AO Smith Boiler 2600 User Manual

Instruction Manual  
XP BOILER  
MODELS: XB/XW  
1000, 1300, 1700  
2000, 2600, 3400  
SERIES 100/101  
INSTALLATION - OPERATION -  
MAINTENANCE - LIMITED WARRANTY  
25589 Highway 1  
McBee, SC 29101  
WARNING: If the information in these  
instructions is not followed exactly, a fire  
or explosion may result causing property  
damage, personal injury or death.  
Do not store or use gasoline or other  
flammable vapors and liquids in the  
vicinity of this or any other appliance.  
WHAT TO DO IF YOU SMELL GAS:  
Do not try to light any appliance.  
Do not touch any electrical switch; do  
not use any phone in your building.  
Immediately call your gas supplier  
from a neighbor’s phone. Follow the  
gas supplier’s instructions.  
If you cannot reach your gas supplier,  
call the fire department.  
Installation and service must be  
performed by a qualified installer,  
service agency or the gas supplier.  
Thank you for buying this energy efficient boiler.  
We appreciate your confidence in our products.  
PRINTED IN THE U.S.A. 0711  
320741-002  
TABLE OF CONTENTS  
TABLE OF CONTENTS.......................................................................... 2  
SAFE INSTALLATION, USE AND SERVICE.......................................... 3  
GENERAL SAFETY................................................................................ 4  
INTRODUCTION.................................................................................... 5  
Model Identification............................................................................ 5  
Abbreviations Used ........................................................................... 5  
Qualifications..................................................................................... 5  
DIMENSIONS AND CAPACITY DATA.................................................... 6  
FEATURES AND COMPONENTS ....................................................... 10  
Component Description................................................................... 12  
CONTROL COMPONENTS ................................................................. 13  
BOILER INSTALLATION CONSIDERATIONS ..................................... 15  
Hydronic System ............................................................................. 15  
Hot water boiler system - general water line connections ............... 16  
GENERAL REQUIREMENTS .............................................................. 21  
Location........................................................................................... 21  
Fresh air openings for confined spaces........................................... 23  
VENTING.............................................................................................. 25  
Vent Installation Considerations ...................................................... 25  
Venting Supports ............................................................................. 27  
CONDENSATE DISPOSAL.................................................................. 37  
GAS SUPPLY CONNECTIONS ........................................................... 38  
BOILER START UP AND OPERATIONS ............................................. 40  
LIGHTING AND OPERATING INSTRUCTIONS .................................. 42  
CONTROL SYSTEM ............................................................................ 45  
Burner Control System .................................................................... 45  
Burner control operation.................................................................. 46  
General operational sequence ........................................................ 47  
Local operator interface: display system ......................................... 49  
Installation instructions (S7999B OI Display) .................................. 50  
Starting up the S7999B OI Display.................................................. 51  
Page Navigation .............................................................................. 51  
TROUBLESHOOTING ......................................................................... 61  
MAINTENANCE PROCEDURES......................................................... 76  
Maintenance schedules................................................................... 76  
General maintenance ...................................................................... 76  
Burner maintenance ........................................................................ 77  
Venting maintenance....................................................................... 78  
Heat exchanger maintenance.......................................................... 78  
Handling ceramic fiber materials ..................................................... 79  
Replacement parts .......................................................................... 79  
PIPING DIAGRAMS............................................................................. 80  
LIMITED WARRANTY.......................................................................... 82  
2
SAFE INSTALLATION, USE AND SERVICE  
The proper installation, use and servicing of this boiler is extremely important to your safety and the safety of others.  
Many safety-related messages and instructions have been provided in this manual and on your boiler to warn you and others of a  
potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the  
meaning of each safety message is understood by you and others who install, use, or service this boiler.  
This is the safety alert symbol. It is used to alert you to  
potential personal injury hazards. Obey all safety  
messages that follow this symbol to avoid possible  
injury or death.  
DANGER indicates an imminently  
hazardous situation which, if not avoided,  
will result in injury or death.  
DANGER  
WARNING indicates a potentially hazardous  
situation which, if not avoided, could result  
in injury or death.  
WARNING  
CAUTION indicates a potentially hazardous  
situation which, if not avoided, could result in  
minor or moderate injury.  
CAUTION  
CAUTION used without the safety alert  
symbol indicates a potentially hazardous  
CAUTION  
situation which, if not avoided, could result in  
property damage.  
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message, and  
how to avoid the risk of injury.  
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances  
known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of  
potential exposure to such substances.  
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This  
boiler can cause low level exposure to some of the substances listed in the Act.  
IMPORTANT DEFINITIONS  
Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning  
appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of  
gas piping up to and including the Natural Gas meter or Propane storage tank of a building. Many gas suppliers also  
offer service and inspection of appliances within the building.  
APPROVALS  
3
GENERAL SAFETY  
GROUNDING INSTRUCTIONS  
HIGH ALTITUDE INSTALLATIONS  
This boiler must be grounded in accordance with the National  
Electrical Code, Canadian Electrical Code and/or local codes.  
Boiler is polarity sensitive; correct wiring is imperative for proper  
operation.  
This boiler must be connected to a grounded metal, permanent  
wiring system, or an equipment grounding conductor must be  
run with the circuit conductors and connected to the equipment  
grounding terminal or lead on the boiler.  
INLET WATER CONSIDERATIONS  
Circulating water through the boiler and to the remote storage  
tank (if applicable) is accomplished by a pump on XW models  
only. For hot water heating systems using the XB model, the  
circulating pump is NOT provided on standard models (optional)  
and must be field installed.  
CORRECT GAS  
Make sure the gas on which the boiler will operate is the same as  
that specified on the boiler rating plate. Do not install the boiler if  
equipped for a different type of gas; consult your supplier.  
PRECAUTIONS  
Rated inputs are suitable up to 2000 feet (610 m) elevation. Consult  
If the unit is exposed to the following, do not operate until all the factory for installation at altitudes over 2000 feet (610 m).  
corrective steps have been made by a qualified service agent:  
FIELD INSTALLED COMPONENTS  
1. Exposure to fire.  
2. If damaged.  
3. Firing without water.  
4. Sooting.  
When installing the boiler, the following components must be  
installed:  
Circulating Pump (Hydronic)  
If the boiler has been exposed to flooding, it must be replaced.  
Remote Temperature Sensor/Header Sensor  
Storage Tank (Temperature & Pressure Relief Valve)  
LIQUEFIED PETROLEUM GAS MODELS  
Boilers for propane or liquefied petroleum gas (LPG) are different  
from natural gas models.Anatural gas boiler will not function safely  
on LP gas and no attempt should be made to convert a boiler from  
natural gas to LP gas.  
LP gas must be used with great caution. It is highly explosive  
and heavier than air. It collects first in the low areas making its  
odor difficult to detect at nose level. If LP gas is present or even  
suspected, do not attempt to find the cause yourself. Leave  
the building, leaving doors open to ventilate, then call your gas  
supplier or service agent. Keep area clear until a service call  
has been made.  
At times you may not be able to smell an LP gas leak. One  
cause is odor fade, which is a loss of the chemical odorant that  
gives LP gas its distinctive smell. Another cause can be your  
physical condition, such as having a cold or diminishing sense  
of smell with age. For these reasons, the use of a propane gas  
detector is recommended.  
If you experience an out of gas situation, do not try to relight  
appliances yourself. Call your local service agent. Only trained  
LP professionals should conduct the required safety checks in  
accordance with industry standards.  
4
INTRODUCTION  
This Instruction Manual covers XP Boiler models XB/XW 1000,  
QUALIFICATIONS  
1300, 1700, 2000, 2600, 3400 - Series 100/101. The instructions  
and illustrations contained in this Instruction manual will provide  
you with troubleshooting procedures to diagnose and repair  
common problems and verify proper operation.  
QUALIFIED INSTALLER OR SERVICE AGENCY  
Installation and service of this boiler requires ability equivalent  
to that of a Qualified Agency, as defined by ANSI below. In the  
field involved. Installation skills such as plumbing, air supply,  
venting, gas supply and electrical supply are required in addition  
to electrical testing skills when performing service.  
MODEL IDENTIFICATION  
Check the rating plate affixed to the Boiler. The following  
information describes the model number structure:  
ANSI Z21.13 - CSA 4.9: “Qualified Agency” - “Any individual,  
firm, corporation or company that either in person or through  
a representative is engaged in and is responsible for (a) the  
installation, testing or replacement of gas piping or (b) the  
connection, installation, testing, repair or servicing of appliances  
and equipment; that is experienced in such work; that is familiar  
with all precautions required; and that has complied with all the  
requirements of the authority having jurisdiction.”  
SERIES-100/101 DESIGNATION:  
• XP = Extreme Performance  
MODEL (APPLICATION):  
• XB = Hydronic Heating Boiler  
• XW = Domestic Hot Water Supply Boiler  
SIZE:  
• 1000 = 920,000 Btu/hr input  
• 1300 = 1,300,000 Btu/hr input  
• 1700 = 1,700,000 Btu/hr input  
• 2000 = 2,000,000 Btu/hr input  
• 2600 = 2,600,000 Btu/hr input  
• 3400 = 3,400,000 Btu/hr input  
If you are not qualified (as defined by ANSI above) and licensed  
or certified as required by the authority having jurisdiction  
to perform a given task do not attempt to perform any of the  
procedures described in this manual. If you do not understand  
the instructions given in this manual do not attempt to perform  
any procedures outlined in this manual.  
FUEL:  
This product requires a formal Start-Up by an authorized service/  
start-up provider that has been approved by the manufacturer for  
this specific product. Call 1-800-527-1953 to locate the nearest  
authorized start-up provider and arrange a factory start-up.  
Please provide as much notice as possible, preferably 2 weeks.  
Please have the model and serial number ready when you call.  
This start-up is required to activate the warranty and ensure safe,  
efficient operation.  
N = Natural gas  
P = Propane  
NOTE:  
XB models are equipped with 50 psi pressure relief valve. (pump  
is optionally installed)  
XW models are factory installed circulating pump (standard),  
with 125 psi pressure relief valve.  
XB models can be special ordered with a factory installed pump  
and XW models can be special ordered without the factory  
installed pump. These factory configurations can also be  
changed in the field by installing circulation pumps and changing  
pressure relief valves to accommodate domestic and hydronic  
hot water system requirements.  
Warranty on this product is limited and could be void in the event  
the unit is not installed per the instructions in this manual and/or  
not started up by an authorized factory trained service/start-up  
provider.  
Properly installed and maintained, it should give you years of  
trouble free service.  
ABBREVIATIONS USED  
Abbreviations found in this Instruction Manual include :  
• ANSI - American National Standards Institute  
• ASME - American Society of Mechanical Engineers  
• NEC - National Electrical Code  
• NFPA - National Fire Protection Association  
• UL - Underwriters Laboratory  
• CSA - Canadian Standards Association  
• AHRI - Air-Conditioning, Heating and Refrigeration Institute  
5
DIMENSIONS AND CAPACITY DATA  
FIGURE 1. SINGLE HEAT EXCHANGER BOILER  
TABLE 1. ROUGH IN DIMENSIONS (SINGLE)  
Models  
XB/XW-1000  
inches  
XB/XW-1300  
inches  
XB/XW-1700  
inches  
Dimensions  
Flue Outlet Diameter  
Air Intake Diameter  
Water Inlet  
mm  
152  
152  
mm  
152  
152  
mm  
203  
203  
6
6
8
6
8
8
2 inch NPT  
2 inch NPT  
2 inch NPT  
2 1/2 inch NPT  
Water Outlet  
2 1/2 inch NPT  
2 inch NPT  
Gas Inlet  
A
B
C
D
E
F
47  
67  
29  
37  
23  
9
1199  
1702  
737  
49  
68  
29  
38  
23  
9
1245  
1727  
737  
57  
76  
29  
37  
24  
9
1448  
1930  
737  
940  
610  
229  
940  
965  
584  
584  
229  
229  
G
H
J
34  
44  
6
864  
1118  
152  
279  
34  
45  
6
864  
1143  
152  
34  
45  
6
864  
1143  
152  
K
11  
11  
279  
11  
279  
L
12  
305  
11  
279  
12  
305  
TABLE 2. OPERATING CHARACTERISTICS  
Manifold Pressure  
Inches W.C.  
Maximum Supply Pressure Minimum Supply Pressure  
Models  
(XB/XW)  
Type of Gas  
kPa  
Inches W.C.  
kPa  
Inches W.C.  
kPa  
Min Fire -0.2 to -0.3 -0.05 to -0.07  
Max Fire -3.0 to -3.9 -0.75 to -0.97  
Min Fire -0.1 to -0.3 -0.025 to -0.07  
Natural  
14.0  
3.49  
4.0  
1.0  
1000, 1300, 1700  
2000, 2600, 3400  
Propane  
14.0  
3.49  
4.0  
2.0  
Max Fire -3.6 to -4.9 -0.90 to -1.22  
6
 
FIGURE 2. DOUBLE HEAT EXCHANGER BOILER  
TABLE 3. ROUGH IN DIMENSIONS (DOUBLE)  
Models  
XB/XW-2000  
inches  
XB/XW-2600  
inches  
XB/XW-3400  
inches  
Dimensions  
mm  
203  
203  
mm  
203  
203  
mm  
254  
254  
Flue Outlet Diameter  
8
8
8
8
10  
10  
Air Intake Diameter  
Water Inlet  
Water Outlet  
Gas Inlet  
3 inch NPT  
3 inch NPT  
2 inch NPT  
4 inch NPT  
4 inch NPT  
3 inch NPT  
A
47  
1194  
49  
1245  
57  
1448  
B
C
D
E
F
78  
36  
22  
40  
7
1981  
914  
80  
37  
22  
41  
6
2032  
940  
91  
37  
22  
41  
6
2311  
940  
559  
559  
559  
1016  
178  
1041  
152  
1041  
152  
G
10  
254  
10  
254  
10  
254  
H
J
4
102  
508  
305  
4
102  
483  
305  
4
102  
483  
330  
20  
12  
19  
12  
19  
13  
K
TABLE 4. RECOVERY CAPACITIES  
Temperature Rise - ΔT °F (°C)  
Input Rating Output Rating Water  
Models  
40  
(22)  
60  
(33)  
70  
(39)  
80  
(44)  
90  
(50)  
100  
(56)  
120  
(67)  
140  
(78)  
(Btu/hr)  
(Btu/hr)  
Flow  
GPH  
LPH  
GPH  
LPH  
GPH  
LPH  
2,593  
9,815  
3,664  
13,868  
4,791  
1,728  
6,543  
2,442  
9,246  
3,194  
1,482  
5,608  
2,094  
7,925  
2,738  
1,296  
4,907  
1,832  
6,934  
2,395  
9,068  
1,152  
4,362  
1,628  
6,164  
2,129  
8,060  
1,037  
3,926  
1,465  
5,547  
1,916  
7,254  
864  
3,272  
1,221  
4,623  
1,597  
6,045  
741  
2,804  
1,047  
3,962  
1,369  
5,182  
XW-1000  
920,000  
854,680  
XW-1300 1,300,000  
1,207,700  
XW-1700 1,700,000  
XW-2000 2,000,000  
XW-2600 2,600,000  
1,579,300  
1,858,000  
2,415,400  
18,136  
12,090  
10,363  
GPH  
LPH  
GPH  
LPH  
GPH  
5,636  
21,336  
7,327  
27,737  
9,582  
3,758  
14,224  
4,885  
18,491  
6,388  
3,221  
12,192  
4,187  
15,850  
5,475  
2,818  
10,668  
3,664  
13,868  
4,791  
2,505  
9,483  
3,257  
12,327  
4,259  
2,255  
8,534  
2,931  
11,095  
3,833  
1,879  
7,112  
2,442  
9,246  
3,194  
1,610  
6,096  
2,094  
7,925  
2,738  
XW-3400 3,400,000  
3,158,600  
LPH  
36,271  
24,181  
20,726  
18,136  
16,121  
14,508  
12,090 10,363  
7
RATINGS  
TABLE 5. IBR RATINGS  
MODELS  
(XB/XW)  
INPUT  
MBH  
GROSS  
OUTPUT MBH  
NET I=B=R RATINGS WATER MBH  
(NOTE 2)  
(NOTE 1)  
MAX  
MIN  
1000  
1300  
920  
100  
130  
856  
744  
1300  
1209  
1051  
1700  
2000  
2600  
3400  
1700  
2000  
2600  
3400  
170  
100  
130  
212  
1581  
1860  
2418  
3162  
1375  
1617  
2103  
2750  
Notes:  
1. The ratings are based on standard test procedures prescribed by the United States Department of Energy.  
2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need  
be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.  
3. Ratings have been confirmed by the Hydronics Institute, Section of AHRI.  
ELECTRICAL REQUIREMENTS  
TABLE 6. ELECTRICAL REQUIREMENTS  
MODELS SUPPLY VOLTAGE FREQUENCY CURRENT  
ELECTRICAL NOTES  
(XB/XW)  
(VOLTS)  
(HZ)  
(AMPS)  
1000  
120  
60  
30  
30  
A dedicated, single phase, 30/60 amp circuit breaker  
with a grounded neutral should be provided to supply  
power to the boiler.  
1300  
120  
60  
1700  
2000  
2600  
3400  
120  
120  
120  
120  
60  
60  
60  
60  
30  
60  
60  
60  
A dedicated, single phase, 60/60 amp circuit breaker  
with a grounded neutral should be provided to supply  
power to the boiler.  
8
 
