weeks or more). Hydrogen gas is extremely flammable and
explosive. To prevent the possibility of injury under these conditions,
we recommend the hot water faucet, located farthest away, be
opened for several minutes before any electrical appliances
which are connected to the hot water system are used (such as a
dishwasher or washing machine). If hydrogen gas is present, there
will probably be an unusual sound similar to air escaping through the
pipe as the hot water faucet is opened. There must be no smoking
or open flame near the faucet at the time it is open.
stranGe sounds
Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not necessarily
represent harmful or dangerous conditions.
Condensation causes sizzling and popping within the burner area
during heating and cooling periods and should be considered
normal. See “Condensate” in this section.
36
perIodIc MaIntenance
water heater will create dangerous conditions which can cause
ventInG sYsteM InspectIon
DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
Contact a qualified installer or service agency to replace a
flooded water heater. Do not attempt to repair the unit! It must be
replaced!
At least once a year a visual inspection should be made of the
main burner and the hot surface igniter assembly for proper flame
characteristics and ignition sequences. You should also check for
sooting. Soot is not normal and will impair proper combustion. A visual
inspection of the main burner and HSI igniter assembly should also be
done at least once a year.
Soot build-up indicates a problem that requires correction before
further use. Turn “OFF” gas to water heater and leave off until repairs
are made, because failure to correct the cause of the sooting can
result in a fire causing death, serious injury, or property damage.
Burner cleanInG
In the event your burner or burner air openings require cleaning,
turn the on/off switch to the “OFF” position and allow the unit to cool.
Call a qualified service agency to remove and clean the burner and
correct the problem that required the burner to be cleaned.
At least once a year a visual inspection should be made of the venting
system. You should look for:
1. Obstructions which could cause improper venting. The combustion
and ventilation air flow must not be obstructed.
2. Damage or deterioration which could cause improper venting or
leakage of combustion products.
houseKeepInG
Vacuum around base of water heater for dust, dirt, and lint on a
regular basis.
Be sure the vent piping is properly connected to prevent escape of
dangerous flue gasses which could cause deadly asphyxiation.
Obstructions and deteriorated vent systems may present serious
health risk or asphyxiation.
Chemical vapor corrosion of the flue and vent system may occur
if air for combustion contains certain chemical vapors. Spray can
propellants, cleaning solvents, refrigerator and air conditioner
refrigerants, swimming pool chemicals, calcium and sodium chloride,
waxes, bleach and process chemicals are typical compounds which
are potentially corrosive.
If after inspection of the vent system you found sooting or
deterioration, something is wrong. Call the local gas utility to correct
the problem and clean or replace the flue and venting before
resuming operation of the water heater.
Burner operatIon and InspectIon
Flood damage to a water heater may not be readily visible or
immediately detectable. However, over a period of time a flooded
37
INSTALLED IN SUITABLEAREA: To insure sufficient ventilation and
combustion air supply, proper clearances from the water heater must
be maintained. See “Facts to Consider About Location” section.
Combustible materials such as clothing, cleaning materials, or
flammable liquids, etc. must not be placed against or adjacent to
the water heater which can cause a fire.
When checking the temperature-pressure relief valve operation,
make sure that (1) no one is in front of or around the outlet of the
temperature-pressure relief valve discharge line, and (2) that the
water discharge will not cause any property damage, as the water
may be extremely hot, see Figure 28.
If after manually operating the valve, it fails to completely reset and
continues to release water, immediately close the cold water inlet
to the water heater, follow the draining instructions, and replace the
temperature-pressure relief valve with a new one.
anode rod InspectIon
If the temperature-pressure relief valve on the appliance weeps
or discharges periodically, this may be due to thermal expansion.
You may have a check valve installed in the water line or a water
meter with a check valve. Consult your local water supplier or a
qualified service agency for further information. Do not plug the
temperature-pressure relief valve.
The anode rod is used to protect the tank from corrosion. Most hot
water tanks are equipped with an anode rod. The submerged rod
sacrifices itself to protect the tank. Instead of corroding the tank,
water ions attack and eat away the anode rod. This does not affect
the water’s taste or color. The rod must be maintained to keep the
tank in operating condition.
draInInG
Anode deterioration depends on water conductivity, not necessarily
water condition. A corroded or pitted anode rod indicates high water
conductivity and should be checked and/or replaced more often than
an anode rod that appears to be intact. Replacement of a depleted
anode rod can extend the life of your water heater. Inspection should
be conducted by a qualified technician, and at a minimum should be
checked annually after the warranty period.
