Commercial Storage Tanks
CUSTOM-LINE FACTORY JACKETED AND
INSULATED STORAGE TANKS
MODELS
TJV TJH
AND
Large volume tanks are designed for storing potable water. Fitting locations
of these custom-line tanks match the needs of normal installations plus those
®
for the A. O. Smith Cer-Temp 80 and Shure-Temp systems.
FEATURES
STANDARD SIZES FROM 140 TO 1,000 GALLONS A. O. Smith stocks vertical
factory jacketed and insulated tanks from 140 gallons up to 1,000 gallons for
fast delivery and retrofit applications. All stock tanks are glass-lined with
standard tank openings as shown on following pages. For custom or larger
capacities, see our custom line tanks or consult your factory representatives.
ASME CODE CONSTRUCTION - All tanks are constructed to the requirements of
the ASME. ASME code tanks are available in 100, 125, 150 and 160 psi working pressures
(125 psi working pressure - standard). Consult factory for ASME code tanks with greater
or lesser working pressures, with special configurations or materials.
INSULATION - Entire tank is surrounded with high density fiber
glass insulation to reduce costly heat loss; non-sagging and
vermin-proof. To meet ASHRAE 90.1 (current standard) depth of
insulation cavity requires use of remote bulb-type tank
temperature control and thermometer.
CABINET - Heavy gauge steel with high quality powder coat paint
provides additional insulating qualities for greater energy savings.
LININGS AND COATINGS - Each lining and coating has
particular capabilities and limitations. Please consult the
factory for recommendations on the uses of linings for specific applications.
Thorough investigation on the service life of steel tanks with protective coatings
or linings has led to the recommendations of the following linings:
■
Glass-lined (Standard) - These are normally stocked tanks for water storage up to 180 F,
with glass lining to prevent corrosion and addition of rust to water. The glass lining was
developed over many years of ceramic research for a wide variety of conditions.
■
Cement - A special formulation of cement provides excellent corrosion protection. Available
on 200 gallon and larger sizes. A manhole or handhole is included for application of cement lining.
■
Epoxy - The application of specially formulated epoxy makes this lining suitable for cold or hot
water storage. A manhole or handhole is included for application of epoxy lining. Available on 200
gallon and larger sizes.
CATHODIC PROTECTION - Glass-lined, cement and epoxy tanks are furnished with
anodes designed for maximum protection.
OPTIONAL
ACCESSORIES - Tanks will be supplied with the fittings located
as indicated on the drawings unless specified otherwise. A
manhole or handhole is included on cement or epoxy tanks.
A manhole or handhole is optional on glass-lined tanks.
CRN
Page 1 of 4
Revised May 2008
AOSTT35200
Download from Www.Somanuals.com. All Manuals Search And Download.
Commercial Storage Tanks
STORAGE TANK SELECTION
TJV-140 THRU TJV-1000
FIGURE 1.
NOTE: Inspection openings, i.e., handholes and manholes, are optional and are to be included with glass lined tanks
only when specified. Tanks so equipped are f.o.b. Seattle.
Other tanks to 66” diameter and 3500 gallon are available on special order.
All openings Female Pipe Thread except as noted.
“F” opening Male Pipe Thread.
MODEL AND
GALLON
CAPACITY
TJV-140
TJV-200
TJV-250
TJV-350
TJV-400
TJVT-500
TJV-500
TJV-750
TJV-1000
A
B
C
D
51
E
F
G
2 1/2
2 1/2
2 1/2
2 1/2
2 1/2
3
H
87
30
36
36
42
42
48
54
54
54
21 1/2
22
8
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
6 3/8
83
45
10
10
14
14
16
18
18
18
7 3/4
93
22
58
7 3/4
97
24 1/2
24 1/2
27
54
9 1/2
105
100
84
61
9 1/2
52
11 5/16
12 3/4
12 3/4
12 3/4
27 3/4
27 3/4
27 3/4
33 1/4
65 1/2
97 1/2
3
116
150
3
3
Page 2 of 4
AOSTT35200
Download from Www.Somanuals.com. All Manuals Search And Download.
Commercial Storage Tanks
STORAGE TANK SELECTION
TJH-200 THRU TJH-1000
FIGURE 2.
NOTE: Inspection openings, i.e., handholes and manholes, are optional and are to be included with glass lined tanks
only when specified. Tanks so equipped are f.o.b. Seattle.
Other tanks to 66” diameter and 3500 gallon are available on special order.
All openings Female Pipe Thread except as noted.
MODEL AND
GALLON
CAPACITY
TJH-200
TJH-350
TJH-400
TJHT-500
TJH-500
TJH-750
TJH-1000
A
B
C
D
E
2 1/2
2 1/2
2 1/2
3
F
G
H
16
41
47
47
53
59
59
59
36
42
42
48
54
54
54
77
16
11
10
10
11
12
12
11
23
26
26
29
32
32
32
93
17 1/2
17 1/2
21
22 1/2
26
99
94
19 1/2
11
79
22 3/4
22 3/4
22 3/4
3
111
143
3
27
3
43
OPTIONAL
■
■
Handle or 11” x 16” manholes
Additional openings
Page 3 of 4
AOSTT35200
Download from Www.Somanuals.com. All Manuals Search And Download.
Commercial Storage Tanks
LIMITED WARRANTY OUTLINES
GLASS-LINED, CEMENT, EPOXY: If the tank should leak anytime
during the first five years, under the terms of the warranty,
A. O. Smith will repair or replace the tank;
installation, laborand handling extra.
BLACK STEEL: If the tank should leak on installation, under the
terms of the warranty, A. O. Smith will repair or replace the tank;
installation, labor and handling extra.
NOTE: THIS OUTLINE IS NOT A WARRANTY. For complete
information, consult the written warranty or A. O. Smith Water
Products Company.Warranty does not apply to product installed
outside of theUnited States of America or its territorial possessions
and Canada.
SUGGESTED SPECIFICATION
SAMPLE SPECIFICATION FOR CUSTOM-LINE STORAGE TANKS
When jacketed or insulated these models meet or exceed the thermal efficiency and standby loss requirements of ASHRAE 90.1 (current standard).
ASME storage tank to be A. O. Smith Custom-Line model ______________. Capacity to be ___________gallons with a diameter of _______ inches. Tank(s) shall be constructed and
stamped according to ASME specifications for __________ psi working pressure. Manhole (11 x 15), handhole (4x6) or inspection openings (2-2˝) shall be installed in accordance with
ASME code requirements and manufacturer(s) standard practice. Tank to be constructed of (carbon steel) _________. Lining shall be (glass, epoxy, cement) ______________. Tank(s) lined
with (glass, cement, epoxy) _____________lining shall be equipped with the number and size of magnesium anode rod(s) sufficient to provide adequate protection for the tank lining.
Tank shall be (vertical, horizontal) _______________ design and provided with (four) ___________ (angle iron legs, threaded leg socket(s)) _____________ ring base, ___________ saddles.
SAMPLE SPECIFICATION FOR TANK HEATERS
Tank heaters shall be Model No. ____________ 3/4˝ OD 20 gauge copper “U” tubes. Heater to have ________ square feet of heating surface to heat ____________ gallons per hour from
_____________ degrees F to ____________ degrees F with heating media of ____________psi steam (or _________ degrees F boiler water). The element shall be constructed so that the
entire section can be removed from the tank for cleaning and inspection.
For Technical Information and Automated Fax Service, call 800-527-1953. A.O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised May 2008
Page 4 of 4
AOSTT35200
Download from Www.Somanuals.com. All Manuals Search And Download.
|