FLOW, HEAD AND TEMPERATURE RISE  
TABLE 7. XB MODELS - FLOW, HEAD AND TEMPERATURE RISE  
Temperature Rise - ΔT °F  
Flow Rate  
Input  
(Btu/hr)  
Output  
(Btu/hr)  
Water  
Flow  
Models  
20  
30  
40  
Maximum  
Minimum  
GPM  
LPM  
ΔP FT  
ΔP M  
GPM  
LPM  
ΔP FT  
ΔP M  
GPM  
LPM  
86  
325  
26  
7.9  
120  
453  
32.5  
9.9  
156  
592  
56  
211  
12  
3.7  
80  
302  
15  
4.6  
104  
395  
43  
162  
7
2.1  
60  
226  
8
2.4  
78  
86  
325  
26  
7.9  
120  
453  
32.5  
9.9  
156  
592  
43  
162  
7
2.1  
60  
226  
8
2.4  
78  
XB-1000  
XB-1300  
920,000  
855,600  
1,300,000  
1,209,000  
296  
296  
XB-1700  
1,700,000  
1,581,000  
ΔP FT  
ΔP M  
35  
14  
8
35  
8
10.7  
4.3  
2.4  
10.7  
2.4  
GPM  
LPM  
ΔP FT  
ΔP M  
GPM  
LPM  
ΔP FT  
ΔP M  
GPM  
LPM  
184  
696  
26  
7.9  
239  
905  
32.5  
9.9  
313  
1184  
123  
464  
12  
3.7  
159  
604  
15  
4.6  
209  
789  
92  
348  
7
2.1  
120  
453  
8
2.4  
156  
592  
184  
696  
26  
7.9  
239  
905  
32.5  
9.9  
313  
1184  
92  
348  
7
2.1  
120  
453  
8
2.4  
156  
592  
XB-2000  
XB-2600  
2,000,000  
2,600,000  
1,860,000  
2,418,000  
XB-3400  
3,400,000  
3,162,000  
ΔP FT  
ΔP M  
35  
14  
8
35  
8
10.7  
4.3  
2.4  
10.7  
2.4  
Note: Head Loss shown is through the boiler only and allows for no additional piping.  
9
FEATURES AND COMPONENTS  
FIGURE 3. SINGLE HEAT EXCHANGER BOILER COMPONENTS  
10  
FIGURE 4. DOUBLE HEAT EXCHANGER BOILER COMPONENTS  
11  
19. Heat exchanger access covers  
COMPONENT DESCRIPTION  
Allows access to the combustion side of the heat exchanger  
coils.  
1. Front access door:  
Provides access to the gas train, burner controllers and the heat  
exchanger.  
20. High gas pressure switch  
Switch provided to detect excessive supply gas pressure.  
2. Air Filter Box:  
21. Spark Igniter  
Provides direct spark for igniting the burners.  
Allows for the connection of the PVC air intake pipe to the boiler  
through a standard PVC adapter. It uses a filter to prevent dust  
and debris from entering the boiler.  
22. Boiler power supply terminals (not visible)  
The main power to the boiler is supplied through the terminals  
housed inside the high voltage junction box.  
3. Automatic air vents:  
Designed to remove trapped air from the heat exchanger coils.  
23. Low gas pressure switch  
Switch provided to detect low gas supply pressure.  
4. Blowers:  
The blowers pull in air and gas through the venturis. Air and gas  
mix inside the venturi and are pushed into the burners, where  
they burn inside the combustion chamber.  
24. High voltage connection box  
This box has terminals for connecting the main power supply  
(120V) to the boiler and outputs power supply (120V) for the  
pumps from the boiler control. This box has terminals for low  
voltage devices such as condensate trap and flow switch.  
5. Boiler inlet temperature sensors  
These sensors monitor system return water temperature.  
6. Boiler outlet temperature sensors/High Limits  
These sensors monitor boiler outlet water temperature. The boiler  
modulates based on the Lead Lag Sensor connected to the tank.  
25. Sensors/Communication Box  
Connects sensors to tank sensor/header sensor and external  
connections to building managements systems through MODBUS.  
7. Burners  
26. Low water cutoff board and sensor probe (LWCO)  
Made with metal fiber and stainless steel construction, the  
burners use pre-mixed air and gas and provide a wide range of  
firing rates.  
Device used to ensure adequate water is supplied to the boiler.  
In the event of inadequate water levels, LWCO will ensure boiler  
shut down. LWCO board is connected to the electronic panel,  
whereas the sensor probe is connected to the heat exchanger.  
8. Condensate Trap  
Disposes the condensate produced from heat exchanger and  
houses a switch that detects in case of blockage.  
27. Main power supply switch  
Turns 120 VAC ON/OFF to the boiler.  
9. Control modules  
28. Pump relay  
The control modules respond to internal and external signals and  
control the blowers, gas valves, and pumps to meet the heating  
demand.  
The pump relays are used tfor providing power to the XW Boiler  
models.  
29. Pressure relief valve  
Protects the heat exchangers from an over pressure condition.  
The relief valve will be set at particular PSI, depending on models.  
10. Touch Screen Display  
Digital controls with touch screen technology and full color  
display.  
30. Reset switch (optional) (not visible)  
Reset switch for the low water cutoff.  
11. Sight glass  
The quartz sight glass provides a view of the flame for inspection  
31. Stainless steel heat exchangers  
purposes.  
Allows system water to flow through specially designed coils.  
12. Flame sensors  
32. Venturi  
Used by the control module to detect the presence of burner  
flame.  
The venturi is a gas/air mixing unit that allows modulation of a  
premix burner with constant gas/air ratio.  
13. Flap valves  
33. Water inlet  
Prevents recirculation of flue products when only one burner is  
Water connection that return water from the system to the heat  
exchangers.  
running.  
14. Flue gas sensors (not visible)  
34. Water outlets  
A NPT water connection that supplies hot water to the system.  
These sensors monitor the flue gas exit temperature. The control  
modules will modulate and shut down the boiler if the flue gas  
temperature gets too hot. This protects the flue pipe from  
overheating.  
35. Enable/Disable Switch  
This is an emergency boiler turn off switch which disconnects  
the interlock voltage to the control board, hence turning off the  
power supply to the gas valves. Do not use this switch for  
turning off the boiler, this should be done from the touch  
screen display, using the Operational Switch on the Lead  
Lag screen.  
15. Flue pipe adapter (not visible)  
Allows for the connection of the PVC vent pipe system to the  
boiler.  
16. Gas shutoff valves (Internal unit)  
Manual valves used to isolate the gas valves from the burners.  
36. Vent outlet  
Provides an outlet for combustion gases to outdoor.  
17. Main gas shutoff valve (External unit)  
Manual valve used to isolate the boiler from the gas supply.  
18. Automatic modulating gas valve  
The gas valve with the addition of venturi and blower are used for  
modulating premix appliances.  
12  
CONTROL COMPONENTS  
THE CONTROL SYSTEM  
The R7910A1138 is a burner control system that provides heat  
control, flame supervision, circulation pump control, fan control,  
boiler control sequencing, and electric ignition function. It will  
also provide status and error reporting.  
FIGURE 7. LOW/HIGH GAS PRESSURE SWITCH  
GAS VALVE  
The gas valve is a normally closed servo regulated gas valve.  
The valve opens only when energized by the burner control and  
closes when the power is removed. The burner control supplies  
24 volts to the gas valve during operation.  
FIGURE 5. BURNER CONTROL SYSTEM  
SPARK IGNITER  
The spark igniter is a device that ignites the main burner. When  
power is supplied to the igniter electrode, an electric arc is  
created between the electrode and the ground terminal which  
ignites the main burner.  
FIGURE 6. SPARK IGNITER  
FIGURE 8. GAS VALVE  
LOW/HIGH GAS PRESSURE SWITCH  
WATER FLOW SWITCH  
This XP boiler is equipped with a low gas pressure switch which  
meets the CSD-1 code requirements.  
The water flow switch activates when sufficient water flow has  
been established. Switch will not close when water flow is not  
present.  
The Low Gas Pressure Switch is normally open and remains  
open unless the pressure falls below the preset pressure.  
The High Gas Pressure Switch is normally closed and is used to  
detect excessive gas pressure.  
FIGURE 9. WATER FLOW SWITCH  
13  
FLAME SENSOR  
WATER TEMPERATURE SENSORS  
Each burner is equipped with a flame sensor to detect the  
presence of the burner flames at high and low fire conditions. If  
no flame is sensed, the gas valve will close automatically. The  
voltage sensed by the flame sensor will also be displayed on the  
Burner Screen.  
FIGURE 12. WATER TEMPERATURE SENSORS  
Temperature sensors are threaded immersion probes.  
Temperature probes have embedded temperature sensors  
(thermistors). The boiler’s control system monitors these sensors  
to determine water temperature at various points in the system.  
FIGURE 10. FLAME SENSOR  
WATER TEMPERATURE LIMIT CONTROLS  
INLET AND OUTLET TEMPERATURE SENSORS  
All models have two inlet and two outlet temperature sensors  
for each heat exchanger, factory installed to monitor the water  
temperature entering and leaving the boiler. The Inlet Probe is  
a temperature sensor only and has two leads. The Outlet probe  
also contains the manual reset high temperature limit switch  
and has four leads. The control system displays the Inlet and  
Outlet water temperatures sensed from these two sensors on the  
default Temperatures screen.  
The “XB/XW” models incorporate an outlet water sensor having  
dual sensors, that are factory set at 210°F (99°C).  
REMOTE SENSORS  
All models are supplied from the factory with a remote sensor.  
The remote sensor is used to control system water temperature  
for a single boiler in a domestic hot water storage tank or in the  
return line from a primary/secondary hydronic heating system.  
MAIN POWER SUPPLY SWITCH  
The main power supply switch is a padlockable switch. This switch  
provides 120V from the power supply to the boiler.  
This switch needs to be turned off when servicing the boiler.  
Note: The Enable/Disable Switch on the front of the boiler  
does not interrupt electrical power to the boiler.  
The boiler will modulate its firing rate in response to the  
actual system temperature and load conditions. The control  
system displays the temperature sensed from the remote sensor  
as the “Lead Lag” temperature on the default Temperatures  
screen.  
LOW WATER CUTOFF DEVICE (LWCO)  
Low water cutoff device is normally a closed switch that opens  
when water drops below a preset level. Each model is equipped  
with a factory installed LWCO. LWCO board is connected to the  
electronic panel, whereas the sensor probe is connected to the  
heat exchanger.  
FIGURE 11. MAIN POWER SUPPLY SWITCH  
FIGURE 13. LWCO BOARD AND PROBE  
14  
BOILER INSTALLATION CONSIDERATIONS  
If the system is of the open type, a pressure reducing valve will not  
GENERAL  
be required as the water supply to the system will be controlled by  
a manually operated valve. An overhead surge tank is required. A  
minimum pressure of 15 psi (100 kPa) must be maintained on the  
boiler at all times to ensure avoidance of potential damage to the  
boiler which may not be covered by the warranty.  
If the system is to be filled with water for testing or other purposes  
during cold weather and before actual operation, care must be taken  
to prevent freezing of water in the system. Failure to do so may cause  
the water in the system to freeze with resulting damage to the system.  
Damage due to freezing is not covered by the warranty.  
EXPANSION TANK  
Figure 78 on Page 80 shows a typical primary, secondary piping  
method. This is the preferred piping method for most stainless steel  
boilers. Other piping methods, however, may provide good system  
operation. A prime concern when designing heating systems is the  
maintenance of proper flow through the unit during boiler operation.  
The secondary pump should be sized per the recommended flow  
rate of the boiler, see Dimension and Capacity Data section in this  
manual.  
If the system is of the closed type, install an expansion tank. The  
sizing of the expansion tank for a closed system is very important and  
is directly related to the total water volume of the system.  
An air separator as shown in the piping diagrams is recommended  
especially for modern commercial hydronic systems. See Figure 78  
on Page 80.  
VENT VALVES  
It is recommended that automatic, loose key or screw-driver type  
vent valves be installed at each convector or radiator.  
Before locating the boiler:  
1. Check for nearby connection to:  
• System water piping  
• Venting connections  
• Gas supply piping  
SYSTEM HEADERS  
Split systems with individual supply and return lines from the  
boiler room should normally have this piping connected to  
supply and return manifold headers near the boiler. To achieve  
good water distribution with maximum pressure drop for several  
circuits, manifolds should be larger than system mains.  
• Electrical power  
2. Locate the boiler so that if water connections should leak,  
water damage will not occur. When such locations cannot  
be avoided, it is recommended that a suitable drain pan,  
adequately drained, be installed under the appliance.  
The pan must not restrict combustion air flow. Under no  
circumstances is the manufacturer to be held responsible  
for water damage in connection with this appliance, or any  
of its components.  
The circuits should be spaced on the heater at a minimum of 3”  
(76 mm) center to center. Install a balancing cock in each return  
line.  
Manifold headers are recommended for split systems with  
or without zone valves and also those installations with zone  
circulators. If the system is to be split at remote points, good  
practice requires special attention be given to main pipe sizing to  
allow balancing of water flow.  
3. Check area around the boiler. Remove any combustible  
CHECK VALVES  
materials, gasoline and other flammable liquids.  
Check valves must be installed to isolate each boiler in  
installations where multiple boilers/pumps are installed in the  
same zone.  
4. Make sure the gas control system components are protected  
from dripping or spraying water or rain during operation or  
service.  
COOLING PIPING  
5. If a new boiler will replace an existing boiler, check for and  
correct system problems, such as:  
When the boiler is used in conjunction with a refrigeration system  
it must be installed so that the chilled medium is piped in parallel  
with the boiler. Appropriate flow control valves, manual or  
motorized, must be provided to prevent the chilled medium from  
entering the boiler.  
• System leaks causing oxygen corrosion or heat  
exchanger cracks from hard water deposits.  
• Lack of freeze protection in boiler water causing system  
and boiler to freeze and leak.  
If the boiler is connected to chilled water piping or its heating coils  
are exposed to refrigerated air, the boiler piping system must be  
equipped with flow valves or other automatic means to prevent  
gravity circulation through the boiler during the cooling cycle.  
HYDRONIC SYSTEM  
The following is a brief description of the equipment required  
for the installations noted in this manual. All installations must  
comply with local code.  
Primary/secondary pumping of both the chiller(s) and the boiler(s) is  
an excellent winter-summer change-over method, because cooling  
flow rates are so much more than heating flow rates. In this way each  
system (heating or cooling) is circulated independently.  
WATER SUPPLY LINE  
These boilers can be used only in a forced circulation hot water  
heating system. Since most forced circulation systems will be of  
the closed type, install the water supply line as shown on piping  
diagram.  
Fast filling of large pipe, old radiator installations and pressure  
purging of series loop systems (where high pressures are not  
available) requires bypassing of the pressure reducing valve.  
Generally, pressure purging is not possible with a well pump  
system. High point air venting is essential.  
15  
CIRCULATING PUMP  
HOT WATER BOILER SYSTEM - GENERAL WATER  
LINE CONNECTIONS  
A circulating pump is used when a system requires a circulating  
loop or there is a storage tank used in conjunction with the boiler.  
Install in accordance with the current edition of the National  
Electrical Code, NFPA 70 or the Canadian Electrical Code,  
CSA C22.1. All bronze circulating pumps are recommended  
for use with commercial boilers. Some circulating pumps are  
manufactured with sealed bearings and do not require further  
lubrication. Some circulating pumps must be periodically oiled.  
Refer to the pump manufacturer’s instructions for lubrication  
requirements.  
Piping diagrams will serve to provide the installer with a  
reference for the materials and methods of piping necessary for  
installation. It is essential that all water piping be installed and  
connected as shown on the diagrams. Check the diagrams to  
be used thoroughly before starting installation to avoid possible  
errors and to minimize time and material cost. It is essential that  
diagrams. See Figure 78 on Page 80 and Figure 79 on Page 81.  
CLOSED WATER SYSTEMS  
XB HYDRONIC BOILERS: The circulating pump is not provided  
on standard models (optional) and must be obtained and installed  
in the field.  
Water supply systems may, because of code requirements  
or such conditions as high line pressure, among others, have  
installed devices such as pressure reducing valves, check  
valves, and back flow preventers. Devices such as these cause  
the water system to be a closed system.  
XW HOT WATER BOILERS: The circulating pump is integral to  
the XW models. This pump has been lubricated at the factory,  
and future lubrication should be in accordance with the motor  
manufacturer’s instructions provided as a supplement to this  
manual.  
THERMAL EXPANSION  
PRIMARY SYSTEM CONTROL  
All XP boiler installations require a “Primary System Control” that  
senses and reacts to water temperature inside the storage tank  
on domestic water applications or in the return line on primary/  
secondary hydronic heating systems. The Primary System  
Control will activate and deactivate boiler heating cycles based  
on its setpoint and current system water temperature. There are  
three suitable methods to configure a Primary System Control.  
One of these three methods must be used.  
As water is heated, it expands (thermal expansion). In a closed  
system the volume of water will increase when it is heated. As the  
volume of water increases there will be a corresponding increase  
in water pressure due to thermal expansion. Thermal expansion  
can cause premature failure (leakage). This type of failure is not  
covered under the limited warranty. Thermal expansion can also  
cause intermittent Temperature-Pressure Relief Valve operation:  
water discharged from the valve due to excessive pressure build  
up. This condition is not covered under the limited warranty.  
The Temperature-Pressure Relief Valve is not intended for the  
constant relief of thermal expansion.  
1.  
The Primary System Control can be the boiler’s  
control system working with the factory supplied Header  
Sensor, installed inside the storage tank on domestic water  
applications or in the return line on primary/secondary  
hydronic heating systems.  
A properly sized thermal expansion tank must be installed on  
all closed systems to control the harmful effects of thermal  
expansion. Contact a local plumbing service agency to have a  
thermal expansion tank installed.  
2.  
Alternatively, the Burner Control system can be used  
as a Primary System Control. It will also provide boiler status  
and error reporting. Multiple boilers can be joined together  
to heat a system instead of a single, larger burner or boiler.  
Using boilers in parallel is more efficient, costs less, reduces  
emissions, improves load control, and is more flexible than  
the traditional large boiler.  
PRESSURE RELIEF VALVE  
An ASME rated pressure relief valve is furnished with the boiler.  
A fitting for the relief valve is provided in the top of the boiler.  
Never operate the heating elements without being certain the  
boiler is filled with water and a properly sized pressure relief  
valve is installed in the relief valve opening provided.  
3.  
MB2 and COM2 ports can be used for Building  
Management Systems.  
The pressure rating of the relief valve should be equal to or less  
than the rated pressure capacity of any component in the system  
INTERNAL CONTAMINANTS  
The hydronic system must be internally cleaned and flushed including the boiler. Should the valve need to be replaced, call  
after a new or replacement boiler has been installed, to remove the toll free phone number listed on the back of this manual for  
contaminants that may have accumulated during installation. further technical assistance  
This is extremely important when a replacement boiler is installed  
into an existing system where Stop Leak or other boiler additives  
have been used.  
Failure to clean and flush the system can produce acid  
concentrations that become corrosive, and leads to heat  
exchanger failure.  
All hot water heating systems should be completely flushed with  
a grease removing solution to assure trouble-free operation. Pipe  
joint compounds, soldering paste, grease on tubing and pipe all  
tend to contaminate a system  
Failure to flush contaminants from a system can cause solids  
to form on the inside of boiler exchangers, create excessive  
blockage of water circulation, deterioration of the pump seals  
and impellers.  
16  
In addition, a CSA design-certified and ASME-rated temperature  
and pressure (T&P) relief valve must be installed on each and  
every water storage tank in hot water supply system. The T&P  
relief valve must comply with applicable construction provisions  
of Standard for Relief Valves for Hot Water Supply Systems,ANSI  
Z21.22 or CSA 4.4. T&P relief valve must be of automatic reset  
type and not embody a single-use type fusible plug, cartridge or  
linkage.  
Explosion Hazard  
Relief Valve must comply with  
ASME code.  
Properly sized Relief Valve must  
be installed in opening provided.  
T&P relief valve should have a temperature rating of 210°F  
(99°C), a pressure rating not exceeding lowest rated working  
pressure of any system component, and a discharge capacity  
exceeding total input of water boilers supplying water to storage  
tank.  
Can result in overheating and  
excessive tank pressure.  
Can cause serious injury or death.  
Locate the T&P relief valve (a) in the top of the tank, or (b) in  
the side of the tank on a centerline within the upper 6 inches  
(152 mm) of the top of the tank, see Figure 78 and Figure 79.  
The tapping should be threaded in accordance with the current  
edition of the Standard for Pipe Threads, General Purpose  
(inch), ANSI/ASME B1.20.1. The location of, or intended location  
for, the T&P relief valve should be readily accessible for servicing  
or replacement.  
A discharge pipe from the relief valve should terminate at an  
adequate floor drain. Do not thread, plug, or cap the end of  
drain line.  
CAUTION  
Water Damage Hazard  
GAS CONNECTIONS  
Pressure Relief Valve discharge pipe must  
terminate at adequate drain.  
The Discharge Pipe:  
• Shall not be smaller in size than the outlet pipe size of the  
valve, or have any reducing couplings or other restrictions.  
• Shall not be plugged or blocked.  
• Shall not be exposed to freezing temperatures.  
• Shall be of material listed for hot water distribution.  
• Shall be installed so as to allow complete drainage of both  
the relief valve and the discharge pipe.  
• Must terminate a maximum of six inches above a floor  
drain or external to the building. In cold climates, it is  
recommended that the discharge pipe be terminated at an  
adequate drain inside the building.  
Make sure the gas on which boiler is to operate is same as that  
specified on the rating plate. Do not install boiler if equipped for a  
different type of gas. Consult your gas supplier.  
• Shall not have any valve or other obstruction between the  
relief valve and the drain.  
This boiler is not intended to operate at gas supply pressure  
other than shown on the rating plate. A lock-up or positive shut-  
off type regulator must be installed in gas supply line. For proper  
gas regulation the lock-up style regulators must be installed no  
closer than a minimum of 3 feet from the boiler and a maximum  
of 8 feet away from the boiler. Exposure to higher gas supply  
pressure may cause damage to gas valves which can result in  
fire or explosion. If overpressure has occurred such as through  
improper testing of gas lines or emergency malfunction of supply  
system, the gas valves must be checked for safe operation.  
Make sure that the outside vents on supply regulators and the  
Once the boiler is installed and filled with water and the system  
is pressurized, manually test the operation of the pressure relief  
valve. See the Maintenance Procedures section of this manual  
for instructions.  
Your local code authority may have other specific safety relief  
valve requirements not covered below. If any pressure relief  
valve is replaced, the replacement valve must comply with the  
current version of the ASME Boiler and Pressure Vessel Code,  
Section IV (“HEATING BOILERS”).  
XB HYDRONIC BOILERS, are shipped with a 50 psi (345 kPa) safety vent valves are protected against blockage. These are  
pressure relief valve. This relief valve must be installed in the  
water outlet as near to the boiler as possible.  
parts of the gas supply system, not boiler. Vent blockage may  
occur during ice build-up or snowstorms.  
XW HOT WATER BOILERS, are shipped with a 125 psi (860  
kPa) pressure relief valve that must be installed in the water out-  
let as near to the boiler as possible.  
The boiler must be isolated from the gas supply piping system by  
closing its main manual gas shut off valve during any pressure  
testing of the gas supply piping system at test pressures equal  
to or less than 1/2 psig.  
This ASME-rated valve has a discharge capacity that exceeds  
maximum boiler input rating and a pressure rating that does not  
exceed maximum working pressure shown on boiler rating plate.  
Disconnect the boiler and its main manual gas shut-off valve  
from the gas supply piping during any pressure testing of the  
gas supply system over 1/2 psig. The gas supply line must be  
capped when not connected to the boiler.  
17  
It is important to guard against gas valve fouling from  
contaminants in the gas ways. Such fouling may cause improper  
operation, fire or explosion. If copper supply lines are used they  
must be approved for gas service.  
TABLE 8.  
SINGLE UNIT INSTALLATION, SUGGESTED GAS PIPE  
SIZING. MAXIMUM EQUIVALENT PIPE LENGTH (IN FEET).  
2”  
2-1/2”  
3”  
4”  
BTU  
When local codes require a main manual shut-off valve outside  
the boiler jacket, a suitable main manual shut-off valve must be  
installed in a location complying with those codes.  
Input  
Nat  
70  
Pro  
Nat  
Pro  
-----  
200  
Nat  
-----  
-----  
Pro  
-----  
-----  
Nat  
-----  
-----  
Pro  
-----  
-----  
920,000  
150 175  
1,300,000 40  
1,700,000 20  
2,000,000 20  
2,600,000 10  
3,400,000 -----  
100  
60  
100  
70  
50  
30  
20  
Before attaching gas line be sure that all gas pipe is clean  
on inside. To trap any dirt or foreign material in the gas supply  
line, a drip leg (or sediment trap) must be incorporated in piping.  
The drip leg must be readily accessible and not subject to  
freezing conditions. Install in accordance with recommendations  
of serving gas supplier. Refer to the current edition of the National  
Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and  
Propane Installation Code, CAN/CSA B149.1  
150  
100  
70  
200  
150  
90  
-----  
-----  
200  
-----  
-----  
-----  
-----  
-----  
-----  
-----  
50  
30  
-----  
40  
50  
125 200  
3
@
@
Natural gas 1000 Btu/ft^ , 0.60 specific gravity  
0.3 in. w.c. pressure drop.  
0.3 in. w.c. pressure drop.  
Size of gas supply piping may be larger than heater connection  
on installations where a significant run of piping is required.  
3
Propane gas 2500 Btu/ft^ , 1.50 specific gravity  
TABLE 9.  
To prevent damage, care must be taken not to apply too much  
torque when attaching gas supply pipe to boiler gas inlet. When  
installing and tightening gas piping use a second wrench to hold  
the gas valve to keep the valve from turning. To prevent damage  
to the gas valve do not use pipe wrench on the valve body.  
SINGLE UNIT INSTALLATION, SUGGESTED GAS PIPE  
SIZING. MAXIMUM EQUIVALENT PIPE LENGTH (IN FEET).  
2”  
2-1/2”  
3”  
4”  
BTU  
Input  
Nat  
125  
Pro  
Nat  
Pro  
-----  
-----  
Nat  
-----  
-----  
Pro  
-----  
-----  
Nat  
-----  
-----  
Pro  
-----  
-----  
Fittings and unions in gas line must be of metal to metal type.  
Apply joint compounds (pipe dope) sparingly and only to the  
male threads of pipe joints. Do not apply compound to the first  
two threads. Use compounds resistant to the action of liquefied  
petroleum gases. The boiler and its gas connection must be leak  
tested before placing the boiler in operation.  
920,000  
200 200  
1,300,000 80  
1,700,000 40  
2,000,000 30  
2,600,000 20  
3,400,000 10  
175  
100  
80  
175  
100  
80  
-----  
200  
125  
70  
-----  
200  
150  
90  
-----  
-----  
-----  
200  
-----  
-----  
-----  
-----  
-----  
-----  
-----  
-----  
50  
50  
GAS SUPPLY LINE SIZING  
30  
30  
The gas piping installation must be capable of supplying the  
maximum probable gas demand without excessive pressure loss.  
Depending on local practices, the ALLOWABLE PRESSURE  
LOSS between the gas meter, or service regulator and each  
appliance is generally 0.3 or 0.5 inches of water column (0.075  
or 0.124 kPa).  
3
@
@
Natural gas 1000 Btu/ft^ , 0.63 specific gravity  
0.5 in. w.c. pressure drop.  
0.5 in. w.c. pressure drop.  
3
Propane gas 2500 Btu/ft^ , 1.50 specific gravity  
CORROSIVE MATERIALS AND CONTAMINATION  
SOURCES  
For single boiler installation, refer to Table 8 and Table 9 to size  
iron pipe or equivalent gas supply line size to be used with single  
unit.  
Products to avoid:  
• Spray cans containing chloro/fluorocarbons  
For multiple boiler installation or installations of a single boiler  
with other gas appliances, please refer to Table 10 and Table 11  
on Page 20 to size iron pipe or equivalent gas supply line. These  
tables are taken from the current edition of the National Fuel Gas  
Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane  
Installation Code, CAN/CSA B149.1.  
• Permanent wave solutions  
• Chlorinated waxes/cleaners  
• Chlorine-based swimming pool chemicals  
• Calcium chloride used for thawing  
• Sodium chloride used for water softening  
• Refrigerant leaks  
column (0.124 kPa), and a gas with a specific gravity of  
0.60 and a heating value of 1,000 BTU/ft3, approximately  
that of Natural Gas.  
• Paint or varnish removers  
• Hydrochloric acid/muriatic acid  
• Cements and glues  
column (0.124 kPa), and a gas with a specific gravity of  
1.53 and a heating value of 2,500 BTU/ft3, approximately  
that of Propane Gas.  
• Antistatic fabric softeners used in clothes dryers  
• Chlorine-type bleaches, detergents, and cleaning  
solvents found in household laundry rooms  
Where it is necessary to use more than the average number of  
fittings (i.e., elbows, tees and valves in gas supply line) use a  
pipe larger than specified to compensate for increased pressure  
drop.  
• Adhesives used to fasten building products and other  
similar products  
Areas likely to have contaminants:  
• Dry cleaning/laundry areas and establishments  
Table 8 and Table 9 shows the maximum equivalent gas pipe  
length for a single unit installation. It does not take into account  
other appliances that may be connected to the gas line.  
For installation of multiple units, or instances where several  
appliances are connected to the same line, use Table 10 and  
• Swimming pools  
• Metal fabrication plants  
• Beauty shops  
Refrigeration repair shops  
• Photo processing plants  
18  
   
LOW VOLTAGE CONTROL WIRING  
• Auto body shops  
1. Header Terminals: In case of Hydronic Boilers, the header  
terminals are connected to the hydronic loop header sensor.  
Whereas in case of Hot water Boilers the header terminals  
are connected to the tank sensor where the temperature can  
• Plastic manufacturing plants  
• Furniture refinishing areas and establishments  
• New building construction  
• Remodeling areas  
Common household products, pool and laundry products may  
contain fluorine or chlorine compounds. When these chemicals  
come in contact with the boiler, they react and can form strong  
acids. The acid can spoil the boiler wall, causing serious damage  
and may result in flue gas spillage or boiler water leakage into  
the building.  
2. Outdoor Terminals: In case of Hydronic Boilers, they are  
connected to the outdoor sensors. But in case of Hot water  
Boilers, they are not connected. See Figure 15. The outdoor  
sensors must be mounted with cable inlet facing down  
as shown in Figure 16. The maximum length of the wire  
connecting from the boiler to the outdoor sensor must be no  
more than 50 feet.  
If the above mentioned contaminants and corrosive materials  
chemicals are present near the location of the boiler, make sure  
to remove the boiler permanently or relocate air inlet and vent  
terminations to other areas.  
3. MB2 and COM2 terminals are meant for building  
management systems.  
FIELD WIRING  
120 VAC POWER SUPPLY WIRING  
A dedicated, single phase, 30-60 amp (refer to Table 6 on Page  
8) circuit breaker with a grounded neutral should be provided to  
supply power to the boilers. Use #10 AWG wire for the 120 VAC  
power supply to the boiler. All 120 VAC power supply connections  
must be made as shown in Figure 14. These connections  
should be made at the rear of the unit where a wiring junction  
box is provided. Field installed power supply wiring to the boiler  
should be installed in conduit. This conduit and wiring should  
be separate from any other conduit/wiring to guard against EMI  
(electromagnetic interference).  
FIGURE 15. LOW VOLTAGE CONTROL WIRING  
POWER SUPPLY CHECK  
To reduce the possibility of electrical interference with the boiler’s  
controlsystemthepowersupplyvoltage, polarityandgroundmust  
be checked. Using an AC volt meter check the 120 VAC power  
supply wiring from the breaker prior to making power supply  
connections at the boiler. Confirm the power supply voltage &  
polarity are correct and that an adequate ground connection is  
present by performing the three voltage tests below. See Figure  
All low voltage control wiring connections must be made as  
shown in Figure 14. These connections should be made at the  
rear of the unit where a wiring junction box is provided. Field  
installed wiring inside 1/2 inch conduit is installed between the  
junction box on the back of the boiler and the temperature probe  
and/or field supplied external control being used. This conduit  
and wiring should be separate from any other conduit/wiring to  
guard against EMI (electromagnetic interference).  
Confirm RMS voltage between:  
H and GND = 108 VAC minimum, 132 VAC maximum.  
N and H = 108 VAC minimum, 132 VAC maximum.  
N and GND = < 1 VAC maximum.  
FIGURE 16. OUTDOOR SENSOR  
FIGURE 14. FIELD WIRING  
The outdoor sensor must be mounted in a shaded location, to  
avoid direct sunlight. It must be atleast 3 feet away from any  
exhaust, dryer, bathroom or other building vents. It must be  
located on the north side of th building, above the expected snow  
line where ice and debris cannot cover it.  
19  
     
20  
   
GENERAL REQUIREMENTS  
REQUIRED ABILITY  
REPLACING EXISTING COMMON VENTED BOILER  
Installation or service of this boiler requires ability equivalent to  
that of a licensed tradesman in the field involved. Plumbing, air  
supply, venting, gas supply, and electrical work are required.  
NOTE: This section does not describe a method for common  
venting XP units. It describes what must be done when a unit  
is removed from a common vent system. The XP units require  
special vent systems and fans for common vent. Contact the  
factory if you have questions about common venting XP units.  
LOCATION  
When an existing boiler is removed from a common venting  
system, the common venting system is likely to be too large  
for proper venting of the appliances remaining connected to it.  
At the time of removal of an existing boiler, the following steps  
should be followed with each appliance remaining connected to  
the common venting system placed in operation, while the other  
appliances remaining connected to the common venting system  
are not in operation.  
When installing the boiler, consideration must be given to proper  
location. The location selected should provide adequate air  
supply and be as centralized with the piping system as possible.  
1. Seal any unused openings in the common venting system.  
2. Visually inspect the venting system for proper size and  
horizontal pitch and determine there is no blockage or  
restriction, leakage, corrosion and deficiencies which could  
cause an unsafe condition.  
3. In so far as it is practical, close all building doors and  
windows and all doors between the space in which the  
appliances remaining connected to the common venting  
system are located and other spaces of the building. Turn  
on clothes dryers and any appliance not connected to the  
common venting system. Turn on any exhaust fans, such as  
range hoods and bathroom exhausts, so they will operate  
at maximum speed. Do not operate a summer exhaust fan.  
Close fireplace dampers.  
4. Place in operation the appliance being inspected. Follow the  
lighting instructions. Adjust thermostat so the appliance will  
operate continuously.  
5. Test for spillage at the draft hood relief opening after 5  
minutes of main burner operation. Use the flame of a match  
or candle, or smoke from a cigarette, cigar or pipe.  
6. After it has been determined that each appliance remaining  
connected to the common venting system properly vents  
when tested as outlined above, return doors, windows,  
exhaust fans, fireplace dampers and any other gas-burning  
appliance to their previous condition of use.  
7. Any improper operation of the common venting system  
should be corrected so that the installation conforms with  
the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/  
or CSA B149.1, Installation Codes. When resizing any  
portion of the common venting system, the common venting  
system should be resized to approach the minimum size as  
determined using the appropriate tables and guidelines in the  
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA  
B149.1, Installation Codes.  
This boiler is intended for Indoor Installation only, and should not  
be installed where freezing temperatures or any moisture could  
damage the external components of the boiler.  
21  
LEVELING  
PANELS AND COVERS  
Because this unit is a Category IV appliance it produces some  
amounts of condensation. The unit has a condensation disposal  
system that requires this unit to be level to properly drain. Each  
unit should be checked to be certain that it is level prior to starting  
the unit.  
All panels and covers (e.g. control and junction box covers; front,  
side and rear panels of boiler) must be in place after service and/  
or before operation of boiler. This will ensure that all gas ignition  
components will be protected from water.  
The XP is a low-pressure boiler (Category IV) to be used as  
either hot water supply (domestic/commercial water heating) or  
hot water heating (hydronic) application. Category IV appliances  
are often termed “High Efficiency” appliances.  
If the unit is not level, obtain and insert shims under the feet at  
the frame base to correct this condition.  
AIR REQUIREMENTS  
CHEMICAL VAPOR CORROSION  
Boiler corrosion and component failure can be caused by the  
heating and breakdown of airborne chemical vapors. Spray can  
propellants, cleaning solvents, refrigerator and air conditioning  
refrigerants, swimming pool chemicals, calcium and sodium  
chloride (water softener salt), waxes, and process chemicals  
are typical compounds which are potentially corrosive. These  
materials are corrosive at very low concentration levels with little  
or no odor to reveal their presence.  
Breathing Hazard - Carbon Monoxide Gas  
Install appliance in accordance with  
the Instruction Manual and NFPA 54 or  
CAN/CSA-B149.1.  
To avoid injury, combustion and ventilation  
air must be taken from outdoors.  
Do not place chemical vapor emitting  
products near water heater.  
Products of this sort should not be stored near boiler. Also, air  
which is brought in contact with boiler should not contain any  
of these chemicals. If necessary, uncontaminated air should be  
obtained from remote or outside sources. Failure to observe this  
requirement will void warranty.  
Breathing carbon monoxide can cause brain damage or  
death. Always read and understand instruction manual.  
INSTALLATION CLEARANCES  
For safe operation an adequate supply of fresh uncontaminated  
air for combustion and ventilation must be provided.  
This boiler is approved for installation in an alcove with minimum  
clearances to combustibles.  
An insufficient supply of air can cause recirculation of combustion  
products resulting in contamination that may be hazardous to  
life. Such a condition often will result in a yellow, luminous burner  
flame, causing sooting of the combustion chamber, burners and  
flue tubes and creates a risk of asphyxiation.  
TABLE 12. INSTALLATION CLEARANCES  
RECOMMENDED  
SERVICE  
CLEARANCES  
CLEARANCES FROM  
COMBUSTIBLE  
MATERIALS  
Do not install the boiler in a confined space unless an adequate  
supply of air for combustion and ventilation is brought in to that  
space using the methods described in the Confined Space  
section that follows.  
Front  
Rear  
Left  
30" (762 mm)  
36" (610 mm)  
24 " (610 mm)  
24 " (610 mm)  
24" (610 mm)  
8" (203 mm)  
24" (610 mm)  
1" (25.4 mm)  
2" (51 mm)  
Never obstruct the flow of ventilation air. If you have any doubts  
or questions at all, call your gas supplier. Failure to provide the  
proper amount of combustion air can result in a fire or explosion  
and cause property damage, serious bodily injury or death.  
Right  
Top  
6" (152 mm)  
UNCONFINED SPACE  
2” (51 mm) clearance is allowable from combustible construction  
for hot water pipes.  
An unconfined space is one whose volume is not less than 50  
cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the  
total input rating of all appliances installed in the space. Rooms  
communicating directly with the space, in which the appliances  
are installed, through openings not furnished with doors, are  
considered a part of the unconfined space.  
Sufficient area should be provided at the front and rear of the  
unit for proper servicing. In a utility room installation, the door  
opening should be wide enough to allow the boiler to enter or  
to permit the replacement of another appliance such as a boiler.  
FLOORING AND FOUNDATION:  
All models are approved for installation on combustible flooring,  
but must never be installed on carpeting. Do not install the boiler  
on carpeting even if foundation is used. Fire can result, causing  
severe personal injury, death, or substantial property damage.  
Makeup air requirements for the operation of exhaust fans,  
kitchen ventilation systems, clothes dryers and fireplaces shall  
also be considered in determining the adequacy of a space to  
provide combustion, ventilation and dilution air.  
If flooding is possible, elevate the boiler sufficiently to prevent  
water from reaching the boiler.  
UNUSUALLY TIGHT CONSTRUCTION  
In unconfined spaces in buildings, infiltration may be adequate  
to provide air for combustion, ventilation and dilution of flue  
gases. However, in buildings of unusually tight construction (for  
example, weather stripping, heavily insulated, caulked, vapor  
barrier, etc.) additional air must be provided using the methods  
described in the Confined Space section that follows.  
22  
CONFINED SPACE  
OUTDOOR AIR THROUGH TWO OPENINGS  
A confined space is one whose volume is less than 50 cubic  
feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input  
rating of all appliances installed in the space.  
Openings must be installed to provide fresh air for combustion,  
ventilation and dilution in confined spaces. The required size for  
the openings is dependent on the method used to provide fresh  
air to the confined space and the total Btu/hr input rating of all  
appliances installed in the space.  
DIRECT VENT APPLIANCES  
Appliances installed in a direct vent configuration that derive all  
air for combustion from the outdoor atmosphere through sealed  
intake air piping are not factored in the total appliance input Btu/  
hr calculations used to determine the size of openings providing  
fresh air into confined spaces.  
FIGURE 17. OUTDOOR AIR THROUGH TWO OPENINGS  
EXHAUST FANS  
The confined space shall be provided with two permanent  
openings, one commencing within 12 inches (300 mm) of the top  
and one commencing within 12 inches (300 mm) of the bottom of  
the enclosure. The openings shall communicate directly with the  
Where exhaust fans are installed, additional air shall be provided  
to replace the exhausted air. When an exhaust fan is installed  
in the same space with a water heater, sufficient openings to  
provide fresh air must be provided that accommodate the  
requirements for all appliances in the room and the exhaust fan.  
Undersized openings will cause air to be drawn into the room  
through the water heater’s vent system causing poor combustion.  
Sooting, serious damage to the water heater and the risk of fire  
or explosion may result. It can also create a risk of asphyxiation.  
Each opening shall have a minimum free area of 1 square inch  
per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating  
of all appliances installed in the enclosure. Each opening shall  
not be less than 100 square inches (645 cm2).  
OUTDOOR AIR THROUGH ONE OPENING  
LOUVERS AND GRILLES  
The free areas of the fresh air openings in the instructions that  
follow do not take in to account the presence of louvers, grilles or  
screens in the openings.  
The required size of openings for combustion, ventilation and  
dilution air shall be based on the “net free area” of each opening.  
Where the free area through a design of louver or grille or screen  
is known, it shall be used in calculating the size of opening  
required to provide the free area specified. Where the louver and  
grille design and free area are not known, it shall be assumed  
that wood louvers will have 25% free area and metal louvers and  
grilles will have 75% free area. Non motorized louvers and grilles  
shall be fixed in the open position.  
FRESH AIR OPENINGS FOR CONFINED SPACES  
The following instructions shall be used to calculate the size,  
number and placement of openings providing fresh air for  
combustion, ventilation and dilution in confined spaces. The  
illustrations shown in this section of the manual are a reference  
for the openings that provide fresh air into confined spaces  
only. Do not refer to these illustrations for the purpose of vent  
installation. See Venting section on Page 25 for complete venting  
installation instructions.  
FIGURE 18. OUTDOOR AIR THROUGH ONE OPENING  
Alternatively a single permanent opening, commencing within 12  
inches (300 mm) of the top of the enclosure, shall be provided.  
See Figure 18. The water heater shall have clearances of at  
least 1 inch (25 mm) from the sides and back and 6 inches (150  
mm) from the front of the appliance. The opening shall directly  
communicate with the outdoors or shall communicate through a  
vertical or horizontal duct to the outdoors or spaces that freely  
communicate with the outdoors and shall have a minimum free  
area of the following:  
1. 1 square inch per 3000 Btu/hr (700 mm2 per kW) of the total  
input rating of all appliances located in the enclosure, and  
2. Not less than the sum of the areas of all vent connectors in  
the space.  
23  
   