The water heater should be drained if being shut down during
freezing temperatures. Also periodic draining and cleaning of
sediment from the tank may be necessary.
teMperature-pressure
relIef valve operatIon
1. Set the power switch to the “OFF” position.
2. CLOSE the cold water inlet valve to the water heater.
3. OPEN a nearby hot water faucet and leave open to allow for
draining.
4. Connect a hose to the drain valve and terminate to an adequate
drain.
5. OPEN the water heater drain valve to allow for tank draining.
note: If the water heater is going to be shut down and
drained for an extended period, the drain valve should be
left open with hose connected allowing water to terminate
to an adequate drain.
6. CLOSE the drain valve.
7. Follow instructions in the “Filling The Water Heater” section.
8. Follow the lighting instructions on the label or see “Lighting
Instructions” in this manual to restart the water heater.
FIGURE 28.
38
servIce
If you are not thoroughly familiar with gas codes, your water heater,
and safety practices, contact your gas supplier or qualified installer
If a condition persists or you are uncertain about the operation of
the water heater contact a qualified service agency.
to check the water heater.
Read this manual first. Then before checking the water heater make
sure the gas supply has been turned “OFF”, and never turn the gas
“ON” before the tank is completely full of water.
Use this guide to check a “Leaking” water heater. Many suspected
“Leakers” are not leaking tanks. Often the source of the water can
be found and corrected.
leaKaGe checKpoInts
Never use this water heater unless it is completely filled with water.
To prevent damage to the tank, the tank must be filled with water.
Water must flow from the hot water faucet before turning “ON” gas
to the water heater.
A
*Condensation may be seen on pipes in humid weather or pipe
connections may be leaking.
B. *The anode rod fitting may be leaking.
C. Small amounts of water from temperature-pressure relief valve
may be due to thermal expansion or high water pressure in your
area.
D. *The temperature-pressure relief valve may be leaking at the
tank fitting.
E. Water from a drain valve may be due to the valve being slightly
opened.
F. *The drain valve may be leaking at the tank fitting.
G. Combustion products contain water vapor which can condense
on the cooler surfaces of the tank. Droplets form and drip onto
the burner or run on the floor. This is common at the time of
start-up after installation and when incoming water is cold.
H. Water in the water heater bottom or on the floor may be from
condensation, loose connections, or the relief valve. DO NOT
replace the water heater until a full inspection of all possible water
sources is made and necessary corrective steps taken.
Leakage from other appliances, water lines, or ground seepage
should also be checked.
*
To check where threaded portion enters tank, insert cotton
swab between jacket opening and fitting. If cotton is wet, follow
“Draining” instructions in the “Periodic Maintenance” section and
then remove fitting. Put pipe dope or teflon tape on the threads
and replace. Then follow “Filling the Water Heater” instructions
in the “Installing the New Water Heater” section.
39
trouBleshootInG GuIdelInes
These guidelines should be utilized by a qualified service agent.
proBleMs
1.) Blower will not run.
a. “ON/OFF” control switch turned off.
b. Blower unplugged.
Turn switch to the “ON” position.
Plug blower back into 115 VAC outlet.
Repair service to outlet.
c. No power at outlet.
d. Thermostat defective.
Replace thermostat.
e. Control harness defective.
Replace control harness.
Reduce the water temperature below 140°F.
Turn the power switch to the off position.
Wait 10 seconds. Turn the power switch to
the on position. Reduce the temperature set
point to minimize likelihood of reoccurrence. If
this does not solve the problem, replace the
thermostat.
f. High limit control circuit open.
not enouGh hot water
g. Blower motor defective.
2.) Thermostat problems
a. Thermostat set too low.
b. Thermostat or ECO defective
3.) Others
Replace blower assembly.
Adjust temperature control higher.
Replace thermostat.
a. Heater undersized..
Reduce hot water use.
b. Low gas pressure
Contact dealer.
c. Incoming water is usually cold.