The confined space shall be provided with two permanent vertical  
ducts, one commencing within 12 inches (300 mm) of the top and  
one commencing within 12 inches (300 mm) of the bottom of the  
enclosure. The vertical ducts shall communicate directly with the  
OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS  
Each duct opening shall have a minimum free area of 1 square  
inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input  
rating of all appliances installed in the enclosure.  
When ducts are used, they shall be of the same cross sectional  
area as the free area of the openings to which they connect.  
The minimum dimension of rectangular air ducts shall be not less  
than 3 inches.  
AIR FROM OTHER INDOOR SPACES  
FIGURE 19. OUTDOOR AIR THROUGH TWO HORIZONTAL  
DUCTS  
The confined space shall be provided with two permanent  
horizontal ducts, one commencing within 12 inches (300 mm) of  
the top and one commencing within 12 inches (300 mm) of the  
bottom of the enclosure. The horizontal ducts shall communicate  
Each duct opening shall have a minimum free area of 1 square  
inch per 2,000 Btu/hr (1100 mm2 per kW) of the aggregate input  
rating of all appliances installed in the enclosure.  
When ducts are used, they shall be of the same cross sectional  
area as the free area of the openings to which they connect.  
The minimum dimension of rectangular air ducts shall be not less  
than 3 inches.  
FIGURE 21. AIR FROM OTHER INDOOR SPACES  
OUTDOOR AIR THROUGH TWO VERTICAL DUCTS  
The confined space shall be provided with two permanent  
openings, one commencing within 12 inches (300 mm) of the top  
and one commencing within 12 inches (300 mm) of the bottom of  
The illustrations shown in this section of the manual are a  
reference for the openings that provide fresh air into confined  
spaces only.  
Do not refer to these illustrations for the purpose of vent  
installation.  
Each opening shall communicate directly with an additional  
room(s) of sufficient volume so that the combined volume of all  
spaces meets the criteria for an Unconfined Space.  
Each opening shall have a minimum free area of 1 square inch  
per 1,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating  
of all appliances installed in the enclosure. Each opening shall  
not be less than 100 square inches (645 cm2).  
FIGURE 20. OUTDOOR AIR THROUGH TWO VERTICAL  
DUCTS  
24  
     
VENTING  
STAINLESS STEEL INSTALLATION:  
Installations must comply with applicable national, state, and  
local codes. Stainless steel vent systems must be listed as a UL-  
1738 approved system for the United States and a ULC-S636  
approved system for Canada.  
Installation of the approved AL 29-4C stainless steel venting  
material should adhere to the stainless steel vent manufacturer’s  
installation instructions supplied with the vent system.  
Refer to Table 14 and Table 15 on Page 36 for air intake and vent  
pipe sizes.  
AIR INTAKE/VENT CONNECTIONS  
1. Air Intake Adapter: Provides an inlet for combustion air  
directly to the unit from outdoors.  
Vent sizing, installation and termination should be in accordance  
with this installation manual. This boiler must be vented using  
PVC/CPVC or Stainless Steel materials.  
2. Vent Outlet: Provides an outlet for combustion gases to  
outdoors.  
All electrical power and gas must be turned off prior to any  
installation of the venting system.  
VENTING SYSTEM  
This boiler may be installed in six separate orientations  
depending on the requirements of the building and  
the appliance. The installer must decide which method is most  
appropriate for each installation. These orientations are:  
VENT INSTALLATION CONSIDERATIONS  
This boiler is a category IV appliance that can be vented using  
room air for intake combustion air, or direct vented so that all  
intake air for combustion comes from the outside through a  
sealed pipe. When installing this appliance as direct vent, special  
vent kits are required.  
1. Vertical Termination - vertical vent termination through  
un-enclosed or enclosed areas with roof penetration, see  
2. Through-the-Wall Termination (TWT) - horizontal vent  
on Page 28.  
In cold climates any water vapor remaining in the flue gases will  
condense into a cloud of vapor at the point where the vent system  
exits the building. Special consideration is recommended, before  
locating the vent termination near walkways, windows and  
building entrances.  
3. Horizontal Direct Vent - using TWT to exhaust flue  
products and PVC piping to bring combustion air to the boiler  
from the outside. See Figure 27 on Page 29 and Figure 30  
on Page 30.  
Direct venting into dead spaces such as alleys, atriums, and  
inside corners can cause recirculation of flue gases. Recirculation  
of flue gases will cause sooting, premature failure of the heat  
exchanger, and icing of the combustion air intake during severe  
cold weather. To prevent the recirculation of flue gases, maintain  
as much distance as possible between the combustion air  
intake and the exhaust vent terminal. Due to large volumes of  
flue gases, multiple boiler applications also require additional  
distance between the intake and the exhaust terminals.  
4. Vertical Direct Vent - using a vertical vent termination to  
exhaust flue products and PVC piping to bring combustion  
air to the boiler from outside, see Figure 28 on Page 29 and  
GENERAL VENT INSTALLATION PROCEDURE  
Prior to beginning the installation of the vent system,  
determine and obtain all parts required for the installation.  
Proper operation of the boiler and venting system is depen-  
dent upon use of all specified parts and installation techniques;  
both safety and proper performance of the system may suffer if  
instructions are not followed.  
This boiler can be vented with PVC/CPVC or an UL approved AL  
29-4C Stainless Steel venting material which are explained in the  
following pages.  
PVC/CPVC INSTALLATION:  
Installation must comply with local requirements and with the  
National Fuel Gas Code, ANSI Z223.1 for U.S. installations or  
CSA B149.1 for Canadian installations.  
Refer to Table 13 on Page 36 for PVC/CPVC piping materials.  
All PVC vent pipes must be glued, properly supported, and  
the exhaust must be pitched a minimum of a 1/4 inch per foot  
back to the boiler (to allow drainage of condensate).  
This appliance requires a special venting system. Use only  
the vent materials, primer, and cement specified in this  
manual to make the vent connections. Failure to follow this  
warning could result in fire, personal injury, or death.  
Note: Make sure that for PVC venting installation, the  
first 10 feet of vent must be CPVC or stainless steel and  
the set point temperature of the boiler must not exceed  
200 °F.  
25  
AIR INLET PIPE MATERIALS  
VENT AND AIR PIPE INSTALLATION  
Make sure the air inlet pipe(s) are sealed. The acceptable air 1. Measure from the boiler level to vent. Refer to the Table 14  
inlet pipe materials are:  
on Page 36 for the allowable lengths.  
• PVC/CPVC  
• AL 29-4C  
2. Prepare pipes to the required lengths and deburr the inside  
and outside of the pipe ends. Chamfer outside the pipe end  
to ensure even cement distribution when joining.  
An adapter is provided for transition between the air inlet  
connection on the boiler and the plastic air inlet pipe.  
3. Clean all pipe ends and fittings using a clean dry rag.  
(Moisture will retard curing and dirt or grease will prevent  
adhesion.)  
Seal all joints and seams of the air inlet pipe using either  
Aluminum Foil Duct Tape meeting UL Standard 723 or 181A-P or  
a high quality UL Listed silicone sealant. Do not install seams of  
vent pipe on the bottom of horizontal runs.  
4. Dry fit vent or air piping to ensure proper fit before assembling  
any joint. The pipe should go a third to two-thirds into the  
fitting to ensure proper sealing after cement is applied.  
Secure all joints with a minimum of 3 sheet metal screws or pop  
rivets. Apply Aluminum Foil Duct Tape or silicone sealant to all  
screws or rivets installed in the vent pipe.  
5. Priming and Cementing:  
• Handle pipes and fittings carefully to prevent  
contamination of surfaces.  
Make sure that the air inlet pipes are properly supported.  
• Apply an even coat of primer to the fitting socket.  
The PVC/ CPVC air inlet pipe must be cleaned and sealed with  
the pipe manufacturer’s recommended solvents and standard  
commercial pipe cement for the material used. The PVC, CPVC,  
air inlet pipe should use a silicone sealant to ensure a proper seal  
at the boiler connection and the air intake adapter connection.  
Proper sealing of the air inlet pipe ensures that combustion air  
will be free of contaminants and supplied in proper volume.  
• Apply an even coat of primer to the pipe end to  
approximately 1/2" beyond the socket depth.  
• Apply a second primer coat to the fitting socket.  
• While primer is still wet, apply an even coat of approved  
cement to the pipe equal to the depth of the fitting  
socket.  
• While primer is still wet, apply an even coat of approved  
cement to the fitting socket.  
• Apply a second coat of cement to the pipe.  
• While the cement is still wet, insert the pipe into the  
fitting, if possible twist the pipe a 1/4 turn as you insert it.  
Note: If voids are present, sufficient cement was not applied and  
joint could be defective.  
• Clear excess cement from the joint removing ring or  
beads as it will needlessly soften the pipe.  
When a sidewall or vertical rooftop combustion air supply system  
is disconnected for any reason, the air inlet pipe must be resealed  
to ensure that combustion air will be free of contaminants and  
supplied in proper volume.  
Failure to properly seal all joints and seams may result in flue  
gas recirculation, spillage of flue products and carbon monoxide  
emissions causing severe personal injury or death.  
FIGURE 22. PVC/CPVC VENTING WITH ADAPTER  
REQUIREMENTS FOR INSTALLATION IN CANADA  
1. Installations must be made with a vent pipe system certified  
to ULC-S636. IPEX is an approved vent manufacturer in  
Canada supplying vent material listed to ULC-S636.  
2. The initial 3 feet of plastic vent pipe from the appliance flue  
outlet must be readily accessible for visual inspection.  
3. The components of the certified vent system must not be  
interchanged with other vent systems or unlisted pipe/  
fittings.  
FIGURE 23. PVC/CPVC VENTING - HORIZONTAL  
26  
(30.5 m). A maximum of three 90° elbows can be used.  
Minimum vertical vent is 7 equivalent feet (2.1 m) for  
direct vent installations. Standard minimum vertical vent  
length is 7 feet (2.1 m). See Figure 25, Figure 28 thru  
Figure 30 for differences between standard and direct  
vent installations.  
3. An AL 29-4C® Vent Vertical Vent Terminal must be used at  
the termination.  
4. Maintain a minimum of 6 feet (2.0 m) separation between  
the air intake and the exhaust terminals.  
HORIZONTAL INSTALLATION REQUIREMENTS  
1. The vent system must terminate with the Through-the-Wall  
Termination (TWT) kits. Do not locate the terminal within 8 feet  
(2.5 m) of an inside corner of a building or adjacent to outside  
walls, shrubs or other such objects that may cause adverse  
wind conditions in the immediate area.  
2. The TWT should be located not less than 12 inches (305  
mm) above grade or, in geographical areas where snow  
accumulates, no less than 12 inches (305 mm) above antici-  
patedsnowline.EnsurethatTWTisprotectedagainstblockage  
which may occur during ice buildup or snowstorms. The TWT  
should terminate at least 3 feet (1.0 m) above any forced air  
inlet within 10 feet (3.0 m), except when the forced air inlet  
is the combustion air intake of a direct vent appliance. The  
TWT should terminate at least 4 feet (1.2 m) below, 4 feet  
(1.2 m) horizontally from or 1 foot (305 mm) above any door,  
window or gravity air inlet into any building as provided in the  
current edition of the national fuel gas code ANSI Z223.1.  
Inaddition, aminimumclearanceof4feet(1.2m)horizontally  
from, and in no case above or below, unless the 4 feet (1.2  
m) of horizontal distance is maintained from electric meters,  
gas meters, regulators and relief equipment.  
FIGURE 24. PVC/CPVC VENTING - VERTICAL  
VENTING SUPPORTS  
Care must be taken in the installation of the venting system  
that adequate support is maintained throughout the installation  
process. When extending more than 10 feet (3.0 m) vertically,  
vertical support kits are required once every 10 feet (3.0 m) of  
vertical run. Vertical support is also required immediately after  
any transition (elbow, tee, etc.) to vertical of over 10 feet (3.0 m)  
of run and after any offset in the vertical run.  
The support brackets (supplied in the Vertical Support Kit)  
are to be securely fastened to a solid vertical member of the  
building using the appropriate fasteners; i.e., wood screws for  
wood framing, machine or tapping screws for structural steel  
or masonry anchors for solid masonry. The bracket should be  
located so that it will not interfere with any joints of the venting  
system. The bottom most support bracket should be located  
directly above the first transition from horizontal to vertical.  
3. This horizontal exhaust vent system must pitch upward toward  
the termination at 1/4 inch per foot (21 mm per meter).  
4. The TWT is designed such that the building is protected from  
degradation by flue gas and condensate. However, if additional  
protection is desired, install against the wall a non-corrosive  
metal sheet under the TWT.  
If a means of support for the brackets is not available and  
horizontal vent sections are present, install hanger straps  
(made from non-combustible material) as close to the points of  
transition as possible. If the horizontal portions of the vent and/or  
vent connector are longer than 6 feet (2.0 m), then install hanger  
straps every 6 feet (2.0 m) to support the connector.  
5. Due to the normal formation of water vapor in the combustion  
process, horizontal terminations must not be located over  
areas of pedestrian or vehicular traffic, (i.e., public walkways  
or over areas where condensate could create a nuisance or  
hazard). This is especially true in colder climates where ice  
buildup is likely to occur. A.O. Smith Corporation will not be  
held liable for any personal injury or property damage due to  
any dislodging of ice.  
Do not rivet or screw the straps to the conduit or otherwise  
puncture the conduit wall. Instead, wrap an extra loop of strap  
around the conduit to hold it in position, or attach the strap to  
the center screw of the double wall AL 29-4C® vent coupling,  
if applicable.  
DIRECT VENT INSTALLATION REQUIREMENTS  
The labels in the Direct Vent Kit must be affixed to the boiler in  
locations specified by the instruction sheet provided in the kit.  
The following are requirements for the Air-Intake Terminal (AIT):  
VERTICAL INSTALLATION REQUIREMENTS  
1. The vent system must terminate at least 3 feet (1.0 m) and  
no more than 6 feet (2.0 m) above the roof line and no closer  
than 10 feet (3.0 m) from any wall or vertical structure. If the  
exhaust vent terminal is within 10 feet (3.0 m) of a wall or  
parapet, it must extend a minimum of 2 feet (610 mm) above  
the wall or parapet, see Figure 25 on Page 28 and Figure  
1. The Air-Intake System (AIS) must terminate with the venting  
equipment provided with the boiler.  
2. The AIT should not be located less than 3 feet (1.0 m) below  
any exhaust vent within 10 feet (3.0 m).  
3. The total horizontal distance of the AIS from the boiler’s  
Blower Adapter to the outside of the “AIT” should not be  
greater than 100 equivalent feet (30.5 m) of vent pipe nor  
less than 3 feet (1.0 m), excluding elbows. A maximum of 3  
elbows, equivalent to 10 feet (3.0 m) each of pipe may be  
used.  
2. For direct vent installations, the total distance of the vent  
system from the boiler vent connector to the vertical  
vent termination should not exceed 100 equivalent feet  
27  
MODELS  
(XB/XW)  
VENT KIT NUMBERS  
(RAIN CAP)  
1000  
1300  
320884-000  
320884-001  
1700  
2000  
2600  
3400  
320884-001  
320884-001  
320884-001  
320884-002  
FIGURE 25. VERTICAL VENTING  
MODELS  
(XB/XW)  
VENT KIT NUMBERS  
(TEE)  
1000  
1300  
321765-000  
321765-001  
1700  
2000  
2600  
3400  
321765-001  
321765-001  
321765-001  
321765-002  
FIGURE 26. HORIZONTAL VENTING  
28  
   
MODELS  
(XB/XW)  
VENT  
KIT NUMBERS  
(TEE)  
AIR INTAKE  
KIT NUMBERS  
(ELBOW)  
1000  
1300  
1700  
2000  
2600  
3400  
321765-000  
321765-001  
321765-001  
321765-001  
321765-001  
321765-002  
321764-000  
321764-000  
321764-001  
321764-001  
321764-001  
321764-002  
FIGURE 27. DIRECT VENT HORIZONTAL  
MODELS  
(XB/XW)  
VENT  
KIT NUMBERS  
(RAIN CAP)  
AIR INTAKE  
KIT NUMBERS  
(ELBOW)  
1000  
1300  
1700  
2000  
2600  
3400  
320884-000  
320884-001  
320884-001  
320884-001  
320884-001  
320884-002  
321764-000  
321764-000  
321764-001  
321764-001  
321764-001  
321764-002  
FIGURE 28. DIRECT VENT VERTICAL  
29  
   
MODELS  
(XB/XW)  
VENT  
KIT NUMBERS  
(RAIN CAP)  
AIR INTAKE  
KIT NUMBERS  
(ELBOW)  
1000  
1300  
1700  
2000  
2600  
3400  
320884-000  
320884-001  
320884-001  
320884-001  
320884-001  
320884-002  
321764-000  
321764-000  
321764-001  
321764-001  
321764-001  
321764-002  
FIGURE 29. DIRECT VENT, VERTICAL VENT HORIZONTAL INTAKE  
MODELS  
(XB/XW)  
VENT  
KIT NUMBERS  
(TEE)  
AIR INTAKE  
KIT NUMBERS  
(ELBOW)  
1000  
1300  
1700  
2000  
2600  
3400  
321765-000  
321765-001  
321765-001  
321765-001  
321765-001  
321765-002  
321764-000  
321764-000  
321764-001  
321764-001  
321764-001  
321764-002  
FIGURE 30. DIRECT VENT, HORIZONTAL VENT VERTICAL INTAKE  
30  
   
TERMINATION CLEARANCES SIDEWALL POWER VENT  
POWER VENT  
(using room air for combustion)  
EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION  
G
V
H
D
A
E
v
L
B
v
B
B
B
V
C
B
D
E
X
I
F
E
D
CLOSED  
E
X
I
OPERABL  
F
V
M
V
V
X
CLOSED  
V
E
X
OPERABL  
V
F
B
K
J
A
VENT TERMINAL  
AIR SUPPLY INLET  
AREA WHERE TERMINAL IS NOT PERMITTED  
V
X
FIGURE 31. POWER VENT  
Vent terminal clearances for “Power Vent” installations. Power Vent configurations use room air for combustion.  
1
2
1
2
CANADIAN INSTALLATIONS  
US INSTALLATIONS  
CANADIAN INSTALLATIONS  
US INSTALLATIONS  
Clearance to each side  
of center line extended  
above meter/regulator  
assembly  
3 feet (91 cm) within a  
height 15 feet (4.5 m)  
above the meter/regulator  
assembly*  
Clearance above grade,  
veranda, porch, deck or 12 inches (30 cm)  
balcony  
3 feet (91 cm) within a height 15 feet  
(4.5 m) above the meter/  
regulator assembly  
12 inches (30 cm)  
A
B
H
I
6 inches (15 cm) for appliances up to  
10,000 Btu/hr (3 kW), 12 inches (30  
cm) for appliances between 10,000  
4 feet (1.2 m) below  
or to side of opening;  
Btu/hr (3 kW) and 100,000 Btu/hr (30 1 foot (30 cm) above  
kW), 36 inches (91 cm) for appliances opening  
above 100,000 Btu/hr (30 kW)  
Clearance to window  
or door that may be  
opened  
Clearance to service  
regulator vent outlet  
3 feet (91 cm)  
3 feet (91 cm)*  
6 inches (15 cm) for appliances up  
to 10,000 Btu/hr (3 kW), 12 inches  
(30 cm) for appliances between  
10,000 Btu/hr (3 kW) and 100,000  
Btu/hr (30kW), 36 inches (91cm)  
for appliances above 100,000 Btu/  
hr (30 kW)  
Clearance to a non  
mechanical air supply  
inlet into building or  
combustion air inlet to  
any other appliance  
4 feet (1.2 m) below or to  
side of opening; 1 foot  
(30 cm) above opening.  
Clearance to  
permanently closed  
window  
12 inches (30 cm)*  
12 inches (30 cm)*  
C
J
Vertical clearance to  
ventilated soffit located  
above the terminal  
within a horizontal  
distance of 2 feet (61  
cm) from the center line  
of the terminal  
3 feet (91 cm) above if  
within  
10 feet (3 m) horizontally  
Clearance to a  
mechanical air supply  
inlet  
12 inches (30 cm)*  
12 inches (30 cm)*  
12 inches (30 cm)*  
12 inches (30 cm)*  
6 feet (1.83 m)  
7 feet (2.13 m)†  
D
E
K
Clearance above paved  
sidewalk or paved  
driveway located on  
public property  
Clearance to  
unventilated soffit  
7 feet (2.13 m)  
L
Clearance under  
veranda, porch, deck, or 12 inches (30 cm) ‡  
balcony  
Clearance to outside  
corner  
2 feet (60 cm)*  
8 feet (2.44 m)*  
2 feet (60 cm)*  
8 feet (2.44 m)*  
12 inches (30 cm) ‡  
F
M
Clearance to inside  
corner  
G
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.  
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.  
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.  
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.  
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.  
31  
TERMINATION CLEARANCES SIDEWALL DIRECT VENT  
DIRECT VENT  
(using outdoor air for combustion)  
EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION  
G
V
H
D
A
E
v
L
B
v
B
B
B
V
C
B
D
E
X
I
F
E
D
CLOSED  
E
X
I
OPERABL  
F
V
M
V
V
X
CLOSED  
V
E
X
OPERABL  
V
F
B
K
J
A
VENT TERMINAL  
AIR SUPPLY INLET  
AREA WHERE TERMINAL IS NOT PERMITTED  
V
X
FIGURE 32. DIRECT VENT  
Vent terminal clearances for “Direct Vent” installations. Direct Vent configurations use outdoor air for combustion.  
1
2
1
2
CANADIAN INSTALLATIONS  
US INSTALLATIONS  
CANADIAN INSTALLATIONS  
US INSTALLATIONS  
Clearance to each side  
of center line extended  
above meter/regulator  
assembly  
Clearance above grade,  
veranda, porch, deck or 12 inches (30 cm)  
balcony  
3 feet (91 cm) within a height 15  
feet (4.5 m) above the meter/  
regulator assembly  
3 feet (91 cm) within a height  
15 feet (4.5 m) above the  
meter/regulator assembly*  
12 inches (30 cm)  
A
B
H
I
6 inches (15 cm)  
for appliances up to  
10,000 Btu/hr (3 kW),  
9 inches (23 cm) for  
appliances between  
10,000 Btu/hr (3 kW)  
and 50,000 Btu/hr (15  
kW), 12 inches (30 cm)  
for appliances above  
50,000 Btu/hr (15 kW)  
6 inches (15 cm) for appliances  
up to 10,000 Btu/hr (3 kW), 12  
inches (30 cm) for appliances  
between 10,000 Btu/hr (3 kW)  
and 100,000 Btu/hr (30 kW), 36  
inches (91 cm) for appliances  
above 100,000 Btu/hr (30 kW)  
Clearance to window or  
door that may be opened  
Clearance to service  
regulator vent outlet  
3 feet (91 cm)  
3 feet (91 cm)*  
6 inches (15 cm) for  
6 inches (15 cm) for appliances up  
to 10,000 Btu/hr (3 kW), 12 inches  
(30 cm) for appliances between  
10,000 Btu/hr (3 kW) and 100,000  
appliances up to 10,000  
Btu/hr (3 kW), 9 inches (23  
cm) for appliances between  
10,000 Btu/hr (3 kW) and  
50,000 Btu/hr (15 kW), 12  
inches (30 cm) for appliances  
above 50,000 Btu/hr (15 kW)  
Clearance to a non  
mechanical air supply  
inlet into building or  
Clearance to  
permanently closed  
window  
6 inches (15 cm)*  
6 inches (15 cm)*  
C
J
combustion air inlet to Btu/hr (30 kW), 36 inches (91 cm)  
any other appliance  
for appliances above 100,000 Btu/  
hr (30 kW)  
Vertical clearance to  
ventilated soffit located  
above the terminal within  
a horizontal distance of  
2 feet (61 cm) from the  
center line of the terminal  
Clearance to a  
mechanical air supply  
inlet  
3 feet (91 cm) above if within  
10 feet (3 m) horizontally  
12 inches (30 cm)*  
12 inches (30 cm)*  
12 inches (30 cm)*  
12 inches (30 cm)*  
6 feet (1.83 m)  
D
E
K
Clearance above  
Clearance to unventilated  
soffit  
paved sidewalk or  
paved driveway located  
on public property  
7 feet (2.13 m)†  
7 feet (2.13 m)†*  
L
Clearance under  
veranda, porch, deck,  
or balcony  
Clearance to outside  
corner  
2 feet (60 cm)*  
8 feet (2.44 m)*  
2 feet (60 cm)*  
8 feet (2.44 m)*  
12 inches (30 cm) ‡  
12 inches (30 cm) ‡*  
F
M
Clearance to inside  
corner  
G
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.  
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.  
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.  
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.  
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.  
32  
INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS  
For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed  
in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by  
the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the  
area of the venting, including but not limited to decks and porches, the following requirements should be satisfied:  
INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled  
equipment, the installing plumber or gasfitter should observe that a hard wired carbon monoxide detector with an alarm and battery  
back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter should  
observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling,  
building or structure served by the sidewall horizontal vented gas fueled equipment. It should be the responsibility of the property owner  
to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.  
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired  
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.  
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner should  
have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery  
operated carbon monoxide detector with an alarm should be installed.  
APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above  
provisions should comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified.  
SIGNAGE A metal or plastic identification plate should be permanently mounted to the exterior of the building at a minimum  
height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating  
appliance or equipment. The sign should read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY  
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”  
INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment should not approve  
the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance  
with the provisions of 248 CMR 5.08(2)(a) 1 through 4.  
EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54  
as adopted by the Board; and  
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the  
dwelling, building, or structure used in whole or in part for residential purposes.  
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manufacturer of Product  
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment,  
the instructions provided by the manufacturer for installation of the equipment and the venting system should include:  
1. Detailed instructions for the installation of the venting system design or the venting system components; and  
2. A complete parts list for the venting system design or venting system.  
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer  
of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue  
gases, but identifies “special venting systems,” the following requirements should be satisfied by the manufacturer:  
1. The referenced “special venting system” instructions should be included with the appliance or equipment installation instructions; and  
2. The “special venting systems” should be Product Approved by the Board, and the instructions for that system should include  
a parts list and detailed installation instructions.  
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting  
instructions, all parts lists for venting instructions, and/or all venting design instructions should remain with the appliance or  
equipment at the completion of the installation.  
33  
Do not terminate closer than 4 feet (1.2 m) horizontally from  
any electric meter, gas meter, regulator, relief valve, or other  
equipment. Never terminate above or below any of these within  
4 feet (1.2 m) horizontally.  
DIRECT VENT: HORIZONTAL TERMINATION  
Gas vent extending through an exterior wall must not terminate  
adjacent to a wall or below building extensions such as eaves,  
parapets, balconies, or decks. Failure to comply could result in  
severe personal injury, death, or substantial property damage.  
6. Locate terminations so they are not likely to be damaged by  
foreign objects, such as stones or balls, or subject to buildup  
of leaves or sediment.  
Installation must comply with local requirements and with the  
National Fuel Gas Code, ANSI Z223.1 for U.S. installations or  
CSA B149.1 for Canadian installations.  
VENT/AIR TERMINATION LOCATIONS:  
Follow these guidelines for locating the vent/air terminations:  
1. Make sure the total length of piping for vent or air do not  
exceed the limits mentioned in Table 14 and Table 15 on  
Page 36.  
2. Consider the surroundings when terminating the vent and  
air:  
• While positioning the vent termination, ensure vapors  
will not damage nearby shrubs, plants or air conditioning  
equipment.  
• The flue products will form a noticeable plume as they  
condense in cold air. Avoid areas where the plume could  
obstruct window views.  
• Prevailing winds could cause freezing of condensate  
and water/ice buildup where flue products impinge on  
building surfaces or plants.  
FIGURE 33. AIR/VENT TERMINATION - HORIZONTAL  
• Do not allow accidental contact of flue products with  
people or pets.  
• Do not locate the terminations near building corners,  
near adjacent buildings or surfaces, window wells,  
stairwells, alcoves, courtyards, or other recessed areas,  
where wind eddies could affect performance or cause  
recirculation .  
• Sidewall vent and air inlet terminations must terminate in  
the same pressure zone.  
• Do not terminate above any door or window, where  
condensate can freeze, causing ice formations.  
• Locate or monitor the vent to prevent condensate  
damage to exterior finishes.  
3. The air piping must terminate in a down-turned elbow, using  
a mesh screen. This setup will avoid recirculation of flue  
4. The vent piping must terminate with a Tee pointed upwards  
5. Maintain clearances as shown in Figure 33 and Figure 34.  
Vent must terminate:  
FIGURE 34. HORIZONTAL CLEARANCES - AIR/VENT  
TERMINATION  
• At least 6 feet (1.8 m) from adjacent walls.  
• No closer than 12 inches (305 mm) below roof overhang.  
• At least 7 feet (2.1 m) above any public walkway.  
• At least 3 feet (0.9 m) above any forced air intake within  
10 feet (3 m).  
• No closer than 12 inches (305 mm) below or horizontally  
from any door or window or any other gravity air inlet.  
Air inlet must terminate at least 12 inches (305 m) above grade or  
snow line; at least 12 inches (305 mm) below the vent termination;  
and the vent pipe must not extend more than 24 inches (610 mm)  
vertically outside the building as shown in Figure 33 and Figure  
34  
   
DIRECT VENTING: VERTICAL TERMINATION  
Installation must comply with local requirements and with the  
National Fuel Gas Code, ANSI Z223.1 for U.S. installations or  
CSA B149.1 for Canadian installations.  
VENT/AIR TERMINATION LOCATIONS:  
Follow these guidelines for locating the vent/air terminations:  
1. Make sure the total length of piping for vent or air do not  
exceed the limits mentioned in Table 14 and Table 15 on  
Page 36.  
2. The vent must terminate at least 3 feet above the highest  
place in which the vent penetrates the roof and at least 2  
feet above any part of a building within 10 feet horizontal.  
FIGURE 36. STAINLESS STEEL AIR/VENT TERMINATION -  
VERTICAL  
3. The air piping must terminate in a down-turned 180° elbow,  
using a mesh screen, no further than 2 feet (0.6 m) from the  
center of the vent pipe. This placement avoids recirculation  
of flue products into the combustion air stream.  
4. The vent piping must terminate in an up-turned rain cap as  
shown in Figure 35. When the vent termination uses a rain  
cap as illustrated in Figure 35, maintain at least 36" (914  
mm) above the air inlet. The air inlet pipe and vent pipe  
can be located in any desired position on the roof, but must  
always be no further than 2 feet (0.6 m) apart and with the  
vent termination at least 1 foot above the air intake.  
5. Locate terminations so they are not likely to be damaged by  
foreign objects, such as stones or balls, or subject to buildup  
of leaves or sediment and also not blocked or restricted by  
snow accumulation.  
6. If installing both intake air and vent piping in a Direct Vent  
configuration vertically through the roof; ensure that all  
exterior vertical clearance requirements shown in Figure 35  
are being maintained. These clearances and those cited by  
local and national codes must be maintained.  
Note: On flat roof installations the intake air and the vent  
terminations must be a minimum of 24 inches (60 cm) above any  
parapet, vertical wall or structure within 10 feet (3 m) horizontally.  
FIGURE 37. VERTICAL TERMINATION - FLAT ROOF  
CLEARANCES  
PREPARE ROOF/WALL PENETRATIONS  
1. Air pipe penetration:  
Cut a hole for the air pipe. Size the air pipe hole as close as  
desired to the air pipe outside diameter.  
2. Vent pipe penetration:  
Cut a hole for the vent pipe. For either combustible or  
noncombustible construction, size the vent pipe hole with at least  
a 1/2 inch clearance around the vent pipe outer diameter:  
• 7½ inch (178 mm) hole for 6 inch (152 mm) vent pipe  
• 8½ inch (203 mm) hole for 7 inch (178 mm) vent pipe  
Insert a galvanized metal thimble in the vent pipe hole (when  
required by local codes).  
3. Space the air and vent holes to provide the minimum spacing  
4. Follow all local codes for isolation of vent pipe when passing  
through floors, ceilings, and roofs.  
5. Provide flashing and sealing boots sized for the vent pipe  
and air pipe.  
FIGURE 35. PVC/CPVC AIR/VENT TERMINATION -  
VERTICAL  
35  
     
TABLE 13. PVC, VENT PIPE, AND FITTINGS  
ALL VENT PIPE MATERIALS AND FITTINGS MUST COMPLY WITH THE FOLLOWING:  
ITEM  
MATERIAL  
STANDARDS FOR INSTALLATION IN:  
UNITED STATES  
CANADA  
ANSI/ASTM D1785 CPVC and PVC venting must be ULC-S636 Certified.  
ANSI/ASTM F441  
Vent pipe and fittings  
Pipe cement/primer  
PVC schedule 40  
CPVC schedule 40/80  
PVC  
ANSI/ASTM D2564 ULC-S636 Certified.  
ANSI/ASTM F493  
CPVC  
NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE  
TABLE 14. DIRECT VENT ALLOWABLE AIR/VENT LENGTHS  
MODEL  
AIR INTAKE  
DIAMETER  
(INCH)  
AIR INTAKE  
MIN. LENGTH MAX. LENGTH DIAMETER  
AIR INTAKE  
VENT  
VENT MIN.  
LENGTH  
(FT)  
VENT MAX.  
LENGTH  
(FT)  
(FT)  
12  
(FT)  
100  
100  
100  
100  
100  
100  
(INCH)  
XP 1000  
XP 1300  
XP 1700  
XP 2000  
XP 2600  
XP 3400  
6
6
6
8
12  
12  
12  
12  
12  
12  
100  
100  
100  
100  
100  
100  
12  
8
12  
8
8
12  
8
8
12  
8
10  
12  
10  
When determining equivalent combustion air and vent length, add 5 feet (1.5 m) for each 90° elbow and 3 feet (0.9 m) for each 45°  
elbow.  
EXAMPLE: 20 feet (6 m) of PVC pipe + (4) 90° elbows + (3) 45° elbows = 49 equivalent feet (15 m) of piping.  
TABLE 15. ROOM AIR ALLOWABLE VENT LENGTHS  
MODEL  
VENT DIAMETER  
(INCH)  
VENT MIN. LENGTH  
(FT)  
VENT MAX. LENGTH  
(FT)  
XP 1000  
XP 1300  
XP 1700  
XP 2000  
XP 2600  
XP 3400  
6
8
12  
12  
12  
12  
12  
12  
100  
100  
100  
100  
100  
100  
8
8
8
10  
36  
     
CONDENSATE DISPOSAL  
CONDENSATE NEUTRALIZER  
FIGURE 38. CONDENSATE DISPOSAL SYSTEM  
FIGURE 40. CONDENSATE NEUTRALIZER  
The condensate drains from the boiler have pH levels between  
4.3 and 5.0. The pH measurement of a fluid is an indicator of  
the acidity or alkalinity. Neutral fluids have pH of 7.0. Acid fluids  
have pH below 7. Some local codes may require the use of a  
condensate neutralizer to raise the pH level of the condensate  
leaving the boiler. The condensate neutralizer be must installed  
between the boiler and the drain and must be installed lower  
than the outlet of the condensate trap as shown in Figure 38. The  
Condensate Neutralizer Kit model must be selected with respect  
to the boiler's output as mentioned in the Table 16.  
TABLE 16. CONDENSATE NEUTRALIZER KIT MODELS  
XP MODELS  
AO SMITH CONDENSATE  
NEUTRALIZER KIT NUMBERS  
XP 1000  
XP 1300  
XP 1700  
XP 2000  
XP 2600  
XP 3400  
9007961005  
9007962005  
9007962005  
9007962005  
9007963005  
9007963005  
FIGURE 39. CONDENSATE TRAP  
CONDENSATE TRAP  
Installation of the Condensate Trap must conform with the  
instructions in this manual and local building codes. Condensate  
Neutralizer Kits are available. Contact your distributor or Service  
Agency. Do not remove, modify or alter the factory installed  
condensate trap. Install a commercially available neutralizing kit  
if required by the local codes.  
The boiler is factory fitted with a 24V condensate trap connected  
to the controller. For safety reasons, if the condensate drain is  
blocked, the control system will turn off all the firing burners and  
bring the boiler to a safe shut down. If there is an air blockage  
in the line, vent out the air by removing the cap. Cap acts as an  
air vent for releasing any air block on down stream condensate  
line. Flexible silicon hose connect from the trap through the  
Condensate Neutralizer to the drain.  
Due to the highly efficient operation of this unit, condensate is  
formed during operation and must be removed by the conden-  
sate drain systems. Inspect the condensate drains and tubes at  
least once a month and insure they will allow the free flow of  
condensate at all times. The system must be inspected more  
frequently in cold weather if the drain system is located in an  
area, such as along the floor, where freezing temperatures are  
likely to occur. The condensate drain system must be protected  
against freezing. Contact a qualified service agent to inspect  
and correct the condition if freezing of the condensate lines is  
a problem.  
37  
   
GAS SUPPLY CONNECTIONS  
6. Use pipe sealing compound compatible with propane gases.  
GAS SUPPLY PIPE CONNECTIONS  
Apply sparingly only to male threads of the pipe joints so that  
pipe dope does not block gas flow.  
Failure to apply pipe sealing compound as detailed in this  
manual can result in severe personal injury, death, or substantial  
property damage.  
7. Make sure the maximum inlet gas pressure do not exceed  
the value specified. Minimum value specified is for input  
adjustment only.  
Make sure to use two wrenches when tightening gas piping at the  
boiler, using one wrench to prevent the boiler gas line connection  
from turning. Failure to support the boiler gas connection pipe to  
prevent it from turning could damage gas line components. Do  
not use wrench on valve body as damage would occur.  
GAS PRESSURE REQUIREMENTS  
The maximum allowable gas supply pressure for this boiler is  
14 inches w.c. (3.5 kPa). Install a positive lock-up gas pressure  
regulator in the gas supply line if inlet gas pressure can exceed  
14 inches w.c. (3.5 kPa) at any time.  
If a positive lock-up regulator is required follow these instructions:  
1. Positive lock-up gas pressure regulators must be rated at or  
above the input Btu/hr rating of the boiler they supply.  
2. Positive lock-up gas pressure regulator(s) should be  
installed no closer than 3 feet (1 meter) and no farther than  
8 feet (2.4 meters) from the boiler’s inlet gas connection.  
FIGURE 41. GAS SUPPLY PIPING  
1. Make sure to install ground joint union for servicing.  
3. After installing the positive lock-up gas pressure regulator(s),  
an initial nominal supply pressure setting of 7 inches w.c.  
(1.7 kPa) while the boiler is operating is recommended and  
will generally provide good boiler operation. Some addition  
adjustment maybe required later to maintain a steady gas  
supply pressure.  
In Canada – When using manual main shutoff to support the  
weight of the piping with valves, ensure that it is identified by the  
installer.  
2. Install drip leg (sediment trap) per NFPA 54 for US and CAN  
B149.1 for Canada.  
4. When installing multiple boilers in the same gas supply  
system it is recommended that individual positive lock-up  
gas pressure regulators be installed at each unit.  
3. Support the piping with hangers, not by the boiler or its  
accessories. The gas valve and blower will not support the  
weight of the piping. Failure to comply could result in severe  
personal injury, death, or substantial property damage.  
4. Purge all air from the gas supply piping.  
5. Before setting the boiler in operation, check the boiler and its  
gas connection for leaks.  
• Disconnect the boiler from the gas supply piping system  
during any pressure testing, at a test pressure in excess  
of 1/2 PSIG (3.5 kPa)  
• The boiler must be isolated from the gas supply piping  
system by closing a manual shutoff valve during any  
pressure testing, at test pressures equal to or less than  
1/2 PSIG (3.5 kPa).  
Do not check for gas leaks with an open flame, instead use the  
bubble test. Failure to use the bubble test or check for gas leaks  
can cause severe personal injury, death, or substantial property  
damage.  
38  
PIPE SIZES FOR PROPANE GAS  
Make sure to contact the gas supplier for pipe sizes, tanks, and  
100% lockup gas pressure regulator.  
PURGING GAS LINE  
Gas line purging is required with new piping or systems in which  
air has entered. Gas purging should be performed per NFPA 54  
for US and CAN B149.1 for Canada.  
CHECK GAS SUPPLY INLET PRESSURE  
CSA or UL listed flexible gas connections are acceptable, but  
make sure that the line has adequate capacity to allow your boiler  
to fire at full rate. Consult with local codes for proper installation  
or service procedures.  
Do not adjust or attempt to measure gas valve outlet pressure.  
Attempting to alter or measure the gas valve outlet pressure  
could result in damage to the valve, causing potential severe  
personal injury, death, or substantial property damage.  
Make sure the gas piping are sized for the proper flow and length  
of pipe, to avoid excessive pressure drop. The gas meter and  
the gas regulator must be properly sized for the total gas load.  
Perform the below steps when checking inlet gas supply:  
1. Turn the main power switch to the “OFF” position.  
2. Shut off gas supply.  
3. Remove the 1/8" pipe plug on the main gas shutoff valve  
and install a suitable 1/8" fitting (field supplied) for the  
manometer tubing. Place the tubing of the manometer over  
the tap once the 1/8" fitting is installed.  
4. Slowly turn on the gas supply.  
5. Ensure inlet pressure is within specified range.  
6. If the gas pressure is out of range, contact the gas utility, gas  
supplier, qualified installer or service agency to determine  
the necessary steps to provide proper gas pressure to the  
control.  
CHECK FOR GAS LEAKS  
Before operating the boiler, make sure to check the floor near and  
around the boiler for gas odorant or any unusual odor. Remove  
the top access panel and check for odor in the interior of the  
boiler enclosure. Do not start the boiler if there is any indication  
of a gas leak. Use an approved leak detection solution and repair  
any leaks at once.  
In the case of propane boilers, the supplier mixes an odorant  
with the propane to make its presence detectable. But in some  
instances, the odorant can fade, and the gas may no longer have  
an odor. Before operating the boiler, make sure the propane  
supplier verify the correct odorant level in the gas.  
Do not adjust or attempt to measure gas valve outlet pressure.  
The gas valve is factory set for the correct outlet pressure. This  
setting is suitable for natural gas and propane, requiring no field  
adjustment. Attempting to alter or measure the gas valve outlet  
pressure could result in damage to the valve, causing potential  
severe personal injury, death, or substantial property damage.  
39  
BOILER START UP AND OPERATIONS  
IMPORTANT  
Only an A.O. Smith Certified Start-up agent must perform the  
initial firing of the boiler. At this time the user should not hesitate  
to ask the start-up agent any questions regarding the operation  
and maintenance of the unit. If you still have questions, please  
contact the factory or your local A.O. Smith representative.  
Contact Technical Support noted on the back cover for the name  
of your closest Certified Start-Up agent.  
Lighting and Operating instructions are included with this manual.  
By using these instructions, the user may be able to make minor  
operational adjustments and save unnecessary service calls.  
However the user should not attempt repairs, but should contact  
a service technician or gas supplier.  
GENERAL  
FIGURE 42. GAS TRAIN ASSEMBLY  
Never operate the boiler without first making sure the boiler and  
system are filled with water, in addition:  
MANIFOLD PRESSURE CONNECTIONS  
• Make sure a temperature and pressure relief valve  
is installed in the storage tank for hot water supply  
installations.  
Take the manifold pressure, refer to Table 2, by removing the pipe  
plug and inserting a suitable 1/8” NPT hose barb for connection to  
the manometer/pressure gauge. Upon completion of measurements  
and adjustments, remove the hose barb and replace the pipe  
plug. Check for gas leaks and insure all connections are gas tight,  
• Make sure that the boiler and system have been purged  
of air and checked for leaks.  
Also ensure to check the gas piping for leaks before beginning  
the initial firing of the boiler.  
FILLING AND PURGING OF HEATING BOILER  
INSTALLATION  
1. Fast fill system through bypass until pressure approaches  
desired system pressure. Close bypass valve and permit  
pressure to be established by the pressure reducing valve.  
2. Vent all high points in system to purge system of air.  
Provisions should be made to permit manual venting of radiators  
or convectors.  
FILLING HOT WATER SUPPLY BOILER  
INSTALLATION  
1. Close the system’s drain valve by turning handle clockwise.  
2. Open a nearby hot water faucet to permit the air to escape  
WATER TEMPERATURE REGULATION  
3. Fully open the cold water inlet pipe valve allowing the boiler  
and piping to be filled.  
4. Close the hot water faucet as water starts to flow.  
PURGING GAS LINE  
Gas line purging is required with new piping or systems in which  
air has entered.  
INLET GAS PRESSURE  
The inlet gas pressure is measured by removing the 1/8” NPT Plug  
located on the upstream side of the supply gas valve, and insert  
a 1/8” NPT hose barb fitting to be connected to a manometer or  
pressure gauge. Once pressure has been checked and/or adjusted,  
replace the plug and check for leaks. The maximum value specified  
in Table 2 on Page 6 must not be exceeded. The minimum values,  
shown in Table 2, must be maintained under both load and no load  
conditions (static and firing conditions). The combination gas valves  
supplied with the boiler are for low pressure service. If upstream  
pressure exceeds 14.0” W.C., an intermediate gas pressure  
regulator of the lockup type must be installed.  
40  
 
HOT WATER CAN SCALD: Boilers are intended to produce hot  
water. Water heated to a temperature which will satisfy space  
heating, clothes washing, dish washing and other sanitizing  
needs can scald and permanently injure you upon contact.  
Some people are more likely to be permanently injured by hot  
water than others. These include the elderly, children, the infirm  
or physically/mentally disabled. If anyone using hot water in your  
home fits into one of theses groups or if there is a local code or  
state law requiring a specific temperature water at the hot water  
tap, then you must take special precautions. In addition to using  
the lowest possible temperature setting that satisfies your hot  
water needs, a means such as a mixing valve should be used  
at the hot water taps used by these people or at the hot water  
supply tank. Mixing valves are available at plumbing supply  
or hardware stores. Follow the manufacturer’s instructions for  
installation of the valves. Before changing the thermostat setting  
on the hot water system controller, refer to Table 17.  
TABLE 18.  
WATER HARDNESS MEDIUM (0-12 GRAINS PER GALLON)  
XW MODEL  
NO.  
∆T ºF  
GPM  
∆P FEET  
1000  
1300  
1700  
2000  
2600  
3400  
25  
25  
25  
25  
25  
25  
76  
99  
17.5  
22  
129  
152  
198  
258  
23  
17.5  
22  
23  
∆T ºF = Temperature rise ºF at the specified GPM.  
GPM = Flow rate in gallons per minute.  
∆P = Pressure loss through the heat exchanger in feet of head.  
For systems over 5 grains per gallon; and for scale free  
operation, boiler setpoint should not exceed 140 ºF.  
Hot water temperatures required for automatic dishwasher  
and laundry use can cause scald burns resulting in serious  
personal injury and/or death. The temperature at which injury  
occurs varies with the person’s age and time of exposure. The  
slower response time of children, aged or disabled persons  
increases the hazards to them. Never allow small children to  
use a hot water tap, or to draw their own bath water. Never  
leave a child or disabled person unattended in a bathtub  
or shower.  
Note: The factory installed/supplied pump on the above listed  
model boilers is sized to maintian a 25 ºF ∆T through the boiler  
when the boiler is firing at 100% fire.  
In addtion to the pressure loss through the heat exchanger,  
the factory supplied pump is sized for an additional 50 feet of  
equivalent feet of piping between the boiler and a storage tank.  
All piping between the boiler and the storage tank must be of  
a pipe size equal to the inlet/outlets of the boiler. Installation  
differences may slightly change these parameters.  
The boiler should be located in an area that is inaccessible to the  
general public.  
TABLE 17. RISK OF SCALDS  
FREEZE PROTECTION (HYDRONIC HEATING  
INSTALLATION)  
Time to Produce 2nd & 3rd  
Water Temperature  
Degree Burns on Adult Skin  
1. Determine freeze protection fluid quantity using system  
180°F (82°C)  
170°F (77°C)  
160°F (71°C)  
150°F (66°C)  
140°F (60°C)  
130°F (54°C)  
120°F (49°C)  
Nearly instantaneous  
Nearly instantaneous  
About 1/2 second  
water content, following fluid manufacturer’s instructions.  
2. Local codes may require a backflow preventer or actual  
disconnect from city water supply.  
About 1-1/2 seconds  
Less than 5 seconds  
About 30 seconds  
3. When using freeze protection fluid with automatic fill, install  
a water meter to monitor water makeup. Freeze protection  
fluid may leak before the water begins to leak, causing  
concentration to drop, reducing the freeze protection level.  
More than 5 minutes  
Should overheating occur or the gas supply fail to shut off, turn  
off the main manual gas shutoff valve to the boiler.  
INSPECT/FILL CONDENSATE SYSTEM  
Inspect/check condensate lines and fittings:  
CHECK/CONTROL WATER HARDNESS  
1. Inspect the condensate drain line, condensate PVC fittings  
and condensate trap.  
XW Model XP Boilers are approved for use in Domestic Water  
Heating Systems with a water supply hardness of 0 grains per  
gallon to a maximim of 12 grains per gallon. Refer to Table 18 for  
recommend flow rate to maintain scale free operation with up to  
a medium water hardness. For scale free operation in hard water  
systems with a water hardness greater than 12 grains per gallon,  
a water softener must be installed and maintained.  
Fill condensate trap with water:  
1. Remove the 2 inch PVC cap with the switch located at the  
top of the trap.  
2. Fill with fresh water until the water begins to pour out of the  
drain.  
3. Replace the cap. Press the cap onto the trap until the cap  
makes contact with the drain.  
The condensate trap must be filled with water during all times of  
boiler operation to avoid flue gas emission from the condensate  
drain line. Failure to fill the trap could result in severe personal  
injury or death.  
41  
   