Allow more time for heater to reheat.
d. Leaking hot water pipes of fixtures. Have plumber check and repair leaks.
e. Heater not lit or thermostat not on. Refer to LIGHTING INSTRUCTIONS.
VENT PIPE TOO HOT (ABOVE 170°F [77°C]) Wrong burner orifice.
Turn off heater and gas, clean burner head.
Turn off heater and gas, clean burner head.
Dirt in burner ports.
Check exhaust venting and air openings
in bottom base pan for obstructions or
blockage.
Yellow flaMe
Combustion air path restricted.
condensatIon
Water on the floor under heater.
See CONDENSATION section.
Improperly sealed, hot or cold supply
connections, relief valve, drain valve or Check for leaks. See Figure 1.
thermostat threads.
water leaKs
Leakage from other appliances or water lines. Inspect other appliances near water heater.
Condensation of flue products.
Refer to CONDENSATION section.
Install thermal expansion tank (Do not plug
T&P valve).
Thermal expansion in closed water system.
leaKInG t & p
Check relief valve for proper operation (Do
not plug T&P valve).
Improperly sealed valve.
High sulfate or mineral content in water
supply.
Drain and flush heater thoroughly then refill.
Chlorinate water supply.
hot water odors
(refer to cathodic protection)
Bacteria in water supply.
Refer to TEMPERATURE REGULATION
section.
hot water too hot
water heater sounds
SIZZLING - RUMBLING
sootInG
Thermostat set too high.
Condensation dripping on burner.
Sediment at bottom of heater tank.
Refer to CONDENSATION above.
Clean sediment from tank. Refer to
DRAINING.
Improper combustion.
Refer to Air Requirements.
Test polarity and correct.
Outlet polarity is reversed.
Contact a qualified service agency to
determine cause.
Burner wIll not staY lIt-Goes out
High ambient room temperature.
4-5 SECONDS
Defective gas control valve thermostat
Lack of air supply.
.
Replace gas control valve thermostat.
Improperly installed vent piping.
Downdraft
Shut off water heater immediately and contact a
qualified service agency to determine cause.
vent Gas odors
Poor Combustion
40
notes
41
notes
42
lIMIted resIdentIal Gas warrantY
THIS WARRANTY IS APPLICABLE TO THE ORIGINAL OWNER ONLY If
b. Shipping and delivery charges for forwarding the new water heater or
replacement part from the nearest distributor and returning the claimed
defective heater or part to such distributor except in the state of California
where such charges are the manufacturer’s responsibility.
c. All cost necessary or incidental for handling and administrative charges,
and for any materials and/or permits required for installation of the
replacement heater or part.
the glass lined tank in this water heater shall prove upon examination by (the
warrantor) to have leaked during the warranty period in normal residential
use, due to natural corrosion from potable water therein, the warrantor will
furnish the ORIGINAL OWNER a replacement water heater of equivalent
size and current model, or a replacement part for any component part which
fails in normal use, in accordance with the warranty terms and conditions
specified below. THE WATER HEATER REPLACEMENT MODEL OR
PART WILL BE WARRANTED FORONLYTHE UNEXPIRED PORTION OF
THE ORIGINAL WARRANTY The warranty period will be determined by the
original installation date of the water heater. PROOF-OF-PURCHASEAND
PROOF-OF-INSTALLATION ARE NECESSARY TO VALIDATE THIS
WARRANTY This warranty is not transferable.
lIMItatIon on IMplIed warrantIes
Implied warranties, including any warranty of merchantability imposed on
the sale of this heater under state law are limited to one year duration for the
heater or any of its parts. Some states do not allow limitations on how long
an implied warranty lasts, so the above limitations may not apply to you.
WARRANTY PERIOD
claIM procedure
Any claim under this warranty should be initiated with the dealer who sold
the heater, or with any other dealer handling the warrantor’s products.
product line
tanK1
parts2
GDHE-50
6 YEARS
6 YEARS
The warrantor will only honor replacement with identical or similar water
heater or parts thereof which are manufactured or distributed by the
warrantor.