LIGHTING AND OPERATING INSTRUCTIONS  
42  
ADJUSTMENT  
There must be sufficient load to operate the boiler at high fire to  
perform the following adjustments. Start the boiler and observe  
proper operating parameters for the system.  
FIGURE 44. BURNER INFORMATION SCREEN  
Required Tools:  
Click on Operation button, and under the Modulation Menu, set  
the required Firing rate (High/Low) by setting the RPM.  
• TORX® T40 or 5 mm hex wrench  
• 3 mm or 7/64 inch hex wrench  
• Combustion analyzer  
These boilers are equipped with a combined gas/air control  
and gas safety shut off control valves. The valve functions in  
parallel with the variable speed combustion blower to supply  
the correct gas air ratio for optimum performance and efficiency.  
The combustion blower speed is controlled automatically and  
determines the amount of negative pressure experienced by the  
gas safety shut off/control valves. The gas/air regulator adjusts  
gas flow to maintain the proper pressure at the outlet nozzle of  
the associated valve.  
SETTING OF THE TEST MODE  
On the Burner Home screen, select any individual boiler which  
will guide to Burner Information screen.  
FIGURE 45. OPERATION SCREEN  
On the Firing Rate page, set the Firing rate RPM by selecting the  
Manual in Run check box.  
FIGURE 43. BURNER HOME SCREEN  
FIGURE 46. FIRING RATE PAGE  
43  
HIGH FIRING RATE SETTING  
Set the boiler to the high firing rate by setting the High Firing Rate RPM as described below. Check combustion readings using a  
combustion analyzer. If combustion readings are not in accordance with the chart below adjust the gas valve as follows: remove the  
flat, round, blue plastic cap from the cover. Using a 3 mm (7/64”) hex wrench, turn the adjustment screw counterclockwise to increase  
or clockwise to decrease gas flow and achieve the desired CO2 level. Refer to the Table 19 for correct settings. There will be a slight  
time delay between the adjustment and the response of the CO2 measuring instrument. Adjust the settings in small increments and  
allow the combustion readings to stabilize before readjusting. When desired adjustments are complete, reinstall the blue plastic cap  
on the cover. Combustion samples should be taken in the stack within two feet of the boiler. The carbon monoxide (CO) values in  
the combustion sample should not exceed 150 PPM under any circumstances. Contact OEM for any abnormal conditions leading to  
excessive CO above 150 PPM.  
TABLE 19. HIGH FIRE RATE  
RPM  
CO2  
*MANIFOLD PRESSURE  
INCHES W.C  
(APPROXIMATE FACTORY SET)  
MODELS (XB/XW)  
NATURAL  
GAS  
PROPANE  
NATURAL  
GAS  
PROPANE  
NATURAL GAS  
PROPANE  
1000 (920,000)  
1300  
4450  
4850  
5700  
4700  
5700  
5700  
4750  
5100  
5700  
4750  
5100  
5700  
8.5 - 9.2%  
8.5 - 9.2%  
8.5 - 9.2%  
8.5 - 9.2%  
8.5 - 9.2%  
8.5 - 9.2%  
9.3 - 10.2%  
9.3 - 10.2%  
9.3 - 10.2%  
9.3 - 10.2%  
9.3 - 10.2%  
9.3 - 10.2%  
-3.5  
-3.0  
-3.6  
-3.9  
-3.3  
-3.5  
-4.7  
-3.6  
-4.4  
-4.9  
-3.6  
-4.4  
1700  
2000  
2600  
3400  
LOW FIRING RATE SETTING  
Set the boiler to the low firing rate by setting the Low Firing Rate RPM as described below. Check combustion readings using a  
combustion analyzer. If combustion readings are not in accordance with the chart shown below adjust as follows: remove the cap  
on the gas regulator using a slotted screwdriver. This will expose the offset adjustment screw. Using a TORX® T40 or a 5 mm hex  
wrench, carefully adjust the low fire gas setting to achieve the CO2 level prescribed in Table 20.  
Note: The rotation of the Low Fire adjustment is opposite of the High Fire as follows: Clockwise rotation increases gas flow,  
counterclockwise rotation decreases gas flow.  
Adjustments to the offset pressure regulators should not exceed 1/4 turn at a time before allowing the readings to respond and  
stabilize.  
After proper low fire offset adjustment is made, reinstall the slotted cap on the regulator.  
Following all gas valve adjustments, check for proper light-off and verify correct fuel/air mix and combustion quality throughout the  
entire firing range (from lowest to highest fan speed).  
Note: Make sure the Manual Mode is set back to Automatic Mode to each of the burners, once the required settings are  
done. Turn off the individual burner before proceeding to the next burner settings.  
TABLE 20. LOW FIRE RATE  
RPM  
CO2  
*MANIFOLD PRESSURE  
INCHES W.C  
(APPROXIMATE FACTORY SET)  
MODELS (XB/XW)  
NATURAL  
GAS  
PROPANE  
NATURAL  
GAS  
PROPANE  
NATURAL GAS  
PROPANE  
1000 (920,000)  
1300  
1650  
1650  
1700  
1550  
1700  
1700  
1540  
1600  
1700  
1540  
1600  
1700  
7.3 - 8.2%  
7.3 - 8.2%  
7.3 - 8.2%  
7.3 - 8.2%  
7.3 - 8.2%  
7.3 - 8.2%  
8.4 - 8.8%  
8.4 - 8.8%  
8.4 - 8.8%  
8.4 - 8.8%  
8.4 - 8.8%  
8.4 - 8.8%  
-0.3  
-0.2  
-0.2  
-0.3  
-0.2  
-0.2  
-0.25  
-0.14  
-0.23  
-0.31  
-0.14  
-0.23  
1700  
2000  
2600  
3400  
* NOTE: Values listed in Table 19 and Table 20 are tested under laboratory conditions with minimum vent length. Values may slightly vary depending on  
ambient conditions and field equipment accuracy.  
44  
CONTROL SYSTEM  
3. Three Pump Outputs with 5 selectable operation modes.  
BURNER CONTROL SYSTEM  
4. 24VAC:  
• Output control of gas valve (Pilot and Main) and External  
Ignition Transformer.  
• Digital inputs for room limit control, high limit control, Gas  
pressure switch, low water cutoff.  
5. External spark transformer.  
6. Flame Sensor.  
7. Test jacks for flame signal measurement from either a flame  
rod or UV flame sensor.  
8. Alarm Output.  
FIGURE 47. R7910A1138 CONTROL SYSTEM  
The R7910A1138 is a burner control system that provide  
heat control, flame supervision, circulation pump control,  
fan control, boiler control sequencing, and electric ignition  
function. It will also provide boiler status and error reporting.  
Multiple boilers can be joined together to heat a system instead  
of a single, larger burner or boiler. Using boilers in parallel is  
more efficient, costs less, reduces emissions, improves load  
control, and is more flexible than the traditional large boiler.  
Control System consists of:  
FIGURE 48. GENERAL R7910A1138 BOILER SCHEMATIC  
• R7910A1138 Control Device.  
The above figure shows two loops of heat control: Central  
Heating (CH), and an optional second loop for Domestic Hot  
Water (DHW) can be configured on each R7910A. The DHW  
loop transfers heat from the boiler outlet to hot water appliances  
in conjunction with the primary system heat loop. Priority  
assignment to each heat loop can be configured to specify which  
loop gets serviced first.  
• S7999B Touchscreen Display—required for setup and  
ModBus communication but not required for the system  
to operate once the R7910A1138 is programmed.  
• S7910A Local Keyboard Display Module.  
• Flame Rod .  
Temperature Sensor, NTC Type 10KΩ at 77°F (25°C) or  
12KΩ at 77°F (25°C).  
• Limit Sensor, NTC Type 10KΩ at 77°F (25°C).  
• 24V Digital I/O.  
OVERVIEW  
Functions provided by the R7910A1138 include automatic boiler  
sequencing, flame supervision, system status indication, firing  
rate control, load control, CH/DHW control, limit control, system  
or self-diagnostics and troubleshooting.  
The R7910 maximum version of the controller offers:  
1. NTC-temperature sensor for:  
• Outlet Limit And Temperature.  
• Stack Temperature Limit and Temperature.  
• Inlet Temperature.  
• Outdoor Temperature (R7910 only).  
2. Modulating output PWM-driven rotation speed controlled  
DC-fan for optimal modulation control.  
45  
CSD-1 Acceptable.  
COMMUNICATIONS AND DISPLAYS  
Meets CSD-1 section CF-300 requirements as a Primary Safety  
Control.  
Two modes of communications are available to the R7910.  
Meets CSD-1 section CW-400 requirements as a Temperature  
Operation control.  
Meets CSD-1 section CW-400 requirements as a Temperature  
High Limit Control when configured for use with 10 kohm NTC  
sensors.  
Federal Communications Commission, Part 15,  
Class B. Emissions.  
1. The R7910 has two RS485 communication ports for  
ModBus that allows for interfacing to one or all R7910s of  
a system and presents them individually to the user. The  
S7999B System Operator interface is a color touchscreen  
displays used for configuration and monitoring of the  
R7910A. Control Operation and display status in both test  
and graphical modes can be shown along with the ability to  
setup. The R7910 can also be remotely reset through the  
S7999B display.  
BURNER CONTROL OPERATION  
2. Either ModBus RS485 communication port can be used to  
allow configuration and status data to be read and written  
to the R7910. Support a Master S7999B or a Building  
Automation master to control the R7910 to respond to  
a single ModBus address to service the requests of the  
ModBus master in a Lead/Lag arrangement.  
SAFETY SHUTDOWN OF BURNER CONTROL FUNCTIONS  
Safety Shutdown (Lockout) occurs if any of the following occur  
during the indicated period:  
1. INITIATE PERIOD:  
a. A/C line power errors occurred.  
The local S7910 Keyboard display, the S7999B System Operator  
interface, and the S7999C Local Operator Interface are optional  
components.  
b. Four minute INITIATE period has been exceeded.  
2. STANDBY PERIOD:  
a. Flame signal is present after 240 seconds.  
b. Preignition Interlock is open an accumulative time of 30  
seconds.  
c. Interlock Start check feature is enabled and the Interlock  
String (including Airflow Switch) is closed for 120 seconds with  
the controller closed. (jumpered or welded Interlock).  
d. Main Valve Terminal is energized.  
The S7999B (or the DSP3944 which is a portable S7999B) or is  
required configuration of the parameters of the R7910 but is not  
needed for the operation of the system once configured.  
SPECIFICATIONS  
1. Electrical Ratings:  
Operating voltage  
• 24VAC (20 to 30 VAC, 60 Hz ±5%)  
e. Internal system fault occurred.  
3. PREPURGE PERIOD:  
• 30 amps (Single Heat Exchanger)  
a. Preignition Interlock opens anytime during PREPURGE  
period.  
b. Flame signal is detected for 10 seconds accumulated time  
during PREPURGE.  
• 60 amps (Double Heat Exchanger)  
Connected Load for Valve and annunciator functions:  
• 24VAC, 60Hz  
c. Purge Rate Fan RPM or High Fire Switch fails to close within  
four minutes and fifteen seconds after the firing rate motor  
is commanded to drive to the high fire position at the start of  
PREPURGE.  
d. Light off Rate Fan RPM or Low Fire Switch fails to close  
within four minutes and fifteen seconds after the firing rate motor  
is commanded to drive to the low fire position at the end of  
PREPURGE.  
• 120VAC (+10%/-15%), 60Hz (±5%)  
• Model Specific  
2. Corrosion:  
• R7910A must not be used in a corrosive environment.  
3. Operating Temperature: -4°F to 150°F (-20°C to 66°C)  
4. Storage/Shipping Temperature: -40°F to 150°F (-40°C to  
66°C).  
e. Lockout Interlock (if programmed) does not close within 10  
seconds.  
5. Humidity:  
f. Lockout Interlock opens during PREPURGE.  
g. Pilot Valve terminal is energized.  
• Up to 95% Relative Humidity, noncondensing at 104°F for  
14 days. Condensing moisture may cause safety shutdown.  
h. Main Valve terminal is energized.  
i. Internal system fault occurred.  
6. Vibration: 0.0 to 0.5g Continuous (V2 level)  
7. Enclosure: Nema 1/IP40.  
8. Approvals:  
4. PRE-IGNITION TIME  
a. Lockout Interlock opens.  
b. IAS Purge and Ignition enabled and the Interlock opens.  
c. Preignition Interlock opens.  
d. Pilot Valve terminal is energized.  
e. Main Valve terminal is energized.  
Underwriters Laboratories, Inc. (UL): Component Recognized:  
File No. MP268 (MCCZ)  
• R7910 is certified as UL372 Primary Safety Controls.  
• The R7910 is certified as UL353 Limit Rated device when  
using part number 50001464 dual element limit rated NTC  
sensors.  
5. PILOT FLAME ESTABLISHING PERIOD (PFEP):  
a. Lockout Interlock opens (if enabled).  
b. Pilot Valve terminal is not energized.  
c. No flame is present at the end of the PFEP, or after programmed  
number of retry attempts.  
d. Main valve terminal is energized.  
e. Internal system fault occurred.  
46  
6. MAIN FLAME ESTABLISHING PERIOD (MFEP):  
GENERAL OPERATIONAL SEQUENCE  
a. Lockout Interlock opens (if enabled).  
b. Pilot valve terminal is not energized.  
c. Main valve terminal is not energized.  
d. No flame present at the end of MFEP.  
e. Internal system fault occurred.  
INITIATE  
The R7910 enters the Initiate sequence on Initial Power up or:  
• Voltage fluctuations vary less than 20VAC or greater than  
30VAC.  
7. RUN PERIOD:  
• Frequency fluctuations vary +/-5% (57 to 63 Hz).  
• If Demand, LCI, or Stat interrupt (open) during the Prepurge  
Period.  
a. No flame is present, or flame is lost (if enabled-lockout).  
b. Lockout Interlock opens) if enabled).  
c. IAS Purge and Ignition enabled and the Interlock opens.  
d. Pilot terminal energized (if programmed as Interrupted Pilot).  
e. Main valve terminal is not energized.  
• After the reset button is pressed or fault is cleared at the  
displays.  
The Initiate sequence also delays the burner motor from being  
energized and de-energized from an intermittent AC line input or  
control input.  
f. Internal system fault occurred.  
8. POSTPURGE PERIOD:  
If an AC problem exists for more than 240 seconds a lockout will  
occur.  
a. Preignition Interlock does not close in five seconds.  
b. Pilot Valve terminal is energized.  
c. Main Valve terminal is energized.  
d. Internal system fault occurred.  
e. Flame sensed 240 seconds accumulated time after the RUN  
period.  
HYDRONIC/CENTRAL HEATING  
Start-up sequence central heating request (system in standby):  
1. Heat request detected (On Setpoint - On Hysteresis).  
2. The CH pump is switched on.  
3. After a system Safe Start Check, the Blower (fan) is switched  
on after a dynamic ILK switch test (if enabled).  
4. After the ILK switch is closed and the purge rate proving fan  
RPM is achieved (or High Fire Switch is closed) - prepurge  
time is started.  
SAFETY SHUTDOWN:  
1. If the lockout interlocks open or a sensor designated as a  
safety limit are read as defective, Control System will lockout  
and the blower motor will be de-energized.  
If these open during the firing period, all fuel valves will be de- 5. When the purge time is complete, the purge fan RPM is  
energized, the system will complete postpurge, and will lockout  
indicated by an alarm.  
changed to the Lightoff Rate or if used, the damper motor is  
driven to the Low Fire Position.  
2. If the pilot flame is not detected by the end of the last (3 6. As soon as the fan-rpm is equal to the light-off rpm (or the  
number recycle attempt), pilot trial for ignition period, the  
pilot valve, and ignition transformer will be de-energized, the  
Low Fire Switch closes), the Trial for Ignition or Pre-Ignition  
Time is started.  
system will complete post purge and will lockout indicated 7. Pre-Ignition Time will energize the ignitor and check for  
by an alarm. flame.  
3. If the main flame is not detected at the end of the last recycle 8. Trial for Ignition. Specifics for timings and device actions are  
attempt of the main flame establishing period, all fuel valves defined by the OEM or installer.  
will be de-energized, the device will complete postpurge, 9. The ignition and the gas valve are switched on.  
and will lockout indicated by an alarm.  
10. The ignition is turned off at the end of the direct burner  
ignition period, or for a system that does use a pilot, at  
the end (or optionally at the middle) of the Pilot Flame  
Establishing Period (PFEP). For an interrupted pilot system  
this is followed by a Main Flame Establishing Period (MFEP)  
where the pilot ignites the main burner. For an intermittent  
pilot there is no MFEP.  
4. If the flame sensing signal is lost during the run period (if  
lockout is selected), all fuel valves will be de-energized within  
4 seconds after the loss of the flame signal, the device will  
complete postpurge, and will lockout indicate by an alarm.  
5. Manual reset is required following any safety shutdown.  
Manual reset may be accomplished by pressing the push  
button on the device, pressing the remote reset wired into 11. The fan is kept at the lightoff rate during the stabilization  
connector J10, or through an attached display.  
timer, if any.  
12. Before the release to modulation, the fan is switched to  
minimum RPM for the CH Forced Rate and Slow Start  
Enable, if the water is colder than the threshold.  
13. At the end of the CH-heat request the burner is switched off  
and the fan stays on until post purge is complete.  
14. A new CH-request is blocked for the forced off time set by  
the Anti Short Cycle (if enabled).  
Interrupting power to Control System will cause electrical resets,  
but does not reset a lockout condition.  
15. The pump stays on during the pump overrun time (if  
enabled).  
16. At the end of the pump overrun time the pump will be  
switched off.  
47  
DOMESTIC HOT WATER  
LEAD LAG (LL) MASTER GENERAL OPERATION  
Start-up sequence DHW-request (system in standby):  
The XP Boiler is a multiple burner application and it works on  
the basis of the Lead Lag Operation. The XB Boiler is factory  
configured for Hydronic/Central Heating application, whereas the  
XWBoilerisfactoryconfiguredforDomesticHotWaterapplication.  
The LL master coordinates the firing of its slave Control Systems.  
To do this it adds and drops stages to meet changes in load, and  
it sends firing rate commands to those that are firing.  
1. Heat request detected (either DHW Sensor Only, DHW  
Sensor and Remote Command or DHW Switch and Inlet  
Sensor, whichever applies).  
2. The pump is switched on (after the DHW Pump Start Delay).  
3. After a system Safe Start Check, the Blower (fan) is switched  
on after a dynamic ILK switch test (if enabled).  
4. After the ILK switch is closed and the purge rate proving fan  
RPM is achieved (or High Fire Switch is closed) - prepurge  
time is started.  
The LL master turns the first stage on and eventually turns the  
last stage off using the same criteria as for any modulation  
control loop:  
5. When the purge time is complete, the purge fan RPM is  
changed to the Lightoff Rate or if used, the damper motor is  
driven to the Low Fire Position.  
6. As soon as the fan-rpm is equal to the light-off rpm (or the  
Low Fire Switch closes), the Trial for Ignition or Pre-Ignition  
Time is started (depending on configuration).  
7. Pre-Ignition Time will energize the ignitor and check for  
flame.  
8. Trial for Ignition. Specifics for timings and device actions are  
defined by the OEM or installer.  
When the operating point reaches the Setpoint minus the  
On hysteresis, then the first Control System is turned on.  
When the operating point reaches the Setpoint plus the Off  
hysteresis then the last slave Control System (or all slave  
Control Systems) are turned off.  
The LL master PID operates using a percent rate: 0% is a  
request for no heat at all, and 100% means firing at the maximum  
modulation rate.  
This firing rate is sent to the slaves as a percentage, but this is  
apportioned to the slave Control Systems according to the rate  
allocation algorithm selected by the Rate allocation method  
parameter.  
9. The ignition and the gas valve are switched on.  
10. The ignition is turned off at the end of the direct burner  
ignition period, or for a system that does use a pilot, at  
the end (or optionally at the middle) of the Pilot Flame For some algorithms, this rate might be common to all slave  
Establishing Period (PFEP). For an interrupted pilot system Control Systems that are firing. For others it might represent the  
this is followed by a Main Flame Establishing Period (MFEP) total system capacity and be allocated proportionally.  
where the pilot ignites the main burner. For an intermittent  
pilot there is no MFEP.  
11. The fan is kept at the lightoff rate during the stabilization  
For example, if there are 4 slaves and the LL master's percent  
rate is 30%, then it might satisfy this by firing all four slaves at  
30%, or by operating the first slave at 80% (20% of the system’s  
capacity) and a second slave at 40% (10% of the system’s  
timer, if any.  
12. Before the release to modulation, the fan is switched to  
capacity).  
minimum RPM for the DHW Forced Rate and Slow Start  
The LL master may be aware of slave Control System’s minimum  
Enable, if the water is colder than the threshold.  
firing rate and use this information for some of its algorithms,  
13. At the end of the DHW-heat request the burner is switched  
but when apportioning rate it may also assign rates that are less  
off and the fan stays on until post purge is complete.  
than this. In fact, the add-stage and drop-stage algorithms may  
14. A new DHW-request is blocked for the forced off time set by  
assume this and be defined in terms of theoretical rates that are  
the Anti Short Cycle (if enabled).  
possibly lower than the actual minimum rate of the Burner Control  
System. A Control System that is firing and is being commanded  
to fire at less than its minimum modulation rate will operate at  
its minimum rate: this is a standard behavior for a Buner control  
15. The pump stays on during the pump overrun time (if  
enabled).  
16. At the end of the pump overrun time the pump will be  
switched off.  
system in stand-alone (non-slave) mode.  
If any slave under LL Master control is in a Run-Limited condition,  
then for some algorithms the LL master can apportion to that  
LEAD LAG  
stage the rate that it is actually firing at. Additionally when a  
slave imposes its own Run-limited rate, this may trigger the LL  
Master to add a stage, if it needs more capacity, or drop a stage  
if the run-limiting is providing too much heat (for example if a  
stage is running at a higher-than commanded rate due to anti-  
condensation).  
Burner Control System devices contain the ability to be a stand-  
alone control, operate as a Lead Lag Master control (which also  
uses the burner control function as one of the slaves), or to  
operate solely as a slave to the lead lag system.  
Control System devices utilize two ModBus™ ports (MB1  
and MB2) for communications. One port is designated to  
support a system S7999B display and the other port supports  
communications from the LL Master with its slaves.  
By adjusting the parameters in an extreme way it is possible  
to define add-stage and drop-stage conditions that overlap or  
even cross over each other. Certainly it is incorrect to do this,  
and it would take a very deliberate and non-accidental act to  
accomplish it. But there are two points in this:  
The Lead Lag master is a software service that is hosted by a  
Control System. It is not a part of that control, but is an entity  
that is “above” all of the individual burner controls (including the  
one that hosts it). The Lead Lag master sees the controls as a  
set of Modbus devices, each having certain registers, and in this  
regard it is entirely a communications bus device, talking to the  
slave buner controls via Modbus.  
1. LL master does not prevent it, and more important;  
2. It will not confuse the LL master because it is implemented  
as a state machine that is in only one state at a time;  
The LL master uses a few of the host Buner Control's sensors  
(header temperature and outdoor temperature) and also the  
STAT electrical inputs in a configurable way, to provide control  
information.  
48  
For example:  
LOCAL OPERATOR INTERFACE: DISPLAY SYSTEM  
— If its add-stage action has been triggered, it will remain in this  
condition until either a stage has been added,  
Or  
— The criteria for its being in an add-stage condition is no longer  
met; only then will it take another look around to see what state  
it should go to next.  
DEFINITIONS  
Modulating stage: The modulating stage is the Control System  
that is receiving varying firing rate requests to track the load.  
First stage: This is the Control System that was turned on first,  
when no slave Control Systems were firing.  
Previous stage: The Control System that was added to those  
stages that are firing Just prior to the adding of the Control  
System that is under discussion.  
Next stage: The Control System that will or might be added as  
the next Control System to fire.  
Last stage: The Control System that is firing and that was added  
the most recently to the group of slaves that are firing. Typically  
this is also the modulating stage, however as the load decreases  
then the last-added stage will be at its minimum rate and the  
previous stage will be modulating.  
FIGURE 49. BURNER CONTROL S7999B DISPLAY SYSTEM  
The S7999B is a microprocessor-based touchscreen Operator  
Interface (OI) display that provide an operator interface for  
monitoring and configuring parameters in the Burner Control  
system.  
Lead boiler: The Lead boiler is the Control System that is the  
first stage to fire among those stages which are in the equalize  
runtime (Lead/Lag) group. If a boiler is in the “Use first” group it  
may fire before the Lead boiler fires.  
The S7999B can be used to monitor an individual boiler but  
is primarily used for multiple boiler applications in a lead/lag  
arrangement. COM 2 port is available for Building Automation  
applications. The S7999B display is flush mounted into a panel  
cutout (8-1/8 in. W x 5-7/8 in. H). Wiring connections to the  
S7999B are through a removable 9-pin wiring header.  
First boiler: A Control System may be assigned to any of three  
groups: “Use First”, “Equalize Runtime”, or “Use Last”. If one or  
more Control Systems are in the “Use First” category, then one  
of these (the one with the lowest sequence number) will always  
be the first boiler to fire. If there is no Control System in the “Use  
First” category and one or more are in the “Equalize Runtime”  
category, then the First boiler is also the Lead boiler.  
FEATURES  
Individual boiler status, configuration, history, and  
diagnostics.  
Allows configuration and monitoring of the Burner Control  
Controls burner control sequence, flame signal, diagnostics,  
historical files, and faults.  
S7999B OI Display only:  
• Allows switching view between multiple boilers  
• Allows viewing Lead-Lag Master  
• Ethernet port for downloading software upgrades (when  
required)  
• Real-time data trending analysis and transferring saved  
trend data to Excel spreadsheet.  
• Audible Alarm  
• COM 2 Modbus port for Building Automation System  
applications.  
• LED indicators:  
• Power  
• Network  
• COM 2  
• COM 1  
Model used:  
• S7999B1067 has Black Border  
49  
Allows for lead/lag commissioning.  
Locates attached boiler(s).  
Allows boiler naming.  
10. Drill 1/4 in. holes through the panel at the marked locations  
and secure the power supply with the two #6-32 screws  
and nuts provided.  
11. Remove the 9-pin connector plug from the back of the OI  
Color 3.5 in. x 4.625 in. (5.7 in. diagonal) user interface  
display.  
Display.  
12. Wire the connector to the power supply and the RS-485  
Graphic user interface.  
Touch screen.  
cables.  
13. Ensure the 9-pin connector plug is aligned with the header  
pins when inserting the 9-pin connector plug back onto the  
Display. Secure firmly.  
Communication between the OI Displays and the Burner  
Control Systems uses Modbus™.  
Flush mounting.  
Touch screen disable for screen cleaning.  
12 VDC power supply (included).  
Screen saver.  
Contrast control.  
Volume control.  
SPECIFICATIONS  
1. Electrical Ratings:  
+12 VDC input, maximum of 500 mA current drain.  
Included Power Supply for S7999B:  
• Inputs: 85 to 264 VAC, 47 to 63 Hz; 120 to 370 VDC.  
• Output: 12 VDC; 0 to 2.1 A.  
• Power: 25 W.  
FIGURE 50. S7999B OI DISPLAY CONNECTOR TERMINALS  
2. Operating Temperature: 32°F to 122°F (0°C to 50°C)  
3. Storage/Shipping Temperature: -40°F to 158°F (-40°C to  
70°C).  
QUICK SETUP (S7999B OI DISPLAY)  
4. Humidity: 85% maximum relative humidity.  
5. Approvals:  
1. Make sure the S7999B 9-pin connector is properly aligned  
and pressed firmly in place.  
FCC Part 15, Class A Digital Device  
2. Make sure the wires between the 9-pin connector and the  
Underwriter’s Laboratories, Inc. (UL) Component Recognized  
(for non-continuous operation): File Number MH20613 (MCCZ)  
controller are properly wired and secure.  
WARNING: Electrical Shock Hazard. Can cause severe injury,  
death or equipment damage. Line voltage is present at the 120  
VAC power supply.  
Canada: ICES-003  
INSTALLATION INSTRUCTIONS (S7999B OI DISPLAY)  
MOUNTING THE S7999B OI DISPLAY AND POWER SUPPLY  
3. Make sure the power supply is connected securely to the  
120 VAC power source.  
The OI Display can be mounted on the door panel of an  
electrical enclosure.  
1. Select the location on the door panel to mount the display;  
note that the device will extend into the enclosure at least  
one inch past the mounting surface.  
2. Provide an opening in the panel door 8-1/8 in. wide by  
5-7/8 in. high.  
3. Place the OI Display in the opening and use it as a  
template to mark the location of the four mounting screw  
holes. Remove the device.  
4. Using pilot holes as guides, drill 1/4 in. holes through the  
door panel.  
5. Place the display in the opening, aligning the mounting  
holes in the device with the drilled holes in the panel.  
6. Secure the display to the panel with four #6-32 screws and  
nuts provided.  
7. Select a location inside the enclosure for mounting the  
power supply.  
8. Using the power supply as a template, mark the locations  
of the two mounting holes in the enclosure.  
9. Remove the power supply.  
50  
On System applications, each Burner Control System is  
represented on the Home page by an icon and name. Pressing  
the icon allows the user to zoom in on that boiler and see its  
specific details. These details are provided on a new page, which  
can include additional buttons that display additional detail and  
operation information, which itself leads to other pages. The  
pages are traversed in a tree structure method, as shown in  
STARTING UP THE S7999B OI DISPLAY  
POWER-UP VALIDATION  
The Home page will appear and the “Power” LED will be blinking  
when the device is properly powered. Select the Setup button to  
adjust the contrast and sound as desired.  
If the screen is dim, check the pin 1 and 2 wiring connections.  
Note: An Advanced Startup screen displays for five seconds after  
power-up before the Home page displays. This screen allows the  
user to upgrade the software in the System Display and should  
normally be bypassed.  
The Control System icons will appear in one of four colors  
indicating the boiler status.  
• Blue: Normal operation  
• Red: Lockout condition  
Three LEDs exist for I/O traffic: one for the Ethernet network port  
and two for Modbus™ ports. Modbus Com Port 2 is not active  
on this device.  
• Gray: Standby mode (burner switch off)  
• Gray and crossed out: communication error  
(disconnected or powered off)  
1. Make sure the Power and COM1 LEDs are blinking.  
2. If the LEDs are not blinking:  
Yellow: Preparing for Start-up.  
• Make sure the proper connections have been made  
between the Modbus COM1 Port and the first controller  
device in the Modbus network.  
Up to 8 Systems can be displayed on the Home page. The name  
of each boiler is displayed next to the Control System icon button.  
When Lead Lag is enabled, the system header temperature and  
firing rate are displayed for each System. When the burner is in  
standby or not firing the firing rate is not displayed.  
• Ensure proper wiring of the OI Display 9-pin Header  
Connections.  
3. If connected to a BAS application, COM2 LED will blink Note: The boiler name may be cut off on the Home page when  
indicating BAS traffic.  
all icons are present.  
HOME PAGE (S7999B OI DISPLAY)  
The Home page also includes a System Analysis button that  
allows the user to view status information on a system-wide  
(that is, multiple boiler) basis. The user can choose which status  
information to compare from the Burner Controls in the system.  
Make sure a screen similar to Figure 51 appears after the OI  
Display has completely powered up.  
Pressing the Setup button on the Home page displays  
miscellaneous setup and diagnostic functions. It also contains  
the setup configuration for BAS applications, under theAdvanced  
Setup button. Pressing the Control System icon opens that  
control’s status page.  
PAGE NAVIGATION  
The Burner Control System OI Displays present information  
and options in a paged manner. Pages are displayed in a tree  
structure in which the user navigates up and down to arrive at  
the desired Function (see Figure 53). The page descriptions  
are provided below so that you can understand the purpose of  
each and view the selections, parameters, and information that  
is available or required on each.  
FIGURE 51. S7999B HOME PAGE  
(BOILER 1 IN NORMAL OPERATION)  
COMMON OI DISPLAY PAGE SYMBOLS  
Most pages have a Home button in the top-left corner of the  
screen and a Back button in the top-right corner of the screen.  
The Home button returns the user to the Home page and  
terminates any operation in progress. The Back button returns  
the user to the previous page.  
Two other icons may be noticed near the boiler name.  
A bell will be displayed if the system is in Lockout that reset will  
be required.  
A padlock will be shown on screens that require a password  
to change the parameter. An unlocked padlock indicates the  
password has been entered to change the parameter.  
FIGURE 52. S7999B LEAD LAG HOME PAGE  
51  
 
FIGURE 53. S7999B DISPLAY PAGE FLOW  
52  
 
STATUS OR HOME PAGE  
CONFIGURE BUTTON  
A status (summary) page (Figure 54) is displayed when the Pressing the Configure button (bottom left) on the Status page  
S7999B display is connected. This status page appears on the opens the Configuration page.  
S7999B when the Burner control icon is pressed on the “Home” The S7999B Configuration page does not have a “Display Setup”  
page. The status page displays the current condition of the burner button.  
control and displays some of the more important configuration  
settings.  
Theconfigurationpageallowstheusertoviewandsetparameters  
that define how the connected R7910A functions in the hydronic  
The boiler name associated with the burner control is displayed heating system. All parameters are factory configured and only  
in the title on the status page.  
a Field Service Agent must perform the configuration settings.  
Note: When the burner control has no boiler name defined, The configuration page contains a menu of parameters grouped  
Modbus address is used to identify the boiler.  
into functional areas that the user selects for configuration (see  
The initial status page displayed contains summary status  
information as shown in Figure 54. Any status information not No specific order for configuration is required. All parameters  
applicable for the installation is grayed/blanked out on the screen. are enabled for editing, though some may not be applicable  
(e.g., a configuration parameter may disable a control feature).  
Selecting a parameter group from the menu displays parameters  
exclusively applicable for the functional group on the page (see  
Figure 56). These parameters can be edited, and when the user  
Buttons on this screen include:  
• Configure: used to configure the burner control  
(password protected).  
Operation: used to perform daily or frequent functions  
is finished, control returns back to the configuration menu page.  
with the burner control, such as setpoint adjustment, etc.  
Each parameter is displayed in its group. If there are more  
parameters than will fit on the screen, a vertical scroll bar allows  
the user to scroll up and down to view all parameters. The  
parameter name is displayed on the left and the current setting is  
displayed in the text box on the right.  
Diagnostic: used to view burner control diagnostic  
information.  
Details: used to view burner control detail status  
information.  
History: used to view burner control history  
Pump: used to expand the pump status information.  
Modulation: used to toggle between status displays:  
pump, setpoints, and modulation.  
FIGURE 55. CONFIGURATION MENU PAGE  
FIGURE 54. SUMMARY STATUS PAGE  
FIGURE 56. SAMPLE CONFIGURATION PAGE  
53  
     
CONFIGURATION PASSWORD  
KEYBOARD  
Some parameters require a valid configuration password be Some pages request user entry of characters. When this type of  
entered by the user before the parameter can be changed. The input is required, a keyboard page appears, as shown in Figure  
password need only be entered once while the user remains on 58. The text box at the top of the screen displays the current (or  
the configuration pages. Leaving the configuration pages ends default) setting of the user input. The user can add to this text,  
the scope of the password.  
clear it, or change it.  
Three levels of access to Burner Control parameters are The Shift key on the left side of the screen shifts between upper  
permitted. Each access level has defined rights when interfacing and lowercase characters. Pressing the Shift key toggles the  
with configuration and status parameters within the controls.  
keyboard from one mode to the other (continuous pressing of the  
Shift button is not required). The OK button should be pressed  
when the user is done entering the text input. The Cancel button  
on the bottom of the screen allows the user to ignore any text  
changes that have been made and keep the original text value.  
Pressing the OK or Cancel buttons returns the user to the page  
displayed prior to the keyboard page.  
End user: The end user can read or view the control  
parameters and be allowed to change some operating  
parameters, CH setpoint as an example.  
Installer: The installer can read all control parameters  
and change default allowed parameters. This access  
level is used to customize the control for a particular  
installation.  
LOGIN  
Pressing the Login button allows entering the password from a  
keyboard as shown in Figure 58. After the password is entered,  
the OK button is selected. The Cancel button aborts the password  
login.  
OEM: The OEM can read and change all parameters,  
change sensor limits and burner control safety  
parameters.  
Different passwords exist in the Burner Control for each access  
level. The end user level requires no password, but the installer  
and OEM levels have unique passwords defined for them.  
The installer and OEM passwords can be changed in the Burner  
Control after logging in with the current password. When the  
password is changed, it is saved for all future logins.  
Note: For the S7999B System OI display, each boiler in a  
multi-boiler configuration has its own set of installer and OEM  
passwords. To avoid user confusion, the passwords should be  
changed to the same password in each control, but there is no  
requirement to do so. Make sure to record your password.  
The user is notified that a new password is needed to change  
a parameter (or until a password is entered successfully)—see  
Figure 57. The user can continue viewing the configuration  
parameters regardless of whether a password is entered  
successfully.  
The Burner Controls maintain a password time-out that limits the  
scope of the password entry. Once a password is successfully  
entered, the control starts an internal timer that expires after 10  
minutes of inactivity. After the timer expires, the user is required  
to re-enter a password before a parameter can be changed.  
FIGURE 58. DEVICE LOGIN SCREEN  
WARNING: Explosion Hazard. Improper configuration can cause  
fuel buildup and explosion. Improper user operation may result in  
property loss, physical injury or death.  
The user is not required to enter a configuration password for a  
parameter that has a lower access level than the access level  
achieved by an earlier password entry for any configuration  
group (as long as the user stays in the configuration pages). The  
user only needs to enter a password once until a parameter that  
has a higher access level is selected.  
Using the OI Displays to change parameters must be attempted  
by only experienced and/or licensed burner/boiler operators and  
mechanics.  
CHANGE PARAMETER SETTINGS  
Change parameter settings by selecting the parameter on the  
page. A dialog box displays for the parameter with controls  
allowing the user to change the value (see Figure 59 on Page 55).  
After changing the setting to a new value, press the OK button.  
Pressing the Cancel button leaves the parameter unchanged.  
The changed setting is reflected on the screen and sent to the  
control when the OK button is pressed.  
FIGURE 57. LOGIN REQUIRED  
54  
   
Note: When the installer proceeds with the safety parameter  
configuration, the control unlocks the safety parameters in this  
group and marks them unusable. Failure to complete the entire  
safety configuration procedure leaves the control in an un-  
runnable state (lockout 2).  
All safety configuration parameters in the group should have the  
same access level. If this condition isn’t so, the user is asked to  
enter another password when a higher access level is needed.  
Successful login is noted by the lock icon, which changes  
to “unlocked” on the page. The installer may begin to change  
safety parameters (or any other parameters) at that time (see  
Figure 61). If the Burner Control is in an unconfigured (or new)  
state, then this warning doesn’t appear. All parameters that need  
changes should be changed during the login.  
FIGURE 59. EXAMPLE OF CHANGE CONFIGURATION  
PARAMETER PAGE  
VERIFY  
Pressing the Verify button displays safety configuration  
parameters for an additional verification step to commit the  
changes.  
Safety parameters are grouped into blocks that include only  
safety parameters, not a mixture of safety data and non-safety  
data.All parameters within the safety group undergo a verification  
process. A safety parameter group is identified on the display to  
indicate when the configuration parameters are safety-related.  
Each safety parameter group is verified one at a time until all  
FIGURE 61. EDIT SAFETY DATA  
If the safety configuration session is terminated after it has  
started (in the Edit or Verify stages), the Burner Control is left in  
an unconfigured (unrunnable) state.  
The installer can terminate the session by pressing the Menu  
button or by attempting to leave the Verification page with  
the Home or Back buttons (top-left and -right screen corners,  
respectively). However, leaving the session at this point leaves  
the control in an unrunnable state and confirms whether the  
installer still wants to do so.  
The settings of all parameters in each safety block must be  
verified to save them in the control.  
When the installer is done changing safety parameters,  
pressing the Verify button on the configuration screen begins  
the Verification process. The settings for all safety parameters  
in each changed block are presented and Verified by the installer  
FIGURE 60. SAFETY VERIFICATION  
Like operating parameters, safety parameters can be viewed  
without the need to enter a password.  
Safety parameter blocks that have been changed require  
verification. The verification steps do not have to be completed  
immediately; the installer can move between and change  
parameter groups before the verification is done. A Verify button  
is enabled that allows the installer to conduct verification sessions  
(the example of the Verify button in Figure 55 is not yet enabled  
because the installer hasn’t logged in).  
55  
     
FAULT/ALARM HANDLING  
Each Burner Control reports to the OI display when a safety  
lockout or an Alert occurs.  
Safety lockouts are indicated on each configuration page as an  
alarm bell symbol. At the status page (for S7999B), the History  
button turns red. If the S7999B is displaying the system status  
icons, the control in alarm will turn red.  
The lockout history can be displayed by pressing on the History  
button. The state information about each lockout is displayed  
along with the date/time that the lockout occurred (refer to Table  
Note: In the event of a power interruption, the date/time must be  
reset. The OI Display does NOT have a backup means.  
TABLE 21. BURNER CONTROL LOCKOUT HISTORY  
DATA  
Lockout time  
COMMENT  
Set by display  
FIGURE 62. SAFETY PARAMETER CONFIRMATION  
Fault Code  
Unique code defining which  
lockout occurred.  
Press the Yes button to confirm each safety parameter block. If  
the No button is selected, the safety parameter block remains  
unconfirmed and the Configuration menu page is displayed. The  
control remains in an unconfigured state in this case.  
Annunciator first out  
First interlock in limit string  
results in a shutdown.  
Description  
Fault description  
After all safety parameter blocks have been confirmed, the  
installer is asked to press and hold the Reset button on the  
Burner Control to complete the safety verification session (see  
Burner Lockout/Hold  
Source/reason for lockout/  
hold  
Burner control state  
Sequence time  
Burner control state timer at  
time of fault  
Cycle  
Burner control cycle  
Burner control hours  
Run Hours  
I/O  
All digital I/O status at time of  
fault  
Annunciator 1-8 states  
Fault data  
All annunciator I/O status at  
time of fault  
Fault dependent data  
An alert log can be displayed for each control by pressing theAlert  
button on the bottom of the history status page. A description of  
the alert is displayed along with the time when the alert occurred  
(refer to Table 22).  
TABLE 22. BURNER CONTROL ALERT LOG  
DATA  
COMMENT  
Set by display  
Alert Line  
FIGURE 63. SAFETY PARAMETER RESET  
Alert Code  
Unique Code defining which  
fault occured.  
When the Reset button is pressed and held for 3 seconds the  
confirmed safety parameters are saved in the control. The  
above Reset dialog box automatically closes when this step is  
completed.  
Description  
Alert description  
If this step is not performed, the control remains in a safety lockout  
state until the installer resolves the unverified safety parameters.  
HISTORY BUTTON  
The History button on the Home page serves not only as a  
button, but also displays Burner Control lockouts, holds, and  
alerts as they occur. The History button can be selected at any  
time, regardless of which type of information is displayed, to view  
history information. Pressing the History button displays a dialog  
box (see Figure 64 on Page 57) that allows the user to select  
the type of history to view. The user can also silence an audible  
alarm generated by the control during a lockout or alert by alarm  
condition.  
56  
       
This History dialog box provides an exploded view of the status  
information displayed in the History button (the font is larger).  
One of the four buttons (OK, Lockouts, Alerts, or Silence) can  
be selected. If none of these buttons are selected the dialog box  
closes after 30 seconds.  
Note: The system time can be set in the OI display to ensure that  
correct timestamps are given to the controls’ lockouts and alerts.  
Power interruptions will require the time to be reset as the display  
DOES NOT have a time backup means.  
The Clear Lockout button allows the user to acknowledge and  
clear (reset) the lockout when in lockout state, much the same  
as pressing the reset button on the front of the Burner Control.  
The user can toggle between displaying the controls’ lockout  
history and alert log by pressing the Alerts or Lockouts button on  
the bottom of the pages.  
FIGURE 64. EXAMPLE OF HYDRONIC HISTORY  
Two types of historical data can be displayed on the history page:  
lockout history and alert log.  
The entire 15 fault code history is displayed in a scrollable list  
with the most recent fault displayed first followed by the next  
most recent fault. Summary information is displayed for each  
fault entry, including the burner cycle count, fault code, and fault  
number with description. Detailed information for a specific fault  
entry that also includes burner control sequence state, burner  
run-time hours, annunciation status, etc., is viewed by selecting  
(touching the History line) the lockout entry in the list.  
FIGURE 66. EXAMPLE OF ALERT SHOWN  
To see additional detail about a lockout or alert, touching on the  
lockout or alert in the list expands the view of that lockout or alert,  
FIGURE 67. CONTROL EXPANDED LOCKOUT DETAIL  
FIGURE 65. EXAMPLE OF LOCKOUT HISTORY  
The date and time that each fault occurred is displayed in the  
lockout history. The lockout timestamp displays in both the  
lockout summary and detail information.  
The Burner Control does not maintain date or time of day  
information. The date and time stamp is assigned by the OI  
display. When the OI display first obtains the lockout and alert  
history from the control (during the display data synchronization),  
no timestamps are assigned since the times that the lockouts  
occurred are unknown. All new lockouts that occur after the  
synchronization are assigned timestamps.  
57  
     
FIGURE 68. CONTROL EXPANDED ALERT DETAIL  
OPERATION BUTTON  
FIGURE 70. PROGRAMMABLE ANNUNCIATION  
The operation button displays the Burner Control running  
operation, including setpoint and firing rate values. From this page  
the user can change setpoints, manually control the boiler’s firing  
rate, manually turn pumps on, view annunciation information,  
and switch between hydronic heating loops (Central Heat and  
Domestic Hot Water), as shown in Figure 69. If a password is  
required to change any of the settings on this page, the user can  
press the Login button to enter the password.  
FIGURE 71. FIXED ANNUNCIATION  
FIGURE 69. HYDRONIC OPERATION PAGE  
58  
     
DIAGNOSTICS BUTTON  
SYSTEM CONFIGURATION (S7999B OI DISPLAY ONLY)  
The Diagnostics button displays analog and digital I/O status  
of the Burner Control. A snapshot of the diagnostic status is  
displayed and updated once per second as it changes in the  
control.  
The OI Display has some functions related to general  
configuration for the control in the end user installation. Pressing  
the Display Refresh button invokes a search procedure (see  
Figure 74). A new R7910A Hydronic Control or R7911 Steam  
Control is identified by “Unknown” status next to its name in  
the boiler system list (see Figure 75). “Unknown” indicates that  
configuration data has not been retrieved from the control yet.  
The digital I/O data is displayed as LEDs that are either on  
(green) or off (red) (See Figure 72). Not all digital I/O can be  
displayed at the same time on the page, so a horizontal scroll bar  
is used to move the view left and right to show all digital I/O data.  
FIGURE 74. SYSTEM REFRESH  
FIGURE 72. DIAGNOSTICS PAGE (DIGITAL I/O)  
The control analog I/O can also be viewed on the OI Display. A  
snapshot of the diagnostic status is displayed and updated as it  
changes in the control.  
The analog I/O data is displayed as bar charts with I/O level  
represented in the I/O range (see Figure 73) Analog I/O that is  
not enabled for the installation displays a blank I/O level. Not all  
analog I/O can be displayed at the same time on the page, so  
a horizontal scroll bar is used to move the view left and right to  
show all analog I/O status.  
FIGURE 75. SYSTEM CONFIGURATION PAGE  
The control connected to the Modbus network is indicated to the  
user after the search procedure has concluded.  
Once the control is located it must be synchronized with the OI  
Display before it can be displayed. New controls are not displayed  
on the Home page until this synchronization is performed.  
FIGURE 73. DIAGNOSTIC PAGE (ANALOG I/O)  
59  
       
SYSTEM SYNCHRONIZATION (S7999B OI DISPLAY ONLY)  
CONFIGURATION  
The user can manually synchronize configuration data from the The Burner Control can be configured from the OI Display. The  
connected controls at any time.  
control configuration is grouped into the functional groups as  
shown in Table 23.  
A new control is visible when configuration and status data is  
gathered from it. This collection procedure takes a few minutes.  
The control is marked as “Unknown” when no configuration  
information exists. Normally, control configuration data collection  
only needs to be performed when the control is initially installed.  
However, a re synchronization is necessary after the OI Display  
TABLE 23. FUNCTIONAL CONFIGURATION GROUPS  
HYDRONIC CONTROL  
System Identification and  
Access  
CH - Central Heat  
Outdoor Reset  
TheuserpressestheSynchronizebuttontobeginsynchronization  
DHW - Domestic Hot Water  
DHW Storage  
DHW Plate  
Warm Weather Shutdown  
Demand Priority  
Modulation Configuration  
Pump Configuration  
Statistics Configuration  
High Limit  
Stack Limit  
Delta T Limits  
T-Rise Limit  
Heat Exchanger High Limit  
Anti-condensation  
Frost Protection Configuration  
Annunciation Configuration  
Burner Control Interlocks  
Burner Control Timings and Rates  
Burner Control Ignition  
Burner Control Flame Failure  
System Configuration  
Fan Configuration  
FIGURE 76. SYSTEM SYNCHRONIZATION  
Status of the synchronization is reflected in the dialog box. The  
synchronization can be aborted by selecting the Cancel button.  
Sensor Configuration  
Lead Lag Slave Configuration  
Lead Lag Master Configuration  
Most of this configuration is performed by the Service Agent  
or at A.O. Smith. Each functional group is displayed on the  
Configuration menu page.  
Parameters in functional groups that are not applicable for  
the installation can be ignored. In some cases, features in a  
functional group are disabled by default and are enabled when  
needed for the installation.  
60  
   
TROUBLESHOOTING  
To support the recommended Troubleshooting, the R7910 has an Alert File. Review the Alert history for possible trends that may have  
been occurring prior to the actual Lockout.  
Note Column: H= Hold message; L=Lockout message; H or L= either Hold or Lockout depending on Parameter Configuration.  
TABLE 24. TROUBLESHOOTING CODES  
CODE  
DESCRIPTION  
RECOMMENDED TROUBLESHOOTING OF  
LOCKOUT CODES  
NOTE  
Safety Data Faults  
1
Unconfigured safety data  
1. New Device, complete device configuration and  
safety verification.  
L
2. If fault repeats, replace module.  
2
Waiting for safety data verification  
1. Device in Configuration mode and safety  
parameters need verification and a device needs  
reset to complete verification.  
L
2. Configuration ended without verification, re enter  
configuration, verify safety parameters and reset  
device to complete verification.  
3. If fault repeats, replace module.  
Internal Operation Errors  
3
Internal fault: Hardware fault  
Internal Fault.  
H
1. Reset Module.  
2. If fault repeats, replace module.  
4
Internal fault: Safety Relay key feedback error  
Internal fault: Unstable power (DCDC) output  
Internal fault: Invalid processor clock  
Internal fault: Safety relay drive error  
Internal fault: Zero crossing not detected  
Internal fault: Flame bias out of range  
Internal fault: Invalid Burner control state  
Internal fault: Invalid Burner control state flag  
Internal fault: Safety relay drive cap short  
Internal fault: PII shorted to ILK  
H
5
H
6
H
7
H
8
H
9
H
10  
11  
12  
13  
14  
15  
L
L
H
H or L  
H or L  
L
Internal fault: HFS shorted to LCI  
Internal fault: Safety relay test failed due to  
feedback ON  
16  
17  
18  
Internal fault: Safety relay test failed due to safety  
relay OFF  
L
L
L
Internal fault: Safety relay test failed due to safety  
relay not OFF  
Internal fault: Safety relay test failed due to  
feedback not ON  
19  
20  
21  
22  
23  
Internal fault: Safety RAM write  
L
Internal fault: Flame ripple and overflow  
Internal fault: Flame number of sample mismatch  
Internal fault: Flame bias out of range  
H
H
H
H
Internal fault: Bias changed since heating cycle  
starts  
24  
25  
Internal fault: Spark voltage stuck low or high  
H
H
Internal fault: Spark voltage changed too much  
during flame sensing time  
26  
27  
Internal fault: Static flame ripple  
H
H
Internal fault: Flame rod shorted to ground  
detected  
28  
29  
Internal fault: A/D linearity test fails  
H
H
Internal fault: Flame bias cannot be set in range  
61  
CODE  
DESCRIPTION  
RECOMMENDED TROUBLESHOOTING OF  
LOCKOUT CODES  
NOTE  
30  
Internal fault: Flame bias shorted to adjacent pin  
Internal fault: SLO electronics unknown error  
Internal fault: Safety Key 0 through 14  
System Errors  
Internal Fault.  
1. Reset Module.  
2. If fault repeats, replace module.  
H
31  
H
32 - 46  
L
47  
48  
49  
Flame Rod to ground leakage  
Static flame (not flickering)  
H
H
H
24 VAC voltage low/high  
1. Check the Module and display connections.  
2. Check the Module power supply and make sure  
that both frequency, voltage and VA meet the  
specifications.  
50  
51  
52  
Modulation fault  
Pump fault  
Internal sub-system fault.  
1. Review alert messages for possible trends.  
2. Correct possible problems.  
H
H
H
Motor tachometer fault  
3. If fault persists, replace module.  
53  
AC inputs phase reversed  
1. Check the Module and display connections.  
2. Check the Module power supply and make  
sure that both frequency and voltage meet the  
specifications.  
L
3. On 24 VAC applications, assure that J4-10 and  
J8-2 are connected together.  
54  
Safety GVT model ID does not match application's Contact the service professional.  
model ID  
L
L
55  
Application configuration data block CRC errors  
RESERVED  
Contact the service professional.  
56 - 57  
58  
Internal fault: HFS shorted to IAS  
Internal Fault: Mux pin shorted  
Normal Event Status  
Internal Fault.  
1. Reset Module.  
2. If fault repeats, replace module.  
L
L
59  
60  
61  
62  
63  
Internal Fault: HFS shorted to LFS  
Anti short cycle  
L
Will not be a lockout fault. Hold Only.  
H
H
H
Fan speed not proved  
LCI OFF  
1. Check wiring and correct any faults.  
2. Check Interlocks connected to the LCI to assure  
proper function.  
3. Reset and sequence the module; monitor the LCI  
status.  
4. If code persists, replace the module.  
64  
PII OFF  
1. Check wiring and correct any faults.  
2. Check Preignition Interlock switches to assure  
proper functioning.  
H or L  
3. Check the valve operation.  
4. Reset and sequence the module; monitor the PII  
status.  
5. If code persists, replace the module.  
65  
66  
Interrupted Airflow Switch OFF  
Interrupted Airflow Switch ON  
1. Check wiring and correct any possible shorts.  
2. Check airflow switches to assure proper  
functioning.  
H or L  
H or L  
3. Check the fan/blower operation.  
4. Reset and sequence the module; monitor the  
airflow status.  
5. If code persists, replace the module.  
62  
CODE  
DESCRIPTION  
RECOMMENDED TROUBLESHOOTING OF  
LOCKOUT CODES  
NOTE  
67  
ILK OFF  
ILK ON  
1. Check wiring and correct any possible shorts.  
2. Check Interlock (ILK) switches to assure proper  
function.  
H or L  
H or L  
68  
3. Verify voltage through the interlock string to the  
interlock input with a voltmeter.  
4. If steps 1-3 are correct and the fault persists,  
replace the module.  
69  
70  
Pilot test hold  
1. Verify Run/Test is changed to Run.  
2. Reset Module.  
3. If fault repeats, replace module.  
H
H
Wait for leakage test completion  
1. Internal Fault. Reset Module.  
2. If fault repeats, replace module.  
71 - 77  
78  
RESERVED  
Demand Lost in Run  
1. Check wiring and correct any possible errors.  
2. If previous steps are correct and fault persists,  
replace the module.  
H
79  
80  
81  
Outlet high limit  
DHW high limit  
Delta T limit  
1. Check wiring and correct any possible errors.  
2. Replace the Outlet high limit.  
3. If previous steps are correct and fault persists,  
replace the module.  
H or L  
1. Check wiring and correct any possible errors.  
2. Replace the DHW high limit.  
3. If previous steps are correct and fault persists,  
replace the module.  
H or L  
1. Check Inlet and Outlet sensors and pump circuits H or L  
for proper operation.  
2. Recheck the Delta T Limit to confirm proper  
setting.  
3. If previous steps are correct and fault persists,  
replace the module.  
82  
Stack limit  
1. Check wiring and correct any possible errors.  
2. Replace the Stack high limit.  
H or L  
3. If previous steps are correct and fault persists,  
replace the module.  
83  
84  
85  
86  
87  
88  
89  
90  
Delta T exchanger/outlet limit  
Delta T inlet/exchanger limit  
Inlet/outlet inversion limit  
Exchanger/outlet inversion limit  
Inlet/exchanger inversion limit  
Outlet T-rise limit  
Not Applicable.  
Not Applicable.  
Not Applicable.  
Not Applicable.  
Not Applicable.  
Check for adequate flow.  
Not Applicable.  
Not Applicable.  
H or L  
H or L  
H or L  
H or L  
H or L  
H or L  
H or L  
H or L  
Exchanger T-rise limit  
Heat exchanger high limit  
Sensor Faults  
91  
92  
93  
Inlet sensor fault  
1. Check wiring and correct any possible errors.  
2. Replace the Inlet sensor.  
3. If previous steps are correct and fault persists,  
replace the module.  
H
H
H
Outlet sensor fault  
DHW sensor fault  
1. Check wiring and correct any possible errors.  
2. Replace the Outlet sensor.  
3. If previous steps are correct and fault persists,  
replace the module.  
1. Check wiring and correct any possible errors.  
2. Replace the DHW sensor.  
3. If previous steps are correct and fault persists,  
replace the module.  
63  
CODE  
DESCRIPTION  
RECOMMENDED TROUBLESHOOTING OF  
LOCKOUT CODES  
NOTE  
94  
Header sensor fault  
1. Check wiring and correct any possible errors.  
2. Replace the header sensor.  
H
3. If previous steps are correct and fault persists,  
replace the module.  
95  
96  
Stack sensor fault  
1. Check wiring and correct any possible errors.  
2. Replace the stack sensor.  
3. If previous steps are correct and fault persists,  
replace the module.  
H
H
Outdoor sensor fault  
1. Check wiring and correct any possible errors.  
2. Replace the outdoor sensor.  
3. If previous steps are correct and fault persists,  
replace the module.  
97  
Internal Fault: A2D mismatch.  
Internal Fault.  
1. Reset Module.  
2. If fault repeats, replace module.  
L
L
L
H
98  
Internal Fault: Exceeded VSNSR voltage  
Internal Fault: Exceeded 28V voltage tolerance  
Pressure Sensor Fault  
99  
100  
1. Verify the Pressure Sensor is a 4-20 ma source.  
2. Check wiring and correct any possible errors.  
3. Test Pressure Sensor for correct operation.  
4. Replace the Pressure sensor.  
5. If previous steps are correct and fault persists,  
replace the module.  
101-104 RESERVED  
Flame Operation Faults  
105  
Flame detected out of sequence  
1. Check that flame is not present in the combustion H or L  
chamber. Correct any errors.  
2. Make sure that the flame detector is wired to the  
correct terminal.  
3. Make sure the F & G wires are protected from  
stray noise pickup.  
4. Reset and sequence the module, if code  
reappears, replace the flame detector.  
5. Reset and sequence the module, if code  
reappears, replace the module.  
106  
107  
108  
109  
Flame lost in MFEP  
Flame lost early in run  
Flame lost in run  
Ignition failed  
1. Check pilot valve (Main Valve for DSI) wiring and  
operation - correct any errors.  
2. Check the fuel supply.  
3. Check fuel pressure and repeat turndown tests.  
4. Check ignition transformer electrode, flame  
detector, flame detector siting or flame rod  
position.  
L
L
L
L
5. If steps 1 through 4 are correct and the fault  
persists, replace the module.  
110  
Ignition failure occurred  
Hold time of recycle and hold option. Will not be a  
lockout fault. Hold Only.  
H
111  
112  
Flame current lower than WEAK threshold  
Pilot test flame timeout  
Internal hardware test. Not a lockout,  
H
Interrupted Pilot or DSI application and flame lost  
when system in “test” mode.  
L
1. Reset the module to restart.  
113  
Flame circuit timeout  
Flame sensed during Initiate or off cycle, hold 240  
seconds, if present after 240 seconds, lockout.  
L
114-121 RESERVED  
Rate Proving Faults  
122  
123  
Lightoff rate proving failed  
Purge rate proving failed  
1. Check wiring and correct any potential wiring  
errors.  
2. Check VFDs ability to change speeds.  
3. Change the VFD  
L
L
4. If the fault persists, replace the module.  
64  
CODE  
DESCRIPTION  
RECOMMENDED TROUBLESHOOTING OF  
LOCKOUT CODES  
NOTE  
124  
High fire switch OFF  
1. Check wiring and correct any potential wiring  
errors.  
2. Check High Fire Switch to assure proper function  
(not welded or jumpered).  
H
125  
High fire switch stuck ON  
H
3. Manually drive the motor to the High Fire position  
and adjust the HF switch while in this position  
and verify voltage through the switch to the HFS  
input with a voltmeter.  
4. If steps 1-3 are correct and the fault persists,  
replace the module.  
126  
127  
Low fire switch OFF  
1. Check wiring and correct any potential wiring  
errors.  
2. Check Low Fire Switch to assure proper function  
(not welded or jumpered).  
H
Low fire switch stuck ON  
H or L  
3. Manually drive the motor to the High Fire position  
and adjust the LF switch while in this position and  
verify voltage through the switch to the LFS input  
with a voltmeter.  
4. If steps 1-3 are correct and the fault persists,  
replace the module.  
128  
129  
130  
131  
132  
Fan speed failed during prepurge  
Fan speed failed during preignition  
Fan speed failed during ignition  
Fan movement detected during standby  
Fan speed failed during run  
1. Check wiring and correct any potential wiring  
errors.  
2. Check VFDs ability to change speeds.  
3. Change the VFD  
H or L  
H or L  
H or L  
H
4. If the fault persists, replace the module.  
H
133-135 RESERVED  
Start Check Faults  
Interrupted Airflow Switch failed to close  
136  
1. Check wiring and correct any possible wiring  
errors.  
2. Check Interrupted Airflow switch(es) to assure  
proper function.  
3. Verify voltage through the airflow switch to the  
IAS input with a voltmeter.  
4. If steps 1-3 are correct and the fault persists,  
replace the module.  
H
H
137  
ILK failed to close  
1. Check wiring and correct any possible shorts.  
2. Check Interlock (ILK) switches to assure proper  
function.  
3. Verify voltage through the interlock string to the  
interlock input with a voltmeter.  
4. If steps 1-3 are correct and the fault persists,  
replace the module.  
138-142 RESERVED  
FAULT CODES 149 THROUGH 165 ARE  
OEM SPECIFIC FAULT CODES.  
Internal fault: Flame bias out of range 1  
Internal fault: Flame bias out of range 2  
Internal fault: Flame bias out of range 3  
Internal fault: Flame bias out of range 4  
Internal fault: Flame bias out of range 5  
Internal fault: Flame bias out of range 6  
Flame detected  
143  
144  
145  
146  
147  
148  
149  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
L
L
L
L
L
L
OEM Specific  
H or L  
1. Holds if flame detected during Safe Start check  
up to Flame Establishing period.  
65  
CODE  
DESCRIPTION  
RECOMMENDED TROUBLESHOOTING OF  
LOCKOUT CODES  
NOTE  
150  
Flame not detected  
OEM Specific  
H
1. Sequence returns to standby and restarts  
sequence at the beginning of Purge after the HF  
switch opens. If flame detected during Safe Start  
check up to Flame Establishing period.  
151  
High fire switch ON  
OEM Specific  
H or L  
1. Check wiring and correct any potential wiring  
errors.  
2. Check High Fire Switch to assure proper function  
(not welded or jumpered).  
3. Manually drive the motor to the High Fire position  
and adjust the HF switch while in this position  
and verify voltage through the switch to the HFS  
input with a voltmeter.  
4. If steps 1-3 are correct and the fault persists,  
replace the module.  
152  
153  
Combustion pressure ON  
Combustion pressure Off  
OEM Specific  
H or L  
H or L  
1. Check wiring and correct any errors.  
2. Inspect the Combustion Pressure Switch to make  
sure it is working correctly.  
3. Reset and sequence the relay module.  
4. During STANDBY and PREPURGE, measure  
the voltage between Terminal J6-5 and L2 (N).  
Supply voltage should be present. If not, the  
lockout switch is defective and needs replacing.  
5. If the fault persists, replace the relay module.  
154  
155  
156  
157  
Purge Fan switch On  
OEM Specific  
1. Purge fan switch is on when it should be off.  
H or L  
H
Purge Fan switch Off  
Combustion pressure and Flame ON  
Combustion pressure and Flame OFF  
OEM Specific  
1. Check that flame is not present in the combustion  
chamber. Correct any errors.  
H or L  
L
2. Make sure that the flame detector is wired to the  
correct terminal.  
3. Make sure the F & G wires are protected from  
stray noise pickup.  
4. Reset and sequence the module, if code  
reappears, replace the flame detector.  
158  
159  
Main valve ON  
Main valve OFF  
OEM Specific  
1. Check Main Valve terminal wiring and correct any  
errors.  
L
L
2. Reset and sequence the module. If fault persist,  
replace the module.  
160  
161  
Ignition ON  
Ignition OFF  
OEM Specific  
1. Check Ignition terminal wiring and correct any  
errors.  
L
L
2. Reset and sequence the module. If fault persist,  
replace the module.  
162  
163  
Pilot valve ON  
Pilot valve OFF  
OEM Specific  
1. Check Pilot Valve terminal wiring and correct any  
errors.  
L
L
2. Reset and sequence the module. If fault persist,  
replace the module.  
66  
CODE  
DESCRIPTION  
RECOMMENDED TROUBLESHOOTING OF  
LOCKOUT CODES  
NOTE  
164  
165  
Block intake ON  
Block intake OFF  
OEM Specific  
L
1. Check wiring and correct any errors.  
2. Inspect the Block Intake Switch to make sure it is  
working correctly.  
L
3. Reset and sequence the module.  
4. During Standby and Purge, measure the voltage  
across the switch. Supply voltage should  
be present. If not, the Block Intake Switch is  
defective and needs replacing.  
5. If the fault persists, replace the relay module.  
166-171 RESERVED  
Feedback  
172  
173  
174  
175  
176  
177  
178  
Main relay feedback incorrect  
Pilot relay feedback incorrect  
Internal Fault.  
1. Reset Module.  
2. If fault repeats, replace module.  
L
L
L
L
L
L
L
Safety relay feedback incorrect  
Safety relay open  
Main relay ON at safe start check  
Pilot relay ON at safe start check  
Safety relay ON at safe start check  
179-183 RESERVED  
Parameter Faults  
184  
185  
186  
187  
188  
189  
190  
191  
Invalid BLOWER/HSI output setting  
Invalid Delta T limit enable setting  
Invalid Delta T limit response setting  
Invalid DHW high limit enable setting  
Invalid DHW high limit response setting  
Invalid Flame sensor type setting  
1. Return to Configuration mode and recheck  
selected parameters, reverify and reset module.  
2. If fault repeats, verify electrical grounding.  
3. If fault repeats, replace module.  
L
L
L
L
L
L
L
L
Invalid interrupted air switch enable setting  
Invalid interrupted air switch start check enable  
setting  
192  
193  
194  
195  
196  
197  
198  
199  
200  
201  
202  
203  
204  
205  
206  
207  
208  
209  
210  
211  
Invalid igniter on during setting  
Invalid ignite failure delay setting  
Invalid ignite failure response setting  
Invalid ignite failure retries setting  
Invalid ignition source setting  
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
1. Return to Configuration mode and recheck  
selected parameters, reverify and reset module.  
2. If fault repeats, verify electrical grounding.  
3. If fault repeats, replace module.  
Invalid interlock open response setting  
Invalid interlock start check setting  
Invalid LCI enable setting  
Invalid lightoff rate setting  
Invalid lightoff rate proving setting  
Invalid Main Flame Establishing Period time  
Invalid MFEP flame failure response setting  
Invalid NTC sensor type setting  
Invalid Outlet high limit response setting  
Invalid Pilot Flame Establishing Period setting  
Invalid PII enable setting  
Invalid pilot test hold setting  
Invalid Pilot type setting  
Invalid Postpurge time setting  
Invalid Power up with lockout setting  
67  
CODE  
DESCRIPTION  
RECOMMENDED TROUBLESHOOTING OF  
LOCKOUT CODES  
NOTE  
212  
Invalid Preignition time setting  
1. Return to Configuration mode and recheck  
selected parameters, reverify and reset module.  
2. If fault repeats, verify electrical grounding.  
3. If fault repeats, replace module.  
L
213  
214  
215  
216  
217  
218  
219  
220  
221  
222  
223  
224  
225  
226  
227  
228  
229  
230  
231  
232  
233  
234  
235  
236  
237  
238  
239  
240  
241  
Invalid Prepurge rate setting  
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
Invalid Prepurge time setting  
Invalid Purge rate proving setting  
Invalid Run flame failure response setting  
Invalid Run stabilization time setting  
Invalid Stack limit enable setting  
Invalid Stack limit response setting  
Unconfigured Delta T limit setpoint setting  
Unconfigured DHW high limit setpoint setting  
Unconfigured Outlet high limit setpoint setting  
Unconfigured Stack limit setpoint setting  
Invalid DHW demand source setting  
Invalid Flame threshold setting  
Invalid Outlet high limit setpoint setting  
Invalid DHW high limit setpoint setting  
Invalid Stack limit setpoint setting  
Invalid Modulation output setting  
Invalid CH demand source setting  
Invalid Delta T limit delay setting  
Invalid Pressure sensor type setting  
Invalid IAS closed response setting  
Invalid Outlet high limit enable setting  
Invalid Outlet connector type setting  
Invalid Inlet connector type setting  
Invalid DHW connector type setting  
Invalid Stack connector type setting  
Invalid S2 (J8-6) connector type setting  
Invalid S5 (J8-11) connector type setting  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
Not Applicable.  
Exchanger sensor not allowed with stack  
connector setting  
242  
243  
Invalid DHW auto detect configuration  
Not Applicable.  
L
L
Invalid UV with spark interference not compatible  
with Ignitor on throughout PFEP  
Contact the service professional.  
244  
245  
246  
Internal fault: Safety relay test invalid state  
Invalid Outlet connector type setting for Trise  
Contact the service professional.  
Contact the service professional.  
Contact the service professional.  
L
L
L
4-20mA cannot be used for both modulation and  
setpoint control  
247  
248  
249  
Invalid ILK bounce detection enable  
Invalid forced recycle interval  
Not Applicable.  
Not Applicable.  
Not Applicable.  
L
L
L
STAT cannot be demand source when Remote  
Stat is enabled  
250  
Invalid Fan speed error response  
1. Check fan cables secured properly. If fault  
L
persists contact the service professional.  
251-255 RESERVED  
68  
TABLE 25. ALERTS  
CODE  
DESCRIPTION  
CODE  
DESCRIPTION  
EE Management Faults  
None (No alert)  
37  
Program Module application parameter revision  
differs from application processor  
0
38  
Program Module safety parameter revision differs  
from safety processor  
1
2
Alert PCB was restored from factory defaults  
Safety configuration parameters were restored  
from factory defaults  
39  
40  
41  
42  
43  
PCB incompatible with product contained in  
Program Module  
3
Configuration parameters were restored from  
factory defaults  
Parameter PCB in Program Module is too large for  
product  
4
Invalid Factory Invisibility PCB was detected  
Invalid Factory Range PCB was detected  
Invalid range PCB record has been dropped  
EEPROM lockout history was initialized  
Range PCB in Program Module was too large for  
product  
5
6
Alert PCB in Program Module was too large for  
product  
7
IAS start check was forced on due to IAS enabled  
System Operation Faults  
8
Switched application annunciation data blocks  
Switched application configuration data blocks  
Configuration was restored from factory defaults  
9
44  
45  
46  
47  
48  
Low voltage was detected in safety processor  
High line frequency occurred  
10  
11  
Backup configuration settings was restored from  
active configuration  
Low line frequency occurred  
12  
13  
14  
Annunciation configuration was restored from  
factory defaults  
Invalid subsystem reset request occurred  
Write large enumerated Modbus register value  
was not allowed  
Annunciation configuration was restored from  
backup  
49  
50  
51  
52  
Maximum cycle count was reached  
Maximum hours count was reached  
Illegal Modbus write was attempted  
Safety group verification table was restored from  
factory defaults  
15  
16  
17  
Safety group verification table was updated  
Invalid Parameter PCB was detected  
Invalid Range PCB was detected  
Modbus write attempt was rejected (NOT  
ALLOWED)  
53  
54  
55  
56  
57  
58  
Illegal Modbus read was attempted  
System Parameter Errors  
Safety processor brown-out reset occurred  
Application processor watchdog reset occurred  
Application processor brown-out reset occurred  
Safety processor watchdog reset occurred  
Alarm was reset by the user at the control  
Demand/Rate Command Faults  
18  
19  
20  
21  
Alarm silence time exceeded maximum  
Invalid safety group verification table was detected  
Backdoor Password could not be determined  
Invalid safety group verification table was not  
accepted  
22  
CRC errors were found in application configuration  
data blocks  
59  
60  
61  
62  
63  
Burner control firing rate was > absolute max rate  
Burner control firing rate was < absolute min rate  
Burner control firing rate was invalid, % vs. RPM  
Burner control was firing with no fan request  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
Backup Alert PCB was restored from active one  
RESERVED  
Lead Lag operation switch was turned OFF  
Lead Lag operation switch was turned ON  
Safety processor was reset  
Burner control rate (nonfiring) was > absolute max  
rate  
64  
Burner control rate (nonfiring) was < absolute min  
rate  
Application processor was reset  
Burner switch was turned OFF  
65  
66  
Burner control rate (nonfiring) was absent  
Burner switch was turned ON  
Burner control rate (nonfiring) was invalid, %  
vs.RPM  
Program Module (PM) was inserted into socket  
Program Module (PM) was removed from socket  
Alert PCB was configured  
67  
68  
69  
70  
Fan off cycle rate was invalid, % vs. RPM  
Setpoint was overridden due to sensor fault  
Modulation was overridden due to sensor fault  
Parameter PCB was configured  
Range PCB was configured  
No demand source was set due to demand priority  
conflicts  
Program Module (PM) incompatible with product  
was inserted into socket  
71-73  
RESERVED  
69  
CODE  
DESCRIPTION  
CODE  
DESCRIPTION  
Fan Parameter Errors  
114  
MIX modulation range (max minus min) was too  
small (< 4% or 40 RPM)  
74  
Periodic Forced Recycle  
Modulation Operation Faults  
75  
Absolute max fan speed was out of range  
Absolute min fan speed was out of range  
Fan gain down was invalid  
115  
116  
117  
118  
119  
120  
Fan was limited to its minimum duty cycle  
Manual rate was > CH max modulation rate  
Manual rate was > DHW max modulation rate  
Manual rate was < min modulation rate  
Manual rate in Standby was > absolute max rate  
76  
77  
78  
Fan gain up was invalid  
79  
Fan minimum duty cycle was invalid  
Fan pulses per revolution was invalid  
Fan PWM frequency was invalid  
RESERVED  
80  
Modulation commanded rate was > CH max  
modulation rate  
81  
82-83  
121  
122  
Modulation commanded rate was > DHW max  
modulation rate  
Modulation Parameter Errors  
84  
85  
Lead Lag CH 4-20 mA water temperature setting  
Modulation commanded rate was < min  
modulation rate  
No Lead Lag add stage error threshold was  
configured  
123  
124  
125  
126  
Modulation rate was limited due to outlet limit  
Modulation rate was limited due to Delta-T limit  
Modulation rate was limited due to stack limit  
86  
87  
88  
No Lead Lag add stage detection time was  
configured  
No Lead Lag drop stage error threshold was  
configured  
Modulation rate was limited due to  
anticondensation  
No Lead Lag drop stage detection time was  
configured  
127  
128  
129  
Fan Speed out of range in RUN  
Modulation rate was limited due to IAS was open  
89  
90  
91  
92  
RESERVED  
Slow start ramp setting of zero will result in no  
modulation rate change  
Modulation output type was invalid  
Firing rate control parameter was invalid  
130  
No forced rate was configured for slow start ramp  
CH parameter Errors  
Forced rate was out of range vs. min/max  
modulation  
131  
132  
133  
134  
135  
136  
137  
138  
139  
140  
141  
142  
143  
144  
145  
CH demand source was invalid  
CH P-gain was invalid  
93  
94  
95  
96  
97  
98  
99  
100  
Forced rate was invalid, % vs. RPM  
Slow start ramp value was invalid  
CH I-gain was invalid  
Slow start degrees value was invalid  
CH D-gain was invalid  
Slow start was ended due to outlet sensor fault  
Slow start was end due to reference setpoint fault  
CH max modulation rate was invalid, % vs. RPM  
CH max modulation rate was > absolute max rate  
CH OFF hysteresis was invalid  
CH ON hysteresis was invalid  
CH sensor type was invalid  
CH hysteresis step time was invalid  
CH remote control parameter was invalid  
CH ODR not allowed with remote control  
Steam P-gain was invalid  
CH modulation range (max minus min) was too  
small (< 4% or 40 RPM)  
101  
102  
DHW max modulation rate was invalid, % vs.RPM  
DHW max modulation rate was > absolute max  
rate  
Steam I-gain was invalid  
103  
DHW modulation range (max minus min) was too  
small (< 4% or 40 RPM)  
Steam D-gain was invalid  
Steam OFF hysteresis was invalid  
Steam ON hysteresis was invalid  
CH Operation Faults  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
Min modulation rate was < absolute min rate  
Min modulation rate was invalid, % vs. RPM  
Manual rate was invalid, % vs. RPM  
146  
147  
148  
149  
CH control was suspended due to fault  
CH header temperature was invalid  
CH outlet temperature was invalid  
CH steam pressure was invalid  
CH Parameter errors (continued)  
Steam setpoint source parameter was invalid  
Slow start enabled, but forced rate was invalid  
Analog output hysteresis was invalid  
Analog modulation output type was invalid  
IAS open rate differential was invalid  
IAS open step rate was invalid  
150  
151  
MIX max modulation rate was invalid, % vs. RPM  
Minimum water temperature parameter was  
greater than setpoint  
MIX max modulation rate was >absolute max or <  
absolute min rates  
70  
CODE  
DESCRIPTION  
CODE  
191  
DESCRIPTION  
152  
Minimum water temperature parameter was  
greater than time of day setpoint  
Lead Lag base load common setting was invalid  
Lead Lag DHW demand switch setting was  
Lead Lag Mix demand switch setting was invalid  
Lead Lag modulation sensor setting was invalid  
192  
153  
154  
Minimum pressure parameter was greater than  
193  
setpoint  
194  
Minimum pressure parameter was greater than  
time of day setpoint  
195  
Lead Lag backup modulation sensor setting was  
invalid  
155  
156  
CH modulation rate source parameter was invalid  
196  
197  
198  
199  
200  
201  
202  
Lead Lag slave mode setting was invalid  
Lead Lag rate allocation setting was invalid  
Lead selection setting was invalid  
Steam modulation rate source parameter was  
invalid  
DHW Parameter Errors  
Lag selection setting was invalid  
157  
158  
159  
160  
161  
162  
163  
164  
165  
166  
167  
168  
169  
170  
DHW demand source was invalid  
DHW P-gain was invalid  
Lead Lag slave return setting was invalid  
Lead Lag add stage method setting was invalid  
DHW I-gain was invalid  
STAT may not be a Lead Lag CH demand source  
when Remote Stat is enabled  
DHW D-gain was invalid  
DHW OFF hysteresis was invalid  
DHW ON hysteresis was invalid  
DHW hysteresis step time was invalid  
DHW sensor type was invalid  
203  
Lead Lag base load rate setting was invalid  
Lead Lag Operation Faults  
204  
205  
206  
207  
Lead Lag master was suspended due to fault  
Lead Lag slave was suspended due to fault  
Lead Lag header temperature was invalid  
Inlet sensor type was invalid for DHW  
Outlet sensor type was invalid for DHW  
DHW Storage OFF hysteresis was invalid  
DHW Storage ON hysteresis was invalid  
DHW modulation sensor type was invalid  
Lead Lag was suspended due to no enabled  
Program Module installed  
208  
209  
210  
211  
212  
213  
Lead Lag slave session has timed out  
Too many Lead Lag slaves were detected  
Lead Lag slave was discovered  
DHW modulation sensor was not compatible for  
AUTO mode  
Incompatible Lead Lag slave was discovered  
No base load rate was set for Lead Lag slave  
DHW Operation Faults  
171  
172  
173  
174  
175  
176  
DHW control was suspended due to fault  
DHW temperature was invalid  
Lead Lag slave unable to fire before demand to  
fire delay expired  
DHW inlet temperature was invalid  
DHW outlet temperature was invalid  
DHW high limit must be disabled for AUTO mode  
214  
Adding Lead Lag slave aborted due to add  
requirement change  
215  
216  
No Lead Lag slaves available to service demand  
DHW sensor type was not compatible for AUTO  
mode  
No Lead Lag active service was set due to  
demand priority conflicts  
177  
178  
DHW priority source setting was invalid  
DHW priority method setting was invalid  
CH Operation Faults (continued)  
CH S5 (J8 terminal 11) sensor was invalid  
CH inlet temperature was invalid  
CH S10 (J10 terminal 7) sensor was invalid  
Lead Lag CH setpoint source was invalid  
Lead Lag Parameter errors  
217  
218  
219  
No Lead Lag add stage method was specified  
No Lead Lag drop stage method was specified  
Using backup lead lag header sensor due to  
sensor failure  
179  
180  
181  
182  
Frost Protection Faults  
220  
221  
222  
223  
224  
Lead Lag frost protection rate was invalid  
Lead Lag drop stage method setting was invalid  
CH frost protection temperature was invalid  
CH frost protection inlet temperature was invalid  
DHW frost protection temperature was invalid  
183  
184  
185  
186  
187  
188  
189  
190  
Lead Lag P-gain was invalid  
Lead Lag I-gain was invalid  
225-226 RESERVED  
Lead Lag D-gain was invalid  
227  
DHW priority override time was not derated due to  
invalid outdoor temperature  
Lead Lag OFF hysteresis was invalid  
Lead Lag ON hysteresis was invalid  
Lead Lag slave enable was invalid  
Lead Lag hysteresis step time was invalid  
No Lead lag Modbus port was assigned  
228  
Warm weather shutdown was not checked due to  
invalid outdoor temperature  
229  
230  
Lead Lag slave communication timeout  
RESERVED  
71  
CODE  
231  
DESCRIPTION  
CODE  
DESCRIPTION  
Lead Lag CH setpoint was invalid  
274  
Abnormal Recycle: Demand off during Pilot Flame  
Establishing Period  
232  
Lead Lag CH time of day setpoint was invalid  
LL outdoor temperature was invalid  
275  
276  
277  
Abnormal Recycle: LCI off during Drive to Purge  
233  
Rate  
234  
Lead Lag ODR time of day setpoint was invalid  
Abnormal Recycle: LCI off during Measured Purge  
Time  
235  
Lead Lag ODR time of day setpoint exceeded  
normal setpoint  
Abnormal Recycle: LCI off during Drive to Lightoff  
236  
237  
Lead Lag ODR max outdoor temperature was  
invalid  
Rate  
278  
279  
280  
Abnormal Recycle: LCI off during Pre-Ignition test  
Abnormal Recycle: LCI off during Pre-Ignition time  
Lead Lag ODR min outdoor temperature was  
invalid  
Abnormal Recycle: LCI off during Main Flame  
Establishing Period  
238  
239  
Lead Lag ODR low water temperature was invalid  
Lead Lag ODR outdoor temperature range was  
too small (minimum 12°C / 22°F)  
281  
282  
Abnormal Recycle: LCI off during Ignition period  
Abnormal Recycle: Demand off during Drive to  
240  
Lead Lag ODR water temperature range was too  
small (minimum 12°C / 22°F)  
Purge Rate  
283  
284  
285  
286  
287  
288  
289  
290  
291  
292  
Abnormal Recycle: Demand off during Measured  
Purge Time  
241  
242  
243  
244  
245  
246  
247  
248  
249  
250  
Lead Lag DHW setpoint was invalid  
Lead Lag Mix setpoint was invalid  
Lead Lag CH demand switch was invalid  
Lead Lag CH setpoint source was invalid  
RESERVED  
Abnormal Recycle: Demand off during Drive to  
Lightoff Rate  
Abnormal Recycle: Demand off during Pre-Ignition  
test  
Abnormal Recycle: Demand off during Pre-Ignition  
time  
CH setpoint was invalid  
CH time of day setpoint was invalid  
CH outdoor temperature was invalid  
CH ODR time of day setpoint was invalid  
Abnormal Recycle: Flame was on during Safe  
Check  
Abnormal Recycle: Flame was on during Drive to  
Purge Rate  
CH ODR time of day setpoint exceeds normal  
setpoint  
Abnormal Recycle: Flame was on during  
Measured Purge Time  
251  
252  
253  
254  
255  
256  
257  
258  
259  
260  
261  
262  
263  
264  
CH max outdoor setpoint was invalid  
CH min outdoor setpoint was invalid  
CH min water setpoint was invalid  
CH outdoor temperature range was too small  
CH water temperature range was too small  
Steam setpoint was invalid  
Abnormal Recycle: Flame was on during Drive to  
Lightoff Rate  
Abnormal Recycle: Flame was not on at end of  
Ignition period  
Abnormal Recycle: Flame was lost during Main  
Flame Establishing Period  
Steam time of day setpoint was invalid  
Steam minimum pressure was invalid  
CH ODR min water temperature was invalid  
RESERVED  
293  
294  
295  
296  
Abnormal Recycle: Flame was lost early in Run  
Abnormal Recycle: Flame was lost during Run  
Abnormal Recycle: Leakage test failed  
Abnormal Recycle: Interrupted air flow switch was  
off during Drive to Purge Rate  
DHW setpoint was invalid  
DHW time of day setpoint was invalid  
DHW storage setpoint was invalid  
297  
298  
299  
300  
301  
302  
303  
Abnormal Recycle: Interrupted air flow switch was  
off during Measured Purge Time  
Abnormal Recycle: Interrupted air flow switch was  
off during Drive to Lightoff Rate  
STAT may not be a DHW demand source when  
Remote Stat is enabled  
Abnormal Recycle: Interrupted air flow switch was  
off during Pre-Ignition test  
265-266 RESERVED  
267  
STAT may not be a CH demand source when  
Remote Stat is enabled  
Abnormal Recycle: Interrupted air flow switch was  
off during Pre-Ignition time  
268  
269  
270  
271  
272  
273  
CH 4mA water temperature setting was invalid  
CH 20mA water temperature setting was invalid  
Steam 4mA water temperature setting was invalid  
Steam 20mA water temperature setting was invalid  
Abnormal Recycle: Pressure sensor fault  
Abnormal Recycle: Safety relay drive test failed  
Abnormal Recycle: Interrupted air flow switch was  
off during Main Flame Establishing Period  
Abnormal Recycle: Ignition failed due to  
interrupted air flow switch was off  
Abnormal Recycle: ILK off during Drive to Purge  
Rate  
72  
CODE  
DESCRIPTION  
CODE  
341  
342  
343  
344  
345  
346  
347  
348  
349  
350  
351  
352  
353  
354  
355  
356  
357  
358  
359  
360  
DESCRIPTION  
304  
Abnormal Recycle: ILK off during Measured Purge  
Time  
Abnormal Recycle: Hardware SLO electronics  
Abnormal Recycle: Hardware processor clock  
Abnormal Recycle: Hardware AC phase  
Abnormal Recycle: Hardware A2D mismatch  
Abnormal Recycle: Hardware VSNSR A2D  
Abnormal Recycle: Hardware 28V A2D  
Abnormal Recycle: Hardware HFS IAS shorted  
Abnormal Recycle: Hardware PII INTLK shorted  
Abnormal Recycle: Hardware HFS LCI shorted  
Abnormal Recycle: Hardware HFS LFS shorted  
Abnormal Recycle: Invalid zero crossing  
Abnormal Recycle: fault stack sensor  
Abnormal Recycle: stack limit  
305  
Abnormal Recycle: ILK off during Drive to Lightoff  
Rate  
306  
307  
308  
Abnormal Recycle: ILK off during Pre-Ignition test  
Abnormal Recycle: ILK off during Pre-Ignition time  
Abnormal Recycle: ILK off during Main Flame  
Establishing Period  
309  
310  
311  
Abnormal Recycle: ILK off during Ignition period  
Run was terminated due to ILK was off  
Run was terminated due to interrupted air flow  
switch was off  
312  
313  
314  
Stuck reset switch  
Run was terminated due to fan failure  
Abnormal Recycle: Fan failed during Drive to  
Abnormal Recycle: delta T limit  
Purge Rate  
Abnormal Recycle: fault outlet sensor  
Abnormal Recycle: outlet high limit  
315  
316  
317  
318  
319  
320  
321  
322  
323  
Abnormal Recycle: Fan failed during Measured  
Purge Time  
Abnormal Recycle: fault DHW sensor  
Abnormal Recycle: DHW high limit  
Abnormal Recycle: Fan failed during Drive to  
Lightoff Rate  
Abnormal Recycle: fault inlet sensor  
Abnormal Recycle: Check Parameters Failed  
Internal Errors  
Abnormal Recycle: Fan failed during Pre-Ignition  
test  
Abnormal Recycle: Fan failed during Pre-Ignition  
time  
361  
Internal error: No factory parameters were  
detected in control  
Abnormal Recycle: Fan failed during Ignition  
period  
362  
363  
Internal error: PID iteration frequency was invalid  
Abnormal Recycle: Fan failed during Main Flame  
Establishing Period  
Internal error: Demand-Rate interval time was  
invalid  
Abnormal Recycle: Main Valve off after 10  
seconds of RUN  
364  
Internal error: Factory calibration parameter for  
modulation was invalid  
Abnormal Recycle: Pilot Valve off after 10 seconds  
365  
366  
367  
368  
369  
370  
371  
Internal error: CH PID P-scaler was invalid  
Internal error: CH PID I-scaler was invalid  
Internal error: CH PID D-scaler was invalid  
Internal error: DHW PID P-scaler was invalid  
Internal error: DHW PID I-scaler was invalid  
Internal error: DHW PID D-scaler was invalid  
of RUN  
Abnormal Recycle: Safety Relay off after 10  
seconds of RUN  
324  
325  
326  
327  
328  
329  
330  
330  
332  
Abnormal Recycle: Hardware flame bias  
Abnormal Recycle: Hardware static flame  
Abnormal Recycle: Hardware flame current invalid  
Abnormal Recycle: Hardware flame rod short  
Abnormal Recycle: Hardware invalid power  
Abnormal Recycle: Hardware invalid AC line  
Abnormal Recycle: Hardware SLO flame ripple  
Abnormal Recycle: Hardware SLO flame sample  
Internal error: Lead Lag master PID P-scaler was  
invalid  
372  
373  
Internal error: Lead Lag master PID I-scaler was  
invalid  
Internal error: Lead Lag master PID D-scaler was  
invalid  
Abnormal Recycle: Hardware SLO flame bias  
374  
375  
376  
377  
378  
Abnormal Recycle: Hardware flame bias high  
Abnormal Recycle: Hardware flame bias low  
Abnormal Recycle: Hardware flame bias delta high  
Abnormal Recycle: Hardware flame bias delta low  
range  
333  
334  
335  
336  
337  
338  
339  
340  
Abnormal Recycle: Hardware SLO flame bias heat  
Abnormal Recycle: Hardware SLO spark stuck  
Abnormal Recycle: Hardware SLO spark changed  
Abnormal Recycle: Hardware SLO static flame  
Abnormal Recycle: Hardware SLO rod shorted  
Abnormal Recycle: Hardware SLO AD linearity  
Abnormal Recycle: Hardware SLO bias not set  
Abnormal Recycle: Hardware SLO bias shorted  
Abnormal Recycle: Hardware flame bias dynamic  
high  
379  
Abnormal Recycle: Hardware flame bias dynamic  
low  
380  
381  
Abnormal Recycle: Fan Speed Not Proven  
Abnormal Recycle: Fan Speed Range Low  
73  
CODE  
DESCRIPTION  
CODE  
482  
483  
484  
485  
486  
487  
488  
489  
490  
491  
492  
493  
494  
495  
496  
497  
498  
499  
500  
501  
DESCRIPTION  
382  
Abnormal Recycle: Fan Speed Range High  
Internal error: Safety key bit 4 was incorrect  
Internal error: Safety key bit 5 was incorrect  
Internal error: Safety key bit 6 was incorrect  
Internal error: Safety key bit 7 was incorrect  
Internal error: Safety key bit 8 was incorrect  
Internal error: Safety key bit 9 was incorrect  
Internal error: Safety key bit 10 was incorrect  
Internal error: Safety key bit 11 was incorrect  
Internal error: Safety key bit 12 was incorrect  
Internal error: Safety key bit 13 was incorrect  
Internal error: Safety key bit 14 was incorrect  
Internal error: Safety key bit 15 was incorrect  
Internal error: Safety relay timeout  
383-450 RESERVED  
Circulator Errors  
451  
452  
453  
454  
455  
456  
457  
458  
459  
Circulator control was invalid  
Circulator P-gain was invalid  
Circulator I-gain was invalid  
Circulator temperature was invalid  
Circulator outlet temperature was invalid  
Circulator inlet temperature was invalid  
Circulator outdoor temperature was invalid  
Circulator sensor choice was invalid  
Circulator PID setpoint was invalid  
Debug Faults  
460  
461  
LCI lost in run  
Internal error: Safety relay commanded off  
Internal error: Unknown safety error occurred  
Internal error: Safety timer was corrupt  
Internal error: Safety timer was expired  
Internal error: Safety timings  
Abnormal Recycle: Demand lost in run from  
application  
462  
463  
464  
465  
466  
Abnormal Recycle: Demand lost in run due to high  
limit  
Abnormal Recycle: Demand lost in run due to no  
flame  
Internal error: Safety shutdown  
RESERVED  
LCI lost in Combustion Pressure Establishing  
Period  
MIX Errors  
LCI lost in Combustion Pressure Stabilization  
Period  
502  
503  
504  
505  
506  
Mix setpoint was invalid  
Mix time of day setpoint was invalid  
Mix outdoor temperature was invalid  
Mix ODR time of day setpoint was invalid  
RESERVED  
Internal Data Faults  
467  
468  
469  
470  
471  
472  
Internal error: EEPROM write was attempted  
before EEPROM was initialized  
Mix ODR time of day setpoint exceeds normal  
setpoint  
Internal error: EEPROM cycle count address was  
invalid  
507  
508  
509  
510  
511  
512  
513  
514  
515  
516  
517  
518  
519  
520  
521  
522  
523  
524  
525  
526  
Mix ODR max outdoor temperature was invalid  
Mix ODR min outdoor temperature was invalid  
Mix ODR low water temperature was invalid  
Mix ODR outdoor temperature range was invalid  
Mix ODR water temperature range was invalid  
Mix demand switch was invalid  
Internal error: EEPROM days count address was  
invalid  
Internal error: EEPROM hours count address was  
invalid  
Internal error: Lockout record EEPROM index was  
invalid  
Mix ON hysteresis was invalid  
Internal error: Request to write PM status was  
invalid  
Mix OFF hysteresis was invalid  
Mix ODR min water temperature was invalid  
Mix hysteresis step time was invalid  
Mix P-gain was invalid  
473  
474  
Internal error: PM parameter address was invalid  
Internal error: PM safety parameter address was  
invalid  
Mix I-gain was invalid  
475  
Internal error: Invalid record in lockout history was  
removed  
Mix D-gain was invalid  
476  
477  
Internal error: EEPROM write buffer was full  
Mix control was suspended due to fault  
Mix S10 (J10-7) temperature was invalid  
Mix outlet temperature was invalid  
Mix inlet temperature was invalid  
Internal error: Data too large was not written to  
EEPROM  
478  
479  
480  
481  
Internal error: Safety key bit 0 was incorrect  
Internal error: Safety key bit 1 was incorrect  
Internal error: Safety key bit 2 was incorrect  
Internal error: Safety key bit 3 was incorrect  
Mix S5 (J8-11) temperature was invalid  
Mix modulation sensor type was invalid  
Mix ODR min water temperature setpoint was  
invalid  
74  
CODE  
527  
DESCRIPTION  
Mix circulator sensor was invalid  
Mix flow control was invalid  
Mix temperature was invalid  
Mix sensor was invalid  
CODE  
571  
DESCRIPTION  
Heat exchanger high limit response was invalid  
Heat exchanger high limit was exceeded  
528  
572  
529  
573  
Heat exchanger high limit wasn't allowed due to  
stack limit setting  
530  
574  
575  
Heat exchanger high limit wasn't allowed due to  
stack connector setting  
531  
Mix PID setpoint was invalid  
532  
STAT may not be a Mix demand source when  
Remote Stat is enabled  
Heat exchanger high limit delay was not  
configured for recycle response  
533-539 RESERVED  
Pump Errors  
540  
541  
542  
543  
544  
545  
546  
547  
548  
549  
Delta T inlet/outlet enable was invalid  
576  
577  
578  
579  
580  
581  
CH pump output was invalid  
DHW pump output was invalid  
Boiler pump output was invalid  
Auxiliary pump output was invalid  
System pump output was invalid  
Mix pump output was invalid  
Delta T exchanger/outlet enable was invalid  
Delta T inlet/exchanger enable was invalid  
Delta T inlet/outlet degrees was out of range  
Delta T exchanger/outlet degrees was out of range  
Delta T inlet/exchanger degrees was out of range  
Delta T response was invalid  
582-589 RESERVED  
DHW Plate Heat Exchanger Errors  
Delta T inversion limit response was invalid  
Delta T rate limit enable was invalid  
590  
591  
592  
593  
594  
595  
596  
597  
598  
599  
DHW plate preheat setpoint was invalid  
Delta T exchanger/outlet wasn't allowed due to  
stack limit setting  
DHW plate preheat ON hysteresis was invalid  
DHW plate preheat OFF hysteresis was invalid  
Tap detect degrees was out of range  
550  
551  
552  
553  
554  
555  
556  
Delta T inlet/outlet limit was exceeded  
Delta T exchanger/outlet limit was exceeded  
Delta T inlet/exchanger limit was exceeded  
Inlet/outlet inversion occurred  
Tap detect ON hysteresis was invalid  
Inlet - DHW tap stop degrees was out of range  
Outlet - Inlet tap stop degrees was out of range  
DHW tap detect on threshold was invalid  
DHW plate preheat detect on threshold was invalid  
DHW plate preheat detect off threshold was invalid  
Exchanger/outlet inversion occurred  
Inlet/exchanger inversion occurred  
Delta T exchanger/outlet wasn't allowed due to  
stack connector setting  
557  
558  
559  
Delta T inlet/exchanger wasn't allowed due to  
stack limit setting  
Delta T inlet/exchanger wasn't allowed due to  
stack connector setting  
Delta T delay was not configured for recycle  
response  
T Rise Errors  
560  
561  
562  
563  
564  
565  
566  
Outlet T-rise enable was invalid  
Heat exchanger T-rise enable was invalid  
T-rise degrees was out of range  
T-rise response was invalid  
Outlet T-rise limit was exceeded  
Heat exchanger T-rise limit was exceeded  
Heat exchanger T-rise wasn't allowed due to stack  
limit setting  
567  
568  
569  
Heat exchanger T-rise wasn't allowed due to stack  
connector setting  
Outlet T-rise wasn't allowed due to outlet  
connector setting  
T-rise delay was not configured for recycle  
response  
Heat Exchanger High Limit Errors  
570  
Heat exchanger high limit setpoint was out of  
range  
75  
MAINTENANCE PROCEDURES  
MAINTENANCE SCHEDULES  
INSPECT BOILER AREA  
Yearly procedures for Service Technician:  
• Check for reported problems.  
1. Verify that boiler area is free of any combustible materials,  
gasoline and other flammable vapors and liquids.  
2. Verify that air intake area is free of any of the contaminants.  
If any of these are present in the boiler intake air vicinity,  
they must be removed. If they cannot be removed, reinstall  
the air and vent lines per this manual.  
• Check the interior; clean and vacuum if needed.  
• Clean the condensate trap and fill with fresh water.  
• Check for water/gas/flue/ condensate leaks.  
• Ensure flue and air lines in good condition and sealed  
tight  
Inspect boiler interior:  
1. Remove the front access cover and inspect the interior of  
• Check system water pressure/system piping/expansion  
tank  
the boiler.  
2. Vacuumanysedimentfrominsidetheboilerandcomponents.  
• Check control settings.  
Remove any obstructions.  
• Check spark igniter and flame sensors. Clear and clean  
any deposits.  
GENERAL MAINTENANCE  
This is a pre-mix burner system. The flame is not supposed to be  
directly on the burner. The flame should be just above the burner  
deck approximately 1/8” and blue in color, see Figure 77.  
• Check wiring and connections.  
• Perform start-up checkout and performance verification.  
• Flame inspection (stable, uniform)  
• Flame signal (at least 10 microamps at high fire)  
• Clean the heat exchanger if flue temperature is more  
than 54°F (30°C) above return water temperature.  
Test low water flow conditions.  
• Clean the heat exchanger.  
• Remove and clean burner using compressed air.  
Maintenance by Owner:  
Daily:  
• Check boiler area .  
• Check pressure/temperature gauge.  
Monthly:  
FIGURE 77. BURNER FLAMES  
Visually check flame characteristics through the view port located  
on the top head of the boiler. Figure 77 shows the normal flame  
condition.  
• Check vent piping.  
• Check air intake piping (Direct Vent).  
• Check air and vent termination screens.  
• Check relief valve.  
These boilers are designed to give many years of efficient and  
satisfactory service when properly operated and maintained.  
To assure continued good performance, the following  
recommendations are made.  
• Check condensate drain system.  
• Check automatic air vents .  
Every 6 months:  
The area around the unit should be kept clean and free from lint  
and debris. Sweeping the floor around the boiler should be done  
carefully. This will reduce the dust and dirt which may enter the  
burner and heat exchanger, causing improper combustion and  
sooting.  
• Check boiler piping (gas and water) for leaks.  
• Check and operate the pressure relief valve.  
End of season months:  
MAIN BURNER  
• Shut the boiler down (unless boiler used for domestic hot  
water)  
Check main burner every three months for proper flame  
characteristics. The main burner should display the following  
characteristics:  
Make sure the maintenance of the boiler must be performed to  
assure maximum boiler efficiency and reliability. Failure to service  
and maintain the boiler and system could result in equipment  
failure.  
Provide complete combustion of gas.  
Cause rapid ignition and carry over of flame across entire burner.  
Make sure to turn off power to the boiler before any service  
operation on the boiler except as noted otherwise in this  
instruction manual. Failure to turn off electrical power could result  
in electrical shock, causing severe personal injury or death.  
Give reasonably quiet operation during initial ignition, operation  
and extinction.  
Cause no excessive lifting of flame from burner ports.  
76  
 
If the preceding burner characteristics are not evident, check for 5. Loosen the seven bolts on the blower adapter at the base  
accumulation of lint or other foreign material that restricts or blocks  
the air openings to the burner or boiler. To check burners:  
and move the burner ground wire (Green) aside.  
6. Lift the blower adapter and remove the manifold assembly  
up from the 6 studs located on the cover plate and remove  
the burner gasket.  
1. Shut off all gas and electricity to unit. Allow unit to cool.  
2. Remove main burners from unit.  
7. Remove any loose foreign material such as dust or lint with a  
vacuum. Check all ports for blockage. Dislodge any foreign  
material causing blockage. Remove any soot or carbon  
deposits with a rag making sure to remove any lint left on  
the burner by vacuuming again.  
3. Check that burner ports are free of foreign matter.  
4. Clean burner with vacuum cleaner. Do not distort burner  
ports.  
5. Reinstall burners in unit. Ensure that all the screws on the  
burner flange are tightened securely so that the gasket will  
provide a good seal.  
8. Reverse the steps to reassemble the unit.  
9. Restore electrical power and gas supply to the boiler.  
6. Also check for good flow of combustion and ventilating air  
• Put the boiler back in operation by following the Lighting  
and Operating instructions in this manual.  
to the unit.  
After placing the boiler in operation, check the ignition system  
safety shut-off devices for proper operation. To accomplish this  
with the main burner operating, close the valve on the manifold.  
Within four seconds the main burners should extinguish. If this  
does not occur immediately, discontinue gas supply by closing  
main manual shut-off and call a qualified serviceman to correct  
the situation. If the burners extinguish, then light boiler in  
accordance with lighting and operating instructions.  
• Check for gas leaks and proper boiler and vent  
operation.  
PRESSURE RELIEF VALVE  
The pressure relief valve should be opened at least twice a year  
to check its working condition. This will aid in assuring proper  
pressure relief protection. Lift the lever at the top of the valve  
several times until the valve seats properly and operates freely.  
Any safety devices including low water cutoffs used in conjunction  
with this boiler should receive periodic (every six months)  
inspection to assure proper operation. A low water cutoff device  
of the float type should be flushed every six months. Periodic  
checks, at least twice a year, should be made for water leaks.  
More frequent inspections may be necessary depending on  
water conditions.  
The boiler-mounted gas and electrical controls have been  
designed to give both dependable service and long life.  
However, malfunction can occur, as with any piece of equipment.  
It is therefore recommended that all components be checked  
periodically by a qualified serviceman for proper operation.  
BLOWER COMPARTMENT  
The blower compartment should be cleaned annually to remove  
any dirt and lint that may have accumulated in the compartment  
or on the blower and motor. Buildups of dirt and lint on the  
blower and motor can create excessive loads on the motor  
resulting in higher that normal operating temperatures and  
possible shortened service life.  
BURNER MAINTENANCE  
Qualified service agent should follow this procedure when the  
boiler’s burner needs cleaning.  
1. Turn off the electrical power to the boiler and close the main  
manual gas shutoff valve(s). Allow the boiler parts to cool  
before disassembly.  
AIR FILTER BOX  
2. Loosen the flange and separate the gas train from the  
manifold assembly.  
The air filter box should be cleaned every three months to remove  
any dust and debris that may have accumulated in the air filter  
or the filter housing. Buildups of dust on the air filter can block  
the air intake into the boiler. Air filter can washed and cleaned  
with water.  
3. Separate the burner from the blower adapter by first  
removing the four (4) bolts and subsequently, the blower  
gaskets. The blower should be free to move at this point.  
4. For Direct Vent units: It is necessary to loosen and slide  
the rubber coupling on the blower adaptor in order to  
move the blower.  
77  
CONDENSATE REMOVAL SYSTEM  
1. Turn off the electrical power, and manual gas shut-off.  
Allow boiler parts to cool before disassembly.  
Due to the highly efficient operation of this unit, condensate  
is formed during operation and must be removed by the  
condensate drain systems. Inspect the condensate drains  
and tubes at least once a month and insure they will allow  
the free flow of condensate at all times. The system must  
be inspected more frequently in cold weather if the drain  
system is located in an area, such as along the floor, where  
freezing temperatures are likely to occur. The condensate  
drain system must be protected against freezing. Contact a  
qualified service agent to inspect and correct the condition if  
freezing of the condensate lines is a problem.  
2. Remove the vent pipe.  
Check parts and chimney for obstructions and clean as  
necessary.  
3. Remove burner from boiler and other metal parts as required  
to clean as necessary.  
Refer to parts list for disassembly aid.  
4. Clean and reinstall the parts removed in steps 2 and 3.  
Be sure the vent pipe has a minimum upward pitch of 1/4"  
per foot (2 cm/m) of length and is sealed as necessary.  
The transparent drain lines and condensate drain on the bottom  
of the vent collector should be visually inspected at one month  
intervals for blockage, particularly in the areas of the loops in the  
lines which trap a small amount of condensate, and the exit point  
of the vent collector drain. Condensate in portions of the line  
other than the loop area indicates a blockage in the drain line.  
Flush the lines with air or water and clear or replace the blocked  
portions of the line as necessary. Note that areas of the drain  
line which include a sag or low spot in the line will also form a  
condensate trap which can be removed by levelling the tube and  
does not indicate a blocked system.  
5. Restore electrical power and gas supply to boiler.  
Check for gas leaks and proper boiler and vent operation.  
HEAT EXCHANGER MAINTENANCE  
1. Shut down the boiler:  
• Turn Off gas to the boiler.  
• Do not drain the boiler unless it will be exposed to  
freezing temperatures. If using freeze prevention fluid in  
system, do not drain.  
Inspect the metal vent drain and vent collector drain connectors  
at six month intervals. Remove the hoses from the connections,  
then check with a small wooden dowel or plastic rod passed  
up through the metal connection to insure the passage is clear,  
using caution to not bend or damage the connector. Call a  
qualified service agent to inspect and correct the problem if any  
obstructions are found in the connectors. Replace all hoses and  
clamps immediately after inspection and before starting the boiler  
in accordance with the Lighting and Operating Instructions. Do not  
operate the boiler unless all condensate drain lines are properly  
connected and working. When a means to neutralize condensate  
has been installed you must also follow operating, inspection and  
maintenance procedures specified by the manufacturer of the  
product. Inspect the installed device to insure that it does not  
cause condensate to remain in the boiler or vent for any reason.  
2. Ensure the boiler cools down to room temperature.  
3. Remove the nuts securing the heat exchanger access cover  
to the heat exchanger and set aside.  
4. Remove the heat exchanger access cover, burner, and gas  
train assembly.  
Note: The boiler contains ceramic fiber materials. Failure to  
comply could result in severe personal injury.  
5. Remove the condensate hose from the heat exchanger end.  
Connect a field supplied 3/4" diameter hose to a drain pan.  
6. Use a vacuum cleaner to remove any deposits/ debris on the  
boiler heating surfaces. Do not use any solvent.  
7. Brush the heat exchanger while dry using a nylon bristle  
brush. Re-vacuum the heat exchanger.  
8. Finish cleaning using a clean cloth dampened with warm  
VENTING MAINTENANCE  
water. Rinse out debris with a low pressure water supply.  
9. Allow the heat exchanger to dry completely.  
It is recommended that the intake and exhaust piping of the  
boiler be checked every 6 months for dust, condensate leakage, 10. Remove the rear refractory cover from the back of the  
deterioration and carbon deposits.  
combustion chamber of the heat exchanger and reassemble.  
11. Close isolation valves on piping to isolate the boiler from  
system. Attach a hose to the boiler drain and flush boiler  
thoroughly with clean water by using purging valves to allow  
water to flow through the water make-up line to the boiler.  
12. Replace the access cover and restore the boiler for operation.  
Qualified service agent should follow this procedure when the  
boiler’s intake and exhaust piping need cleaning:  
78  
HANDLING CERAMIC FIBER MATERIALS  
Removal of combustion chamber lining:  
The combustion chamber insulation in this boiler contains ceramic  
fiber material. Ceramic fibers can be converted to cristobalite in  
very high temperature applications. The International Agency for  
Research on Cancer (IARC) has concluded, “Crystalline silica  
in the form of quartz or cristobalite from occupational sources  
is carcinogenic to humans (Group 1).” Normal operating  
temperatures in this boiler are below the level to convert ceramic  
fibers to cristobalite.  
The ceramic fiber material used in this boiler is an irritant; hence  
when handling or replacing the ceramic materials it is advisable  
that the installer follow these safety guidelines.  
1. Avoid breathing dust and contact with skin and eyes.  
• Use NIOSH certified dust respirator (N95). This type  
of respirator is based on the OSHA requirements for  
cristobalite at the time this document was written. Other  
types of respirators may be needed depending on the  
job site conditions. Current NIOSH recommendations  
gov/niosh/homepage.html. NIOSH approved respirators,  
manufacturers, and phone numbers are also listed on  
this website.  
• Wear long-sleeved, loose fitting clothing, gloves, and eye  
protection.  
2. Apply enough water to the combustion chamber lining to  
prevent airborne dust.  
3. Remove the combustion chamber lining from the boiler and  
place it in a plastic bag for disposal.  
4. Wash potentially contaminated clothes separately from  
other clothing. Rinse clothes washer thoroughly.  
NIOSH stated First Aid:  
• Eye: Irrigate immediately.  
• Breathing: Fresh air.  
REPLACEMENT PARTS  
Replacement parts may be ordered through A. O. Smith dealers,  
authorized servicers or distributors. Refer to the Yellow Pages  
for where to call or contact (in United States) the A. O. Smith  
Water Products Company, 500 Tennessee Waltz Parkway,  
Ashland City, TN 37015, 1-800-433-2545 or (in Canada) A.  
O. Smith Enterprises Ltd., 599 Hill Street West, Fergus, ON  
N1M2X1, 1-888-479-2837. When ordering parts be sure to state  
the quantity, part number and description of the item including the  
complete model and serial number as it appears on the product.  
Refer to the parts list for more information.  
For Technical Assistance call A. O. Smith Technical Information  
Center at 1-800-527-1953.  
79  
PIPING DIAGRAMS  
80  
 
S T O R A G E T A N K  
A O S  
81  
 
LIMITED WARRANTY  
A. O. Smith Corporation, the warrantor, extends the following LIMITED WARRANTY to the owner of this boiler:  
1. If within TEN years after initial installation of the boiler, a heat exchanger or gas burner should prove upon examination by the warrantor to be defective in  
material or workmanship, the warrantor, at his option will exchange or repair such part or portion. This term is reduced to FIVE years if this boiler is used  
for water heating purposes other than hydronic space heating.  
a. This warranty is extended to the owner for all other parts or portion during the FIRST year following initial installation of this boiler.  
b. The warranty on the repair or replacement of the part or portion will be limited to the unexpired term of the original warranty.  
2. CONDITIONS AND EXCEPTIONS  
This warranty should apply only when the boiler is installed in accordance with local plumbing and building codes, ordinances and regulations, the printed  
instructions provided with it and good industry practices. In addition, a pressure relief valve, certified by C.S.A. and approved by the American Society of  
Mechanical Engineers, must have been installed and fresh water used for filling and make-up purposes.  
a. This warranty should apply only when the boiler is used:  
(1) with outlet water temperatures not exceeding the maximum setting of its operative and/or high limit control;  
(2) at water pressure not exceeding the working pressure shown on the boiler;  
(3) when filled with boiler water, free to circulate at all times and with the heat exchanger free of damaging scale deposits;  
(4) in a non-corrosive and non-contaminated atmosphere;  
(5) in the United States, its territories or possessions, and Canada;  
(6) at a water velocity flow rate not exceeding or below the boiler’s designed rates;  
(7) indoor installation only.  
b. Any accident to the boiler, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form, or any attempt to repair leaks  
in the heat exchanger will void this warranty.  
3. SERVICE AND REPAIR EXPENSE  
Under this limited warranty the warrantor will provide only a replacement part. The owner is responsible for all other costs. Such costs may include but are  
not limited to:  
a. Labor charges for service, removal, repair, or reinstallation of the component part;  
b. Shipping, delivery, handling, and administrative charges for forwarding the replacement part from the nearest distributor and returning the claimed defec-  
tive part to such distributor.  
c. All cost necessary or incidental for any material and/or permits required for installation of the replacement.  
4. LIMITATIONS ON IMPLIED WARRANTIES  
Implied warranties, including any warranty of merchantability imposed on the sale of this boiler under state or provincial law are limited to one (1) year  
duration for the boiler or any of its parts. Some states and provinces do not allow limitations on how long an implied warranty lasts, so the above limitation  
may not apply to you.  
5. CLAIM PROCEDURE  
Any claim under this warranty should be initiated with the dealer who sold the boiler, or with any other dealer handling the warrantor’s products. If this is  
not practicable, the owner should contact:  
U.S. Customers  
Canadian Customers  
A. O. Smith Corporation  
500 Tennessee Waltz Parkway  
Ashland City, TN 37015  
Telephone: 800-527-1953  
A. O. Smith Enterprises Ltd.  
599 Hill Street West  
Fergus, ON N1M 2X1  
Telephone: 1-888-479-2837  
a. The warrantor will only honor replacement with identical or similar parts thereof which are manufactured or distributed by the warrantor.  
b. Dealer replacements are made subject to in-warranty validation by warrantor.  
6. DISCLAIMERS  
NO OTHER EXPRESS WARRANTY HAS BEEN OR WILLBE MADE ON BEHALF OF THE WARRANTOR WITH RESPECTTO THE MERCHANTABILITY OF  
THE BOILER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE BOILER. THE WARRANTOR Should NOT BE RESPONSIBLE  
FOR WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONALPROPERTY, OR OTHER CONSEQUENTIAL  
DAMAGE. THE WARRANTOR Should NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS OR  
PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR TORT.  
a. Some states and provinces do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or exclusions may  
not apply to you.  
b. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province.  
Fill in the following for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the boiler’s rating plate.  
Owner______________________________________________________________________________________________________________________________________  
InstallationAddress_________________________________________________________________________________________________________________________  
City and State__________________________________________________________________________________ Zip Code __________________________________  
Date Installed____________________ Model No. __________________________________________Serial No. ___________________________________________  
Dealer’s Name___________________________________________________________________________ Phone No._______________________________________  
Dealer’s Address ________________________________________________________________________________________________________________________  
______________________________________________________________________________________________________________________________________  
FILL IN WARRANTY AND KEEP FOR FUTURE REFERENCE  
82  
25589 Highway 1, McBee, SC 29101  
Technical Support: 800-527-1953 • Parts: 800-433-2545 • Fax: 800-644-9306  
83  

AO Smith Boiler GB 2100 User Manual
AO Smith Water Heater BFM 30 User Guide
AO Smith Water Heater GAHH 40 100 User Manual
AO Smith Water Heater TJV 120M User Manual
AO Smith Water Heater TWI 45 190 User Manual