When the water heater has been used for other than single family residential
application: 1. The Tank warranty shall be reduced to 3 years on 10 year
models and 1 year on 6 and 8 year models. 2. The parts warranty shall
be reduced to 1 year for all models. Returned parts which meet any of
the following conditions are not covered by this warranty: 1) improper
installation or removal; 2) damaged by other than normal wear; 3) replaced
for cosmetic purposes; or 4) returned with defaced date codes.
Dealer replacements are made subject to in-warranty validation by
warrantor.
PROOF-OF-PURCHASE AND PROOF-OF-INSTALLATION DATES ARE
REQUIRED TO SUPPORT WARRANTY FOR CLAIM FROM ORIGINAL
OWNER. THIS FORM DOES NOT CONSTITUTE PROOF-OF-PURCHASE
OR PROOF-OF-INSTALLATION.
condItIons and eXceptIons
This warranty shall apply only when the water heater is installed and
operated in accordance with: 1) all local fire codes and plumbing codes,
ordinances and regulations; 2) the printed instructions provided with it; 3)
good industry practices; and 4) proper safety practices such as but not
limited to a properly sized drain pan if installed in an area where leakage
from connections of the tank would result in damage to the area adjacent
to the heater. In addition, a new temperature and pressure relief valve,
certified by the Canadian Standards Association must have been properly
installed and piped to the nearest drain.
dIsclaIMers
NO EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF
OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY
OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR
REPLACEMENT OF THE HEATER OR PARTS. THE WARRANTOR SHALL
NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE
UNIT,INCONVENIENCE,LOSSORDAMAGETOPERSONALPROPERTY,
OR OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL
NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR
DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR
INDIRECT, AND WHETHER ARISING IN CONTRACT OR IN TORT.
This warranty shall apply only when the heater is:
•
•
owned by the original purchaser;
used at temperatures not exceeding the maximum calibrated setting of
its thermostat;
Some states do not allow the limitation or exclusion of incidental or
consequential damages, so the above limitation or exclusion may not
apply to you.
•
•
notsubjectedtoexcessivewaterpressurefluctuationsandnotsubjectto
an operating pressure greater than 150 P.S.I.;
filled with potable water, free to circulate at all times and with the tank
free of damaging water sediment or scale deposits;
used in a non-corrosive and non-contaminated atmosphere;
used with factory approved anode(s) installed;
in its original installation location;
in the United States and its territories or possessions or Canada;
sized in accordance with proper sizing techniques for residential
water heaters;
This warranty gives you specific legal rights, and you may also have other
rights which vary from state to state. Should governmental regulations or
industry standards prohibit the Manufacturer from furnishing a comparable
model replacement under this warranty, the Owner will be furnished with
the closest comparable water heater meeting the current governmental
regulations and industry standards. A supplementary fee may be assessed
to cover the additional cost associated with the changes made to meet
applicable regulations and standards.
•
•
•
•
•
•
•
•
•
•
bearing a rating plate which has not been altered, defaced or removed
except as required by the warrantor;
used in an open system or in a closed system with a properly sized and
installed thermal expansion tank;
fired at the factory rated input using the fuel stated in the face of the
rating plate;
operated with the inner and outer combustion chamber doors
in place;
Fill out and keep with water heater.
IMportant InforMatIon
maintained in accordance with the instructions printed in the manual
included with the heater.
Model Number _________________________________________
Serial Number__________________________________________
Installation Information:
Any accident to the water heater or any part thereof (including freezing,
fire, floods, or lightning), any misuse, abuse or alteration of it, any
operation of it in a modified form, or any attempt to repair tank leaks or
parts, will void this warranty.
Date Installed __________________________________________
Company’s Name ______________________________________
Street or P.O. Box_______________________________________
City, State, and Zip Code _________________________________
Phone Number ____________ Plumber’s Name_______________
servIce and laBor responsIBIlItY
UNDER THIS LIMITED WARRANTY, THE WARRANTOR WILL
PROVIDE ONLY A REPLACEMENT WATER HEATER OR PART
THEREOF. THE OWNER IS RESPONSIBLE FOR ALL OTHER COSTS.
Such costs may include but are not limited to:
a. Labor charges for service, removal, or reinstallation of the water heater
or part thereof.
43
500 Tennessee Waltz Parkway, Ashland City, TN 37015
Phone: 800-527-1953 Fax: 800-433-2515
www.hotwater.com